Modbus is a serial communication protocol used for transmitting information over serial lines between electronic devices. The device requesting the information is called “Master”, while devices supplying the requested information are
“Slaves”. When it comes to planning data communication for open, multi-vendor industrial control systems, Modbus is
the first choice of end users and integrators alike.
The Modbus/RTU protocol defines how a “master” device polls one or more “slave” devices to read and write data in
real time by means of RS232, RS422, or RS485 serial data communication. Modbus/TCP, an extension of Modbus/RTU,
defines how Modbus/RTU and Modbus/ASCII messages are encoded within and transported over TCP/IP-based networks. Modbus/TCP is just as simple to implement and flexible to apply as the original Modbus/RTU.
1.1Physical layer
New Systemair controls have standard and readily available Modbus/RTU over three-wire (A, B and GND) RS485 on the
Connection Board (CB) and Modbus/TCP over TCP/IP using Internet Access Module (available as an accessory - Art. No.
211243). For Modbus/TCP connection over TCP/IP using Internet Access Module refer to the IAM quick guide.
Slave address: 1 to 247
Baud rate: 9600 to 115200
Parity: None, Even, Odd
Stop bits: 1 (fixed)
Parameters can be changed in Modbus page (Service -> Communication -> Modbus) in the Control Panel.
1
1.2Transmission modes
The registers are Input registers (read-only) and Holding registers (read-write) when using Modbus/RTU and Holding
registers (read-write) when using Modbus/TCP.
All registers are 16 bit Integers.
Table 1 Signal types used
Unsigned Integers
Signed Integers
I
I*
Table 2 Register types used
Input Registers
16-bit quantity, Analog Input Register provided by an I/O system, read-only, Modbus Function
04
Holding registers16-bit quantity, analog output HR alterable by an application program, read-write , Modbus
function 03 / 06 / 16
2Modbus variable list
Tables below provides an extensive list of Modbus variables used in the system grouped according to the functionality
the variables are related to.
2.1Demand Control
Symbolic register name
REG_DEMC_RH_HIGHESTI
REG_DEMC_CO2_HIGHESTI
REG_DEMC_RH_PI_SPI
REG_DEMC_RH_PI_FEEDBACKI
REG_DEMC_RH_PI_OUTPUTI
| 30
Sig.
Modbus Reg. typeMod-
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
MinMaxDescription
bus
Adr.
10010100
100202000
10110100
10120100
1019
Highest value of all RH sensors
Highest value of all CO2 sensors
Set point for RH demand control
Sensor value for RH demand control
Output value for RH demand control.(1):
Depends on regulation type. Value can be
%, RPM, Pressure or Flow
| Modbus variable list
2
Symbolic register name
REG_DEMC_CO2_PI_SPI
REG_DEMC_CO2_PI_FEEDBACKI
REG_DEMC_CO2_PI_OUTPUTI
REG_DEMC_RH_SETTINGS_PBANDI
REG_DEMC_RH_SETTINGS_SP_SUMMERI
REG_DEMC_RH_SETTINGS_SP_WINTERI
REG_DEMC_RH_SETTINGS_ON_OFFI
REG_SUMMER_WINTERI
REG_DEMC_CO2_SETTINGS_PBANDI
REG_DEMC_CO2_SETTINGS_SPI
REG_DEMC_CO2_SETTINGS_ON_OFFI
REG_IAQ_SPEED_LEVEL_MINI
REG_IAQ_SPEED_LEVEL_MAXI
REG_IAQ_LEVELI
Sig.
Modbus Reg. typeMod-
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
MinMaxDescription
bus
Adr.
102102000
102202000
1029
10311100
103310100
103410100
103501
103901
1041502000
10431002000
104401
112123
112235
112302
Set point for CO2 demand control
Sensor value for CO2 demand control
Output value for CO2 demand control(1):
Depends on regulation type. Value can be
%, RPM, Pressure or Flow
Pband setting for RH demand control
Set point setting for RH demand control
during (temperature based) winter time
Set point setting for RH demand control
during (temperature based) summer time
Flag indicating if RH demand control is
allowed
Actual seasson for Demand Control0:
Summer1: Winter
Pband setting for CO2 demand control
Set point setting for CO2 demand control
Flag indicating if CO2 demand control is
allowed
Minimum level for Demand Control2: Low3:
Normal
Maximum level for user Demand Control3:
Normal4: High5: Maximum
Actual IAQ level:0: Economic1: Good2:
Improving
2.2User modes
Symbolic register name
REG_USERMODE_HOLIDAY_TIMEI
REG_USERMODE_AWAY_TIMEI
REG_USERMODE_FIREPLACE_TIMEI
REG_USERMODE_REFRESH_TIMEI
REG_USERMODE_CROWDED_TIMEI
REG_USERMODE_REMAINING_TIME_LI
REG_USERMODE_REMAINING_TIME_HI
REG_USERMODE_CROWDED_AIRFLOW_
LEVEL_SAF
REG_USERMODE_CROWDED_AIRFLOW_
LEVEL_EAF
REG_USERMODE_REFRESH_AIRFLOW_
LEVEL_SAF
REG_USERMODE_REFRESH_AIRFLOW_
LEVEL_EAF
REG_USERMODE_FIREPLACE_AIRFLOW_
LEVEL_SAF
Sig.
Modbus Reg. typeMod-
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
I
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
MinMaxDescription
bus
Adr.
11011365
1102172
1103160
11041240
110518
1111
1112
113535
113635
113735
113835
113935
Time delay setting for user mode Holiday
Time delay setting for user mode Away
Time delay setting for user mode Fire Place
Time delay setting for user mode Refresh
Time delay setting for user mode Crowded
Remaining time for the state Holiday/
Away/Fire Place/Refresh/Crowded
Remaining time for the state Holiday/
Away/Fire Place/Refresh/Crowded
Fan speed level for mode Crowded3:
Normal4: High5: Maximum
Fan speed level for mode Crowded3:
Normal4: High5: Maximum
Fan speed level for mode Refresh3:
Normal4: High5: Maximum
Fan speed level for mode Refresh3:
Normal4: High5: Maximum
Fan speed level for mode Fire Place3:
Normal4: High5: Maximum
| 30
Modbus variable list |
3
Symbolic register name
REG_USERMODE_FIREPLACE_AIRFLOW_
LEVEL_EAF
REG_USERMODE_AWAY_AIRFLOW_
LEVEL_SAF
REG_USERMODE_AWAY_AIRFLOW_
LEVEL_EAF
REG_USERMODE_HOLIDAY_AIRFLOW_
LEVEL_SAF
REG_USERMODE_HOLIDAY_AIRFLOW_
LEVEL_EAF
REG_USERMODE_COOKERHOOD_
AIRFLOW_LEVEL_SAF
REG_USERMODE_COOKERHOOD_
AIRFLOW_LEVEL_EAF
REG_USERMODE_VACUUMCLEANER_
AIRFLOW_LEVEL_SAF
REG_USERMODE_VACUUMCLEANER_
AIRFLOW_LEVEL_EAF
REG_USERMODE_CROWDED_T_OFFSET
REG_USERMODE_MODEI
REG_USERMODE_HMI_CHANGE_
REQUEST
REG_CDI_1_AIRFLOW_LEVEL_SAFI
REG_CDI_1_AIRFLOW_LEVEL_EAFI
REG_CDI_2_AIRFLOW_LEVEL_SAFI
REG_CDI_2_AIRFLOW_LEVEL_EAFI
REG_CDI_3_AIRFLOW_LEVEL_SAFI
REG_CDI_3_AIRFLOW_LEVEL_EAFI
REG_PRESSURE_GUARD_AIRFLOW_
LEVEL_SAF
REG_PRESSURE_GUARD_AIRFLOW_
LEVEL_EAF
REG_SENSOR_DI_AWAYI
REG_SENSOR_DI_HOLIDAYI
REG_SENSOR_DI_FIREPLACEI
Sig.
Modbus Reg. typeMod-
I
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
Holding Register
I*
(Function 03/06/16)
Read Input Register
(Function 04)
I
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
MinMaxDescription
bus
Adr.
114013
114103
114203
114303
114403
114515
114615
114715
114815
1151-1000
1161012
116207
117105
117205
117305
117405
117505
117605
117705
117805
1230101
1230201
1230301
Fan speed level for mode Fire Place1:
Minimum2: Low3: Normal
Fan speed level for mode Away.0: Off(1)1:
Minimum2: Low3: Normal.(1): value Off
only allowed if contents of register REG_
FAN_MANUAL_STOP_ALLOWED is 1.
Fan speed level for mode Away.0: Off(1)1:
Minimum2: Low3: Normal.(1): value Off
only allowed if contents of register REG_
FAN_MANUAL_STOP_ALLOWED is 1.
Fan speed level for mode Holiday.0: Off(1)
1: Minimum2: Low3: Normal.(1): value Off
only allowed if contents of register REG_
FAN_MANUAL_STOP_ALLOWED is 1.
Fan speed level for mode Holiday.0: Off(1)
1: Minimum2: Low3: Normal.(1): value Off
only allowed if contents of register REG_
FAN_MANUAL_STOP_ALLOWED is 1.
Fan speed level for mode Cooker Hood2:
Low3: Normal4: High
Fan speed level for mode Cooker Hood1:
Minimum2: Low3: Normal
Fan speed level for mode Vacuum Cleaner2:
Low3: Normal4: High
Fan speed level for mode Vacuum Cleaner1:
Minimum2: Low3: Normal
Temperature setpoint offset for user mode
Crowded
Active User mode.0: Auto1: Manual2:
Crowded3: Refresh4: Fireplace5: Away6:
Holiday7: Cooker Hood8: Vacuum Cleaner9:
CDI110: CDI211: CDI312: PressureGuard
New desired user mode as requested by
HMI0: None1: AUTO2: Manual 3: Crowded4:
Refresh5: Fireplace6: Away7: Holiday
Fan speed level for configurable digital input
1.0: Off1: Minimum2: Low3: Normal4:
High5: Maximum
Fan speed level for configurable digital input
1.0: Off1: Minimum2: Low3: Normal4:
High5: Maximum
Fan speed level for configurable digital input
2.0: Off1: Minimum2: Low3: Normal4:
High5: Maximum
Fan speed level for configurable digital input
2.0: Off1: Minimum2: Low3: Normal4:
High5: Maximum
Fan speed level for configurable digital input
3.0: Off1: Minimum2: Low3: Normal4:
High5: Maximum
Fan speed level for configurable digital input
3.0: Off1: Minimum2: Low3: Normal4:
High5: Maximum
Fan speed level for configurable pressure
guard function.0: Off1: Minimum2: Low3:
Normal4: High5: Maximum
Fan speed level for configurable pressure
guard function.0: Off1: Minimum2: Low3:
Normal4: High5: Maximum
Value of physical Digital Input of Away
function
Value of physical Digital Input of Holiday
function
Value of physical Digital Input of Fireplace
function
| 30
| Modbus variable list
4
Symbolic register name
REG_SENSOR_DI_REHRESHI
REG_SENSOR_DI_CROWDEDI
REG_SENSOR_DI_COOKERHOODI
REG_SENSOR_DI_VACUUMCLEANERI
REG_USERMODE_HOLIDAY_DI_OFF_
DELAY
REG_USERMODE_AWAY_DI_OFF_DELAYI
REG_USERMODE_FIRPLACE_DI_OFF_
DELAY
REG_USERMODE_REFRESH_DI_OFF_
DELAY
REG_USERMODE_CROWDED_DI_OFF_
DELAY
REG_CDI1_OFF_DELAYI
REG_CDI2_OFF_DELAYI
REG_CDI3_OFF_DELAYI
REG_SPEED_CDI1_SAFI
REG_SPEED_CDI1_EAFI
REG_SPEED_CDI2_SAFI
REG_SPEED_CDI2_EAFI
REG_SPEED_CDI3_SAFI
REG_SPEED_CDI3_EAFI
REG_SPEED_PRESSURE_GUARD_SAFI
REG_SPEED_PRESSURE_GUARD_EAFI
REG_USERMODE_REMAINING_TIME_
CDI1_L
REG_USERMODE_REMAINING_TIME_
CDI1_H
REG_USERMODE_REMAINING_TIME_
CDI2_L
REG_USERMODE_REMAINING_TIME_
CDI2_H
REG_USERMODE_REMAINING_TIME_
CDI3_L
REG_USERMODE_REMAINING_TIME_
CDI3_H
REG_FUNCTION_ACTIVE_PRESSURE_
GUARD
Sig.
Modbus Reg. typeMod-
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
I
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
I
Read Input Register
(Function 04)
I
Read Input Register
(Function 04)
I
Read Input Register
(Function 04)
I
Read Input Register
(Function 04)
I
Read Input Register
(Function 04)
I
Read Input Register
(Function 04)
I
Read Input Register
(Function 04)
MinMaxDescription
bus
Adr.
1230401
1230501
1230601
1230701
11810365
1182072
1183060
11840240
118508
11880240
11890240
11900240
1221
1222
1223
1224
1225
1226
1227
1228
1621Remaining time
1622
1623Remaining time
1624
1625Remaining time
1626
311401
Value of physical Digital Input of Refresh
function
Value of physical Digital Input of Crowded
function
Value of physical Digital Input of
Cookerhood function
Value of physical Digital Input of Vacuum
Cleaner function
Off delay for DI
Off delay for DI
Off delay for DI
Off delay for DI
Off delay for DI
Off delay for DI
Off delay for DI
Off delay for DI
SAF speed value for user mode Holiday.(1):
Depends on regulation type. Value can be
%, RPM, Pressure or Flow
EAF speed value for user mode Holiday.(1):
Depends on regulation type. Value can be
%, RPM, Pressure or Flow
SAF speed value for mode Cooker Hood.(1):
Depends on regulation type. Value can be
%, RPM, Pressure or Flow
EAF speed value for mode Cooker Hood.(1):
Depends on regulation type. Value can be
%, RPM, Pressure or Flow
SAF speed value for mode Vacuum Cleaner.
(1): Depends on regulation type. Value can
be %, RPM, Pressure or Flow
EAF speed value for mode Vacuum Cleaner.
(1): Depends on regulation type. Value can
be %, RPM, Pressure or Flow
SAF speed value for low fan speed.(1):
Depends on regulation type. Value can be
%, RPM, Pressure or Flow
EAF speed value for low fan speed.(1):
Depends on regulation type. Value can be
%, RPM, Pressure or Flow
Indicates if function is active
| 30
Modbus variable list |
5
Symbolic register name
REG_FUNCTION_ACTIVE_CDI_1I
REG_FUNCTION_ACTIVE_CDI_2I
REG_FUNCTION_ACTIVE_CDI_3I
REG_SENSOR_DI_PRESSURE_GUARDI
REG_SENSOR_DI_CDI_1I
REG_SENSOR_DI_CDI_2I
REG_SENSOR_DI_CDI_3I
2.3Airflow Control
Symbolic register name
REG_SENSOR_RPM_SAFI
REG_SENSOR_RPM_EAFI
REG_SENSOR_FLOW_PIGGYBACK_SAFI
REG_SENSOR_FLOW_PIGGYBACK_EAFI
REG_SENSOR_DI_BYFI
REG_SYSTEM_UNIT_FLOWI
REG_SYSTEM_UNIT_PRESSUREI
REG_MANUAL_OVERRIDE_OUTPUT_SAFI
REG_MANUAL_OVERRIDE_OUTPUT_EAFI
REG_MANUAL_OVERRIDE_OUTPUT_
SAF_VALUE
REG_MANUAL_OVERRIDE_OUTPUT_
EAF_VALUE
REG_USERMODE_MANUAL_AIRFLOW_
LEVEL_SAF
REG_USERMODE_MANUAL_AIRFLOW_
LEVEL_EAF
REG_FAN_MANUAL_STOP_ALLOWEDI
REG_FAN_REGULATION_UNITI
REG_SPEED_FANS_RUNNINGI
REG_SPEED_SAF_DESIRED_OFFI
REG_FAN_LEVEL_SAF_MINI
Sig.
Modbus Reg. typeMod-
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Sig.
Modbus Reg. typeMod-
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
MinMaxDescription
bus
Adr.
311501
311601
311701
1231601
1231701
1231801
1231901
MinMaxDescription
bus
Adr.
1240105000
1240205000
12403
12404
12405
900102
900201
1360101
1360201
138010100
138020100
113114
113224
135301
127404
135101
135201
1301
Indicates if function is active
Indicates if function is active
Indicates if function is active
Indicates if physical DI is active
Indicates if physical DI is active
Indicates if physical DI is active
Indicates if physical DI is active
Supply Air Fan RPM indication from TACHO
Extract Air Fan RPM indication from TACHO
Flow value calculated from piggyback
pressure sensor.
Flow value calculated from piggyback
pressure sensor.
Value from Bypass Damper Feedback input.
In %.
Unit for CAV control mode.0: l/s1: m3/h2:
cfm
Units for VAV control mode.0: Pa1: InH2O
SAF Override.0: Auto1: Manual
EAF Override.0: Auto1: Manual
SAF Override value in % if manual (1)
selected
EAF override value in % if manual (1)
selected
Fan speed level for mode Manual, supply
fan.(1): value Off only allowed if contents of
register 1353 is 1.(1): Off2: Low3: Normal4:
High
Fan speed level for mode Manual, extract
fan.2: Low3: Normal4: High
Allow manual fan stop (also as selection for
user modes and Week schedule).0: Manual
stop not allowed1: Manual stop allowed
Type of fan control mode.0: Manual1:
RPM2: VAV (Constant Pressure)3: CAV
(Constant Flow)4: DCV (External)
Indicates that both fans are running
Indicates that the SAF shall be turned off
once the electrical reheater is cooled down.
SAF speed value for minimum fan speed.
(1): Depends on regulation type. Value can
be %, RPM, Pressure or Flow
| 30
| Modbus variable list
6
Symbolic register name
REG_FAN_LEVEL_EAF_MINI
REG_FAN_LEVEL_SAF_LOWI
REG_FAN_LEVEL_EAF_LOWI
REG_FAN_LEVEL_SAF_NORMALI
REG_FAN_LEVEL_EAF_NORMALI
REG_FAN_LEVEL_SAF_HIGHI
REG_FAN_LEVEL_EAF_HIGHI
REG_FAN_LEVEL_SAF_MAXI
REG_FAN_LEVEL_EAF_MAXI
REG_FAN_LEVEL_SAF_MIN_
PERCENTAGE
REG_FAN_LEVEL_EAF_MIN_
PERCENTAGE
REG_FAN_LEVEL_SAF_LOW_
PERCENTAGE
REG_FAN_LEVEL_EAF_LOW_
PERCENTAGE
REG_FAN_LEVEL_SAF_NORMAL_
PERCENTAGE
REG_FAN_LEVEL_EAF_NORMAL_
PERCENTAGE
REG_FAN_LEVEL_SAF_HIGH_
PERCENTAGE
REG_FAN_LEVEL_EAF_HIGH_
PERCENTAGE
REG_FAN_LEVEL_SAF_MAX_
PERCENTAGE
REG_FAN_LEVEL_EAF_MAX_
PERCENTAGE
REG_FAN_LEVEL_SAF_MIN_RPMI
REG_FAN_LEVEL_EAF_MIN_RPMI
REG_FAN_LEVEL_SAF_LOW_RPMI
REG_FAN_LEVEL_EAF_LOW_RPMI
REG_FAN_LEVEL_SAF_NORMAL_RPMI
REG_FAN_LEVEL_EAF_NORMAL_RPMI
REG_FAN_LEVEL_SAF_HIGH_RPMI
Sig.
Modbus Reg. typeMod-
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
I
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
MinMaxDescription
bus
Adr.
1302
1303
1304
1305
1306
1307
1308
1309
1310
140116100
140216100
140316100
140416100
140516100
140616100
140716100
140816100
140916100
141016100
14115005000
14125005000
14135005000
14145005000
14155005000
14165005000
14175005000
EAF speed value for minimum fan speed.
(1): Depends on regulation type. Value can
be %, RPM, Pressure or Flow
SAF speed value for low fan speed.(1):
Depends on regulation type. Value can be
%, RPM, Pressure or Flow
EAF speed value for low fan speed.(1):
Depends on regulation type. Value can be
%, RPM, Pressure or Flow
SAF speed value for normal fan speed.(1):
Depends on regulation type. Value can be
%, RPM, Pressure or Flow
EAF speed value for normal fan speed.(1):
Depends on regulation type. Value can be
%, RPM, Pressure or Flow
SAF speed value for high fan speed.(1):
Depends on regulation type. Value can be
%, RPM, Pressure or Flow
EAF speed value for high fan speed.(1):
Depends on regulation type. Value can be
%, RPM, Pressure or Flow
SAF speed value for maximum fan speed.
(1): Depends on regulation type. Value can
be %, RPM, Pressure or Flow
EAF speed value for maximum fan speed.
(1): Depends on regulation type. Value can
be %, RPM, Pressure or Flow
SAF speed value for minimum fan speed
EAF speed value for minimum fan speed
SAF speed value for low fan speed
EAF speed value for low fan speed
SAF speed value for normal fan speed
EAF speed value for normal fan speed
SAF speed value for high fan speed
EAF speed value for high fan speed
SAF speed value for maximum fan speed
EAF speed value for maximum fan speed
SAF speed value for minimum fan speed
EAF speed value for minimum fan speed
SAF speed value for low fan speed
EAF speed value for low fan speed
SAF speed value for normal fan speed
EAF speed value for normal fan speed
SAF speed value for high fan speed
| 30
Modbus variable list |
7
Symbolic register name
REG_FAN_LEVEL_EAF_HIGH_RPMI
REG_FAN_LEVEL_SAF_MAX_RPMI
REG_FAN_LEVEL_EAF_MAX_RPMI
REG_FAN_LEVEL_SAF_MIN_PRESSUREI
REG_FAN_LEVEL_EAF_MIN_PRESSUREI
REG_FAN_LEVEL_SAF_LOW_PRESSUREI
REG_FAN_LEVEL_EAF_LOW_PRESSUREI
REG_FAN_LEVEL_SAF_NORMAL_
PRESSURE
REG_FAN_LEVEL_EAF_NORMAL_
PRESSURE
REG_FAN_LEVEL_SAF_HIGH_PRESSUREI
REG_FAN_LEVEL_EAF_HIGH_PRESSUREI
REG_FAN_LEVEL_SAF_MAX_PRESSUREI
REG_FAN_LEVEL_EAF_MAX_PRESSUREI
REG_FAN_LEVEL_SAF_MIN_FLOWI
REG_FAN_LEVEL_EAF_MIN_FLOWI
REG_FAN_LEVEL_SAF_LOW_FLOWI
REG_FAN_LEVEL_EAF_LOW_FLOWI
REG_FAN_LEVEL_SAF_NORMAL_FLOWI
REG_FAN_LEVEL_EAF_NORMAL_FLOWI
REG_FAN_LEVEL_SAF_HIGH_FLOWI
REG_FAN_LEVEL_EAF_HIGH_FLOWI
REG_FAN_LEVEL_SAF_MAX_FLOWI
REG_FAN_LEVEL_EAF_MAX_FLOWI
REG_INPUT_EXTERNAL_CTRL_SAFI
REG_INPUT_EXTERNAL_CTRL_EAFI
REG_OUTPUT_SAFI
REG_OUTPUT_EAFI
REG_OUTPUT_FAN_SPEED1I
REG_OUTPUT_FAN_SPEED2I
Sig.
Modbus Reg. typeMod-
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
MinMaxDescription
bus
Adr.
14185005000
14195005000
14205005000
1421
1422
1423
1424
1425
1426
1427
1428
1429
1430
1431
1432
1433
1434
1435
1436
1437
1438
1439
1440
21010100
21020100
140010100
140020100
143710100
143720100
EAF speed value for high fan speed
SAF speed value for maximum fan speed
EAF speed value for maximum fan speed
SAF speed value for minimum fan speed
EAF speed value for minimum fan speed
SAF speed value for low fan speed
EAF speed value for low fan speed
SAF speed value for normal fan speed
EAF speed value for normal fan speed
SAF speed value for high fan speed
EAF speed value for high fan speed
SAF speed value for maximum fan speed
EAF speed value for maximum fan speed
SAF speed value for minimum fan speed
EAF speed value for minimum fan speed
SAF speed value for low fan speed
EAF speed value for low fan speed
SAF speed value for normal fan speed
EAF speed value for normal fan speed
SAF speed value for high fan speed
EAF speed value for high fan speed
SAF speed value for maximum fan speed
EAF speed value for maximum fan speed
Value from External Controller Input, SAF. In
%.
Value from External Controller Input, EAF. In
%.
SAF fan speed
EAF fan speed
Supply air fan control signal in %
Extract air fan control signal in %
| 30
| Modbus variable list
8
2.4Outdoor Airflow Compensation
Symbolic register name
REG_FAN_OUTDOOR_COMP_TYPEI
REG_FAN_OUTDOOR_COMP_MAX_
VALUE
REG_FAN_OUTDOOR_COMP_STOP_T_
WINTER
REG_FAN_OUTDOOR_COMP_MAX_TEMP
REG_FAN_OUTDOOR_COMP_START_T_
WINTER
REG_FAN_OUTDOOR_COMP_START_T_
SUMMER
REG_FAN_OUTDOOR_COMP_STOP_T_
SUMMER
REG_FAN_OUTDOOR_COMP_VALUE_
SUMMER
2.5Temperature Control
Symbolic register name
REG_SYSTEM_UNIT_TEMPERATUREI
REG_TC_CONTROL_MODEI
REG_TC_SP
REG_TC_SP_SATC
REG_TC_CASCADE_SP
REG_TC_ROOM_CTRL_SP_SATC
REG_TC_CASCADE_SP_MIN
REG_TC_CASCADE_SP_MAX
REG_TC_EAT_RAT_SP
REG_SATC_HEAT_DEMANDI
REG_SATC_PI_SP
REG_SATC_PI_OUTPUT
REG_ROOM_CTRL_PI_SP
REG_ROOM_CTRL_PI_OUTPUT
Sig.
Modbus Reg. typeMod-
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
Holding Register
I*
(Function 03/06/16)
Holding Register
I*
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
Sig.
Modbus Reg. typeMod-
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
I*
(Function 03/06/16)
Read Input Register
I*
(Function 04)
Holding Register
I*
(Function 03/06/16)
Read Input Register
I*
(Function 04)
Holding Register
I*
(Function 03/06/16)
Holding Register
I*
(Function 03/06/16)
Read Input Register
I*
(Function 04)
Read Input Register
(Function 04)
Read Input Register
I*
(Function 04)
Read Input Register
I*
(Function 04)
Read Input Register
I*
(Function 04)
Read Input Register
I*
(Function 04)
Max
Min
bus
Adr.
125101
1252050
1253-3000
1254-3000
1256-3000
1257150300
1258150400
1259050
bus
Adr.
900301
203102
2001120300
2054120300
2013120400
2053120400
2021120400
2022120400
2051120400
20550100
2061120300
20690100
2071120300
20790100
MinMaxDescription
Description
Compensate only SF or both SF and EF0:
SAF1: SAF/EAF
Compensation value at lowest temperature.
Temperature at which compensation
reaches maximum value during the winter
period.
Temperature at which highest
compensation is applied.
Temperature at which compensation starts
during the winter period.
Temperature at which compensation starts
during the summer period.
Temperature at which compensation
reaches maximum value during the summer
period.
Compensation value during summer period
Units for temperature.0: Celcius1:
Fahrenheit
Unit temperature control mode0: Supply1:
Room2: Extract
Temperature setpoint for the supply air
temperature
Temperature setpoint for the supply air
temperature
Temperature set point for SATC, as
calculated by RATC/EATC during cascade
control
Temperature set point for SATC, as
calculated by RATC/EATC during cascade
control
Minimum temperature set point for the
SATC
Maximum temperature set point for the
SATC
EAT or RAT value, used for room/extract air
controller.
Output of the SATC (0-100%)
SATC setpoint value
SATC output signal
RATC setpoint value
RATC output signal
| 30
2.6Cooler
Modbus variable list |
9
Symbolic register name
REG_COOLER_FROM_SATCI
REG_COOLER_OAT_INTERLOCK_TI
REG_COOLER_CIRC_PUMP_START_TI
REG_COOLER_CIRC_PUMP_STOP_DELAYI
REG_OUTPUT_Y3_CIRC_PUMPI
REG_OUTPUT_Y3_ANALOGI
REG_OUTPUT_Y3_DIGITALI
2.7Heater
Symbolic register name
REG_HEATER_CIRC_PUMP_START_T
REG_HEATER_CIRC_PUMP_STOP_DELAYI
REG_OUTPUT_Y1_CIRC_PUMPI
REG_SPEED_ELECTRICAL_HEATER_HOT_
COUNTER
REG_FAN_SPEED_AFTER_HEATER_
COOLING_DOWN_SAF
REG_FAN_SPEED_AFTER_HEATER_
COOLING_DOWN_EAF
REG_FUNCTION_ACTIVE_HEATER_COOL_
DOWN
REG_OUTPUT_TRIAC_CONFIGUREDI
REG_PWM_TRIAC_OUTPUTI
REG_OUTPUT_TRIACI
REG_OUTPUT_Y1_ANALOGI
REG_OUTPUT_Y1_DIGITALI
Sig.
Modbus Reg. typeMod-
Read Input Register
(Function 04)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Sig.
Modbus Reg. typeMod-
Holding Register
I*
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
I
Read Input Register
(Function 04)
I
Read Input Register
(Function 04)
I
Read Input Register
(Function 04)
I
Read Input Register
(Function 04)
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
MinMaxDescription
bus
Adr.
23110100
2316120250
23140200
2317060
14302
142010100
1420201
MinMaxDescription
bus
Adr.
21130200
2122060
14301
1357
13580100
13590100
311301
1320101
21490100
1438101
141010100Heater AO state.
1410201Heater DO state:0: Output not active1:
Cooler signal
Temperature at which cooling is interlocked
Temperature at which the cooler circulation
pump is started
Off time delay for the cooler circulation
pump in minutes
Cooler circulation pump output
Cooler AO state.
Cooler DO state:0: Output not active1:
Output active
Temperature at which the Heater circulation
pump is started
Off time delay for the heater circulation
pump in minutes
Heating circulation pump output
Electrical Heater hot counter. Count down
from 120 sec.
Supply Air Fan Speed Level After Heater
Cooling Down
Extract Air Fan Speed Level After Heater
Cooling Down
Active Heater Cool Down
Indicates if the TRIAC shall be used
TRIAC after manual override
TRIAC control signal
Output active
2.8Extra Controller
Symbolic register name
REG_EXTRA_CONTROLLER_CIRC_PUMP_
START_T
REG_EXTRA_CONTROLLER_CIRC_PUMP_
STOP_DELAY
REG_OUTPUT_Y4_CIRC_PUMPI
REG_EXTRA_CONTROLLER_SET_PI_
SETPOINT
| 30
Sig.
Modbus Reg. typeMod-
Holding Register
I*
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
Holding Register
I*
(Function 03/06/16)
MinMaxDescription
bus
Adr.
24040200
2405060
14304
2403-300400
Start temperature for extra controller
circulation pump
Off time delay for the extra controller
circulation pump in minutes
Extra controller circulation pump output
Set point value for the extra controller PI
regulator
| Modbus variable list
10
Symbolic register name
REG_EXTRA_CONTROLLER_PREHEATER_
SETPOINT_TYPE
REG_EXTRA_CONTROLLER_GEO_
PREHEATER_SP
REG_EXTRA_CONTROLLER_GEO_
PREHEATER_ACTIVATION_T
REG_EXTRA_CONTROLLER_GEO_
PRECOOLER_SP
REG_EXTRA_CONTROLLER_GEO_
PRECOOLER_ACTIVATION_T
REG_SENSOR_DI_EXTRA_CONTROLLER_
EMT
REG_OUTPUT_Y4_ANALOGI
REG_OUTPUT_Y4_DIGITALI
Sig.
Modbus Reg. typeMod-
I
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
I
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
2.9Change-over (Heating/Cooling)
Symbolic register name
REG_CHANGE_OVER_CIRC_PUMP_
START_T
REG_CHANGE_OVER_CIRC_PUMP_STOP_
DELAY
REG_OUTPUT_Y1_Y3_CIRC_PUMPI
Sig.
Modbus Reg. typeMod-
Holding Register
I*
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
MinMaxDescription
bus
Adr.
241801
2420–300100
2421–3000
2422100300
2423150300
1231001
142030100
1420401
MinMaxDescription
bus
Adr.
24510200
2452060
14303
Temperature setpoint for the preheater.0:
Auto1: Manual
Extra controller EMT input value
Extra controller AO state.
Extra controller DO state:0: Output not
active1: Output active
Start temperature for the change-over
circulation pump
Off time delay for the change-over
circulation pump in minutes
Indicates if conditions for ECO mode are
active (low temperature)
Description
Indicates if free cooling is enabled
Minimum of highest daytime temperature
for start of free cooling.
Highest night temperature limit for
termination free cooling
Lowest night temperature limit for
termination free cooling
Lowest temperature room temperature for
termination of free cooling
Start time of free cooling night-period, hour.
Valid range is from 0 to 8 and from 21 to
23.
Start time of free cooling night-period,
Minute
End time of free cooling night-period, hour.
Valid range is from 0 to 8 and from 21 to
23.
End time of free cooling night-period,
Minute
Indicates if free cooling is being performed
Minimum speed level during free cooling,
SAF.3: Normal4: High5: Maximum
Minimum speed level during free cooling,
EAF.3: Normal4: High5: Maximum
2.14 Week Schedule
Symbolic register name
REG_FREE_COOLING_ON_OFFI
REG_WS_T_OFFSET_ACTIVE
REG_WS_T_OFFSET_INACTIVE
REG_WS_DAY1_PRD1_START_HI
REG_WS_DAY1_PRD1_START_MI
REG_WS_DAY1_PRD1_END_HI
REG_WS_DAY1_PRD1_END_MI
| 30
Sig.
Modbus Reg. typeMod-
Holding Register
(Function 03/06/16)
Holding Register
I*
(Function 03/06/16)
Holding Register
I*
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
MinMaxDescription
bus
Adr.
41011
5001-1000
5002-1000
5003023
5004059
5005023
5006059
Indicates if free cooling is enabled
Temperature offset during active week
schedule.
Temperature offset during inactive week
schedule.
Monday, Period 1, start
Monday, Period 1, end
| Modbus variable list
12
Symbolic register name
REG_WS_DAY1_PRD2_START_HI
REG_WS_DAY1_PRD2_START_MI
REG_WS_DAY1_PRD2_END_HI
REG_WS_DAY1_PRD2_END_MI
REG_WS_DAY2_PRD1_START_HI
REG_WS_DAY2_PRD1_START_MI
REG_WS_DAY2_PRD1_END_HI
REG_WS_DAY2_PRD1_END_MI
REG_WS_DAY2_PRD2_START_HI
REG_WS_DAY2_PRD2_START_MI
REG_WS_DAY2_PRD2_END_HI
REG_WS_DAY2_PRD2_END_MI
REG_WS_DAY3_PRD1_START_HI
REG_WS_DAY3_PRD1_START_MI
REG_WS_DAY3_PRD1_END_HI
REG_WS_DAY3_PRD1_END_MI
REG_WS_DAY3_PRD2_START_HI
REG_WS_DAY3_PRD2_START_MI
REG_WS_DAY3_PRD2_END_HI
REG_WS_DAY3_PRD2_END_MI
REG_WS_DAY4_PRD1_START_HI
REG_WS_DAY4_PRD1_START_MI
REG_WS_DAY4_PRD1_END_HI
REG_WS_DAY4_PRD1_END_MI
REG_WS_DAY4_PRD2_START_HI
REG_WS_DAY4_PRD2_START_MI
REG_WS_DAY4_PRD2_END_HI
REG_WS_DAY4_PRD2_END_MI
REG_WS_DAY5_PRD1_START_HI
REG_WS_DAY5_PRD1_START_MI
Sig.
Modbus Reg. typeMod-
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
MinMaxDescription
bus
Adr.
5007023
5008059
5009023
5010059
5011023
5012059
5013023
5014059
5015023
5016059
5017023
5018059
5019023
5020059
5021023
5022059
5023023
5024059
5025023
5026059
5027023
5028059
5029023
5030059
5031023
5032059
5033023
5034059
5035023
5036059
Monday, Period 2, start
Monday, Period 2, end
Tuesday, Period 1, start
Tuesday, Period 1, end
Tuesday, Period 2, start
Tuesday, Period 2, end
Wednesday, Period 1, start
Wednesday, Period 1, end
Wednesday, Period 2, start
Wednesday, Period 2, end
Thursday, Period 1, start
Thursday, Period 1, end
Thursday, Period 2, start
Thursday, Period 2, end
Friday, Period 1, start
| 30
Modbus variable list |
13
Symbolic register name
REG_WS_DAY5_PRD1_END_HI
REG_WS_DAY5_PRD1_END_MI
REG_WS_DAY5_PRD2_START_HI
REG_WS_DAY5_PRD2_START_MI
REG_WS_DAY5_PRD2_END_HI
REG_WS_DAY5_PRD2_END_MI
REG_WS_DAY6_PRD1_START_HI
REG_WS_DAY6_PRD1_START_MI
REG_WS_DAY6_PRD1_END_HI
REG_WS_DAY6_PRD1_END_MI
REG_WS_DAY6_PRD2_START_HI
REG_WS_DAY6_PRD2_START_MI
REG_WS_DAY6_PRD2_END_HI
REG_WS_DAY6_PRD2_END_MI
REG_WS_DAY7_PRD1_START_HI
REG_WS_DAY7_PRD1_START_MI
REG_WS_DAY7_PRD1_END_HI
REG_WS_DAY7_PRD1_END_MI
REG_WS_DAY7_PRD2_START_HI
REG_WS_DAY7_PRD2_START_MI
REG_WS_DAY7_PRD2_END_HI
REG_WS_DAY7_PRD2_END_MI
REG_WS_ACTIVEI
REG_WS_FAN_LEVEL_SCHEDULEDI
REG_WS_FAN_LEVEL_UNSCHEDULEDI
REG_WS_DAY1_PRD1_ENABLEDI
REG_WS_DAY1_PRD2_ENABLEDI
Sig.
Modbus Reg. typeMod-
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
MinMaxDescription
bus
Adr.
5037023
5038059
5039023
5040059
5041023
5042059
5043023
5044059
5045023
5046059
5047023
5048059
5049023
5050059
5051023
5052059
5053023
5054059
5055023
5056059
5057023
5058059
505901
506015
506115
510101
510201
Friday, Period 1, end
Friday, Period 2, start
Friday, Period 2, end
Saturday, Period 1, start
Saturday, Period 1, end
Saturday, Period 2, start
Saturday, Period 2, end
Sunday, Period 1, start
Sunday, Period 1, end
Sunday, Period 2, start
Sunday, Period 2, end
Indicates that the current time lays within
the indicated intervals
Fan speed levels for SAF and EAF during
active week schedule.1: Off(1)2: Low3:
Normal4: High5: Demand(2)(1): Off
available if Manual Fan Stop is enabled.(2):
Demand available if demand control active
or external fan control enabled.
Fan speed levels for SAF and EAF during
inactive week schedule.1: Off(1)2: Low3:
Normal4: High5: Demand(2)(1): Off
available if Manual Fan Stop is enabled.(2):
Demand available if demand control active
or external fan control enabled.
Flag indicating if this period is enabled.
Flag indicating if this period is enabled.
| 30
| Modbus variable list
14
Symbolic register name
REG_WS_DAY2_PRD1_ENABLEDI
REG_WS_DAY2_PRD2_ENABLEDI
REG_WS_DAY3_PRD1_ENABLEDI
REG_WS_DAY3_PRD2_ENABLEDI
REG_WS_DAY4_PRD1_ENABLEDI
REG_WS_DAY4_PRD2_ENABLEDI
REG_WS_DAY5_PRD1_ENABLEDI
REG_WS_DAY5_PRD2_ENABLEDI
REG_WS_DAY6_PRD1_ENABLEDI
REG_WS_DAY6_PRD2_ENABLEDI
REG_WS_DAY7_PRD1_ENABLEDI
REG_WS_DAY7_PRD2_ENABLEDI
Sig.
Modbus Reg. typeMod-
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
MinMaxDescription
bus
Adr.
510301
510401
510501
510601
510701
510801
510901
511001
511101
511201
511301
511401
Flag indicating if this period is enabled.
Flag indicating if this period is enabled.
Flag indicating if this period is enabled.
Flag indicating if this period is enabled.
Flag indicating if this period is enabled.
Flag indicating if this period is enabled.
Flag indicating if this period is enabled.
Flag indicating if this period is enabled.
Flag indicating if this period is enabled.
Flag indicating if this period is enabled.
Flag indicating if this period is enabled.
Flag indicating if this period is enabled.
2.15 Time and Date
Symbolic register name
REG_TIME_YEARI
REG_TIME_MONTHI
REG_TIME_DAYI
REG_TIME_HOURI
REG_TIME_MINUTEI
REG_TIME_SECONDI
REG_TIME_AUTO_SUM_WINI
REG_HOUR_FORMATI
REG_DAY_OF_THE_WEEKI
REG_DST_PERIOD_ACTIVEI
REG_TIME_RTC_SECONDS_LI
REG_TIME_RTC_SECONDS_HI
REG_SYSTEM_START_UP_TIME_LI
Sig.
Modbus Reg. typeMod-
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
MinMaxDescription
bus
Adr.
600102999Current time
6002112Current time
6003131Current time
6004023Current time
6005059Current time
6006059Current time
600701
600801
600906
601001
6011
6012
6021
Flag indicating if DST is enabled.0: Daylight
saving time not enabled1: Daylight saving
time enabled
Indicaties the presentation of time in the
HMI. 24H/12H
Monday (0)...Sunday (6)
Now time in seconds. Lower 16 bits.
Now time in seconds. Higher 16 bits.
| 30
Modbus variable list |
15
Symbolic register name
REG_SYSTEM_START_UP_TIME_HI
REG_TIME_RTCI
2.16 Filter replacement
Symbolic register name
REG_FILTER_PERIODI
REG_FILTER_REPLACEMENT_TIME_LI
REG_FILTER_REPLACEMENT_TIME_HI
REG_FILTER_PERIOD_SETI
REG_FILTER_REMAINING_TIME_LI
REG_FILTER_REMAINING_TIME_HI
Sig.
Modbus Reg. typeMod-
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Sig.
Modbus Reg. typeMod-
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
MinMaxDescription
bus
Adr.
6022
6101
MinMaxDescription
bus
Adr.
7001315
7002
7003
7004
7005
7006
RTC value in seconds, highest 16 bits
Filter replacement time in months
Timestamp of latest filter replcement, lower
16 bits
Timestamp of latest filter replcement,
higher 16 bits
Indicates that the
LastFilterReplacementTime shall be set
Now.
Remaining filter time in seconds, lower 16
bits.
Remaining filter time in seconds, higher 16
bits.
2.17 Analog Input values (Temperatures, CO2, RH)
Symbolic register name
REG_SENSOR_FPT
REG_SENSOR_OAT
REG_SENSOR_SAT
REG_SENSOR_RAT
REG_SENSOR_EAT
REG_SENSOR_ECT
REG_SENSOR_EFT
REG_SENSOR_OHT
REG_SENSOR_RHSI
REG_SENSOR_CO2SI
REG_SENSOR_PDM_EAT_VALUEI
REG_SENSOR_RHS_PDMI
REG_SENSOR_CO2S_1I
REG_SENSOR_CO2S_2I
REG_SENSOR_CO2S_3I
Sig.
Modbus Reg. typeMod-
Holding Register
I*
(Function 03/06/16)
Holding Register
I*
(Function 03/06/16)
Holding Register
I*
(Function 03/06/16)
Holding Register
I*
(Function 03/06/16)
Holding Register
I*
(Function 03/06/16)
Holding Register
I*
(Function 03/06/16)
Holding Register
I*
(Function 03/06/16)
Holding Register
I*
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
bus
Adr.
12101-400800
12102-400800
12103-400800
12104-400800
12105-400800
12106-400800
12107-400800
12108-400800
121090100
1211502000
12544-400800
121360100
1215102000
1215202000
1215302000
MinMaxDescription
Frost Protection Temperature sensor value
(Water Heater)
Outdoor Air Temperature sensor (standard)
Supply Air Temperature sensor (standard)
Room Air Temperature sensor (accessory)
Extract Air Temperature sensor (accessory)
Extra Controller Temperature sensor
(accessory)
Efficiency temperature sensor (accessory)
Over Heat Temperature sensor (Electrical
Heater)
Relative Humidity Sensor (Accessory)
CO2 value (accessory)
PDM EAT sensor value (standard)
PDM RHS sensor value (standard)
CO2 sensor value - UI1 (accessory)
CO2 sensor value - UI2 (accessory)
CO2 sensor value - UI3 (accessory)
| 30
| Modbus variable list
16
Symbolic register name
REG_SENSOR_CO2S_4I
REG_SENSOR_CO2S_5I
REG_SENSOR_CO2S_6I
REG_SENSOR_RHS_1I
REG_SENSOR_RHS_2I
REG_SENSOR_RHS_3I
REG_SENSOR_RHS_4I
REG_SENSOR_RHS_5I
REG_SENSOR_RHS_6I
REG_INPUT_ANALOG_UI_1I
REG_INPUT_ANALOG_UI_2I
REG_INPUT_ANALOG_UI_3I
REG_INPUT_ANALOG_UI_4I
REG_INPUT_ANALOG_UI_5I
REG_INPUT_ANALOG_UI_6I
REG_INPUT_DIGITAL_UI_1I
REG_INPUT_DIGITAL_UI_2I
REG_INPUT_DIGITAL_UI_3I
REG_INPUT_DIGITAL_UI_4I
REG_INPUT_DIGITAL_UI_5I
REG_INPUT_DIGITAL_UI_6I
Sig.
Modbus Reg. typeMod-
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
MinMaxDescription
bus
Adr.
1215402000
1215502000
12156
121610100
121620100
121630100
121640100
121650100
121660100
12011mV
12012mV
12013mV
12014mV
12015mV
12016mV
1202101
1202201
1202301
1202401
1202501
12026
CO2 sensor value - UI4 (accessory)
CO2 sensor value - UI5 (accessory)
CO2 sensor value - UI6 (accessory)
RH sensor value - UI1 (accessory)
RH sensor value - UI2 (accessory)
RH sensor value - UI3 (accessory)
RH sensor value - UI4 (accessory)
RH sensor value - UI5 (accessory)
RH sensor value - UI6 (accessory)
State of UI1
State of UI2
State of UI3
State of UI4
State of UI5
State of UI6
2.18 Digital Input functions
Symbolic register name
REG_SENSOR_RGSI
REG_SENSOR_DI_EXTERNAL_STOPI
REG_SENSOR_DI_LOAD_DETECTEDI
REG_SENSOR_DI_FIRE_ALARMI
REG_SENSOR_DI_CHANGE_OVER_
FEEDBACK
Sig.
Modbus Reg. typeMod-
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
I
Read Input Register
(Function 04)
MinMaxDescription
bus
Adr.
1211201
1230801
1230901
1231101
1231201
Rotating guard Sensor input
External Stop input value
Load Detected input value
Fire Alarm input value
Change over feedback value
| 30
Modbus variable list |
17
Symbolic register name
REG_DI_CONNECTION_1I
REG_DI_CONNECTION_2I
REG_DI_CFG_POLARITY_1I
REG_DI_CFG_POLARITY_2I
REG_INPUT_DIGITAL_DI_1I
REG_INPUT_DIGITAL_DI_2I
2.19 Output values
Sig.
Modbus Reg. typeMod-
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
MinMaxDescription
bus
Adr.
11401018
11402018
1142101
1142201
1203101
1203201
Indicates what kind of DI functionality is
connected to DI1.0: None /Away/ BYP/
Vacuum Cleaner/ Cooker Hood/ Crowded/
EMT/ External Stop/ Extra Controller Alarm/
Fireplace/ Holiday/ Refresh/ RGS/ Change
Over Feedback/ 14: Fire Alarm/
ConfigurableDI1 / ConfigurableDI2 /
ConfigurableDI3 / 18: Pressure Guard
Indicates what kind of DI functionality is
connected to DI1.0: None /Away/ BYP/
Vacuum Cleaner/ Cooker Hood/ Crowded/
EMT/ External Stop/ Extra Controller Alarm/
Fireplace/ Holiday/ Refresh/ RGS/ Change
Over Feedback/ 14: Fire Alarm/
ConfigurableDI1 / ConfigurableDI2 /
ConfigurableDI3 / 18: Pressure Guard
Polarity of DI1.0: NO1: NC
Polarity of DI1.0: NO1: NC
Boolean
Boolean
Symbolic register name
REG_SENSOR_RGSI
REG_DO1_AFTER_MUXI
REG_DO2_AFTER_MUXI
REG_DO3_AFTER_MUXI
REG_DO4_AFTER_MUXI
REG_AO1_AFTER_MUXI
REG_AO2_AFTER_MUXI
REG_AO3_AFTER_MUXI
REG_AO4_AFTER_MUXI
REG_AO5_AFTER_MUXI
REG_OUTPUT_OUTDOOR_EXTRACT_
DAMPER
REG_OUTPUT_Y2_ANALOGI
REG_OUTPUT_Y2_DIGITALI
REG_OUTPUT_AO1I
REG_OUTPUT_AO2I
REG_OUTPUT_AO3I
Sig.
Modbus Reg. typeMod-
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
I
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
MinMaxDescription
bus
Adr.
1211201
1330101
1330201
1330301
1330401
133110100
133120100
133130100
133140100
133150100
1400401
141030100
1410401
14351
14352
14353
Rotating guard Sensor input
Digital output after multiplexer
Digital output after multiplexer
Digital output after multiplexer
Digital output after multiplexer
Analog output after multiplexer
Analog output after multiplexer
Analog output after multiplexer
Analog output after multiplexer
Analog output after multiplexer
Indicates if Outdoor/Exhaust air damper
signal is On/Off
Heat Exchanger AO state.
Heat Exchanger DO state.0: Output not
active1: Output active
Voltage signal from AO1
Voltage signal from AO2
Voltage signal from AO3
| 30
| Modbus variable list
18
Symbolic register name
REG_OUTPUT_AO4I
REG_OUTPUT_AO5I
REG_OUTPUT_DO1I
REG_OUTPUT_DO2I
REG_OUTPUT_DO3I
REG_OUTPUT_DO4I
2.20 Alarms
Symbolic register name
REG_FILTER_ALARM_WAS_DETECTEDI
REG_OUTPUT_ALARMI
REG_ALARM_SAF_CTRL_ALARMI
REG_ALARM_SAF_CTRL_CLEAR_ALARMI
REG_ALARM_EAF_CTRL_ALARMI
REG_ALARM_EAF_CTRL_CLEAR_ALARMI
REG_ALARM_FROST_PROT_ALARMI
REG_ALARM_FROST_PROT_CLEAR_
ALARM
REG_ALARM_DEFROSTING_ALARMI
REG_ALARM_DEFROSTING_CLEAR_
ALARM
REG_ALARM_SAF_RPM_ALARMI
REG_ALARM_SAF_RPM_CLEAR_ALARMI
REG_ALARM_EAF_RPM_ALARMI
REG_ALARM_EAF_RPM_CLEAR_ALARMI
Sig.
Modbus Reg. typeMod-
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Sig.
Modbus Reg. typeMod-
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Read Input Register
(Function 04)
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
I
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
I
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
Holding Register
(Function 03/06/16)
MinMaxDescription
bus
Adr.
14354
14355
1436101
1436201
1436301
1436401
MinMaxDescription
bus
Adr.
7007
1400301
1500203
1500301
1500903
1501001
1501603
1501701
1502303
1502401
1503003
1503101
1503703
1503801
Voltage signal from AO4
Voltage signal from AO5
State of DO1
State of DO2
State of DO3
State of DO4
Indicates if the filter warning alarm was
generated.
Sum Alarm DO
0: Output not active
1: Output active
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
Signal to clear the alarm
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
Signal to clear the alarm
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
Signal to clear the alarm
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
Signal to clear the alarm
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
Signal to clear the alarm
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
Signal to clear the alarm
| 30
Modbus variable list |
19
Symbolic register name
REG_ALARM_FPT_ALARMI
REG_ALARM_FPT_CLEAR_ALARMI
REG_ALARM_OAT_ALARMI
REG_ALARM_OAT_CLEAR_ALARMI
REG_ALARM_SAT_ALARMI
REG_ALARM_SAT_CLEAR_ALARMI
REG_ALARM_RAT_ALARMI
REG_ALARM_RAT_CLEAR_ALARMI
REG_ALARM_EAT_ALARMI
REG_ALARM_EAT_CLEAR_ALARMI
REG_ALARM_ECT_ALARMI
REG_ALARM_ECT_CLEAR_ALARMI
REG_ALARM_EFT_ALARMI
REG_ALARM_EFT_CLEAR_ALARMI
REG_ALARM_OHT_ALARMI
REG_ALARM_OHT_CLEAR_ALARMI
REG_ALARM_EMT_ALARMI
REG_ALARM_EMT_CLEAR_ALARMI
REG_ALARM_RGS_ALARMI
Sig.
Modbus Reg. typeMod-
Read Input Register
(Function 04)
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
MinMaxDescription
bus
Adr.
1505803
1505901
1506503
1506601
1507203
1507301
1507903
1508001
1508603
1508701
1509303
1509401
1510003
1510101
1510703
1510801
1511403
1511501
1512103
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
Signal to clear the alarm
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
Signal to clear the alarm
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
Signal to clear the alarm
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
Signal to clear the alarm
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
Signal to clear the alarm
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
Signal to clear the alarm
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
Signal to clear the alarm
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
Signal to clear the alarm
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
Signal to clear the alarm
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
| 30
| Modbus variable list
20
Symbolic register name
REG_ALARM_RGS_CLEAR_ALARMI
REG_ALARM_BYS_ALARMI
REG_ALARM_BYS_CLEAR_ALARMI
REG_ALARM_SECONDARY_AIR_ALARMI
REG_ALARM_SECONDARY_AIR_CLEAR_
ALARM
REG_ALARM_FILTER_ALARMI
REG_ALARM_FILTER_CLEAR_ALARMI
REG_ALARM_EXTRA_CONTROLLER_
ALARM
REG_ALARM_EXTRA_CONTROLLER_
CLEAR_ALARM
REG_ALARM_EXTERNAL_STOP_ALARMI
REG_ALARM_EXTERNAL_STOP_CLEAR_
ALARM
REG_ALARM_RH_ALARMI
REG_ALARM_RH_CLEAR_ALARMI
REG_ALARM_CO2_ALARMI
REG_ALARM_CO2_CLEAR_ALARMI
REG_ALARM_LOW_SAT_ALARMI
REG_ALARM_LOW_SAT_CLEAR_ALARMI
REG_ALARM_BYF_ALARMI
REG_ALARM_BYF_CLEAR_ALARMI
Sig.
Modbus Reg. typeMod-
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
I
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
Holding Register
(Function 03/06/16)
I
Read Input Register
(Function 04)
I
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
I
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
Holding Register
(Function 03/06/16)
MinMaxDescription
bus
Adr.
1512201
1512803
1512901
1513503
1513601
1514203
1514301
1514903
1515001
1515603
1515701
1516303
1516401
1517003
1517101
1517703
1517801
15184
151850
Signal to clear the alarm
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
Signal to clear the alarm
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
Signal to clear the alarm
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
Signal to clear the alarm
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
Signal to clear the alarm
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
Signal to clear the alarm
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
Signal to clear the alarm
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
Signal to clear the alarm
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
Signal to clear the alarm
Alarm active/inactive
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
Signal to clear the alarm
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
Signal to clear the alarm
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
Signal to clear the alarm
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
Signal to clear the alarm
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
Signal to clear the alarm
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
Signal to clear the alarm
Alarm active/inactive.
0: Inactive
1: Active
2: Waiting
3: Cleared Error Active
Signal to clear the alarm
Counter for delay
Indicates if an alarm Type A is active
Indicates if an alarm Type B is active
Indicates if an alarm Type C is active
| 30
| Modbus variable list
22
2.21 System settings
Symbolic register name
REG_PASSWD_ADMINI
REG_LOCKED_USERI
REG_LOCKED_FILTERI
REG_LOCKED_WEEK_SCHEDULEI
REG_PASSWD_USER_LEVEL_REQUIREDI
REG_PASSWD_FILTER_REQUIREDI
REG_PASSWD_WEEK_SCHEDULE_
REQUIRED
REG_PASSWD_PC_SETTINGSI
REG_PASSWD_PC_UNLOCKEDI
REG_SUW_REQUIREDI
Sig.
Modbus Reg. typeMod-
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
I
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Read Input Register
(Function 04)
Holding Register
(Function 03/06/16)
MinMaxDescription
bus
Adr.
16001
1600201
1600301
1600401
1605101
1605201
1605301
16061
1606201
1610101
Administrator password.
Bit 12-15: digit 1
Bit 8-11: digit 2
Bit 4-7: digit 3
Bit 0-3: digit 4
Indicates if the User level is locked.
0: User menu locked
1: User menu not locked
Indicates if the Filter menu is locked.
0: menu locked
1: menu not locked
Indicates if the Week schedule menu is
locked.
0: menu locked
1: menu not locked
Home screen lock
Filter Change menu lock
Week schedule menu lock
Indicates if the start-up wizard shall be
activated.
2.22 Modbus
Symbolic register name
REG_COMM_MODBUS_ADDRESSI
REG_COMM_MODBUS_BAUD_RATEI
REG_COMM_MODBUS_PARITYI
2.23 Unit Backups
Symbolic register name
REG_FACTORY_RESETI
REG_SET_USER_SAFE_CONFIGI
REG_ACTIVATE_USER_SAFE_CONFIGI
Sig.
Modbus Reg. typeMod-
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Sig.
Modbus Reg. typeMod-
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Holding Register
(Function 03/06/16)
Max
Min
bus
Adr.
170010255
17002010
1700302
MinMaxDescription
bus
Adr.
30101322-83228
3010301
3010401
Description
Modbus address of the MB.
Only relevant if the MB is a modbus slave.
Baudrate of the modbus connection
0=1200
1=2400
2=4800
3=9600
4=14400
5=19200
6=28800
7=38400
8=57600
9=76800
10=115200
Parity setting for the modbus connection.
0: None
1: Even
2: Odd
Activates setting of the parameters to their
default values.
Only activated by writing 3228 to this
register.
| 30
Revision table |
23
Symbolic register name
REG_USER_SAFE_CONFIG_VALIDI
REG_SAFE_CONFIG_VALIDI
3Revision table
Main board
software
compatibility
1.5.0
1.6.0
2.0
Modbus Table
Revision
20180927 (Rev.
25)
20190116 (Rev.
29)
20200703 (Rev.
30)
20210301 (Rev.
36)
Sig.
Modbus Reg. typeMod-
Read Input Register
(Function 04)
Read Input Register
(Function 04)
30105
30106
MinMaxDescription
bus
Adr.
Change Log
-
Chapter 2.3. User modesRegisters:12316, ... , 12319 were added.1171, ... , 1190,1221, ... ,
1228,1621, ... , 1626,3114, ... , 3117,12316, ... , 12319 were addedRegisters:1141, ... ,
1144, 1161 have increase range.Changes related to Away and Holiday User modes, and 4
new user functions added - CDI 1-3 and Pressure Guard.
Chapter 2.5. Outdoor Airflow Compensation.Registers 1253. 1256 ... 1259 were added.
Compensation starting temperature for winter is added. Summer outdoor compensation is
added.
Chapter 2.18. Digital Input Functions.Registers 11401 and 11402.Max range changed from
14 to 18 adding new DI functions.
Chapter 2.23. Unit Backups.Registers 30103, ... , 30106 added. Registers allow to set,
check and use safe user settings (store unit configuration in memory).