Systemair KBR, KBR/F Operating Instructions

Thermo box KBR, KBR/F
Installation and Operating Instructions
Document in original language | · 004
GB
© Copyright Systemair AB All rights reserved E&OE
Systemair AB reserves the rights to alter their products without notice. This also applies to products already ordered, as long as it does not affect the previously agreed specifications.
| 004
1 General information ......... .... ......... .... .... ......... ..1
1.1 Notice symbols . .... ............. .... ............. ...1
1.1.1 Instruction symbols...... .... ...........1
2 Important safety information ..... .... .... ..... .... .... ...1
2.1 Personnel .... ............. .... .... ..... .... .... .......1
2.2 Personal protective equipment.. .... .... ........2
2.3 5 rules of electrical safety ......... .... .... .......2
3 Warranty....... .... .... ............. .... .... ......... .... .... ..2
4 Delivery, transport, storage ........ .... .... ......... .... ..2
5 Description ... .... .... ..... .... .... ......... .... .... ...........3
5.1 Intended use ............. .... ............. .... .... ..3
5.2 Technical data .... .... ......... .... .... ......... .... .4
5.3 KBR and KBR/F ............ .... .... ......... .... .... .4
6 Name plate and type key .... .... ......... .... .... .........5
7 Accessories........ .... .... ......... .... .... ......... .... .... ..6
8 Installation.. .... .... ......... .... .... ............. .... .........6
8.1 Assembly/Disassembly impeller —
Internal rotor motor ......... .... .... ............. ..7
9 Electrical connection ........ .... ............. .... .... .......9
9.1 Electrical connection accessories ......... .... ..9
9.2 Protecting the motor... .... .... ......... .... .... . 10
9.3 Variable-speed fans ............. .... ............. 10
10 Commissioning .... .... ............. .... .... ......... .... ... 11
11 Operation . ............. .... .... ......... .... .... ......... .... 11
12 Troubleshooting/maintenance/repair ........ .... .... 12
12.1 Troubleshooting.. .... .... ..... .... .... ......... ...12
12.2 Maintenance... ..... .... .... ............. .... ...... 13
13 Cleaning....... .... .... ............. .... .... ..... .... .... ..... 14
14 Deinstallation/dismantling. .... ......... .... .... ......... 14
15 Disposal .... .... .... ......... .... .... ......... .... ............14
16 Commissioning Report.. .... ............. .... .... ......... 15
17 EU Declaration of conformity... .... ............. .... ....16
18 EU Declaration of conformity — Smoke extract
fans .... ............. .... ............. .... .... ......... .... .... 16
Contents
| 004

1 General information

1.1 Notice symbols

General information |
1
Danger
Direct hazard
Failure to comply with this warning will lead directly to death or to serious injury.
Warning
Potential hazard
Failure to comply with this warning may lead to death or serious injury.
Note:
Useful information and instructions

1.1.1 Instruction symbols

Instruction
Carry out this action
(if applicable, further actions)
Caution
Hazard with a low risk
Failure to comply with this warning may lead to moderate injuries.
Important
Hazard with risk of damage to objects
Failure to comply with this warning will lead to damage to objects.
Instruction with xed sequence
1. Carry out this action
2. Carry out this action
3. (if applicable, further actions)

2 Important safety information

Planners, plant builders and operators are responsible for the proper assembly and intended use.
Read the operating instructions completely and carefully.Keep the operating instructions and other valid documents, such as the circuit diagram or motor instructions, with
the fan. They must always be available at the place of use.
Observe and respect local conditions, regulations and laws.Abide by the system-related conditions and requirements of the system manufacturer or plant constructor.Safety elements may not be dismantled, circumvented or deactivated.Only use the fan in a awless condition.Provide generally prescribed electrical and mechanical protective devices.During installation, electrical connection, commissioning, troubleshooting, and maintenance, secure the location and
premises against unauthorised access.
Do not circumvent any safety components or put them out of action.Before any work on the fan, test absence of voltage.
Even when the motor is stopped, dangerous voltages may be present on terminals.
Keep all the warning signs on the fan complete and in a legible condition.The device is not to be used by persons (including children) with reduced physical, sensory or mental capabilities, or
lack of experience and knowledge, unless they have been given supervision or instruction.
Do not allow children to play with the device.

2.1 Personnel

The fan may only be used by qualified, instructed and trained personnel. The persons must know the relevant safety di­rectives in order to recognise and to avoid risks. The individual activities and qualifications can be found in Table 1 Qual- ifications, page 2.
| 004
Warranty
|
2
Table 1 Qualifications
Activities
Storage, operation, transport, cleaning, disposal Trained personnel (see following note)
Electrical connection, commissioning, electrical disconnection
Installation, disassembly Fitter or matching qualification
Maintenance
Repair
Qualifications
Electrical expert or matching qualification
Electrical expert or matching qualification
Electrical expert or matching qualification
Smoke extraction fans and EX fans only by agreement with Systemair.
Fitter or matching qualification
Fitter or matching qualification
Note:
The operator is responsible for ensuring that personnel are instructed and have understood the contents of the operating instructions. If something is unclear, please contact Systemair or its representative.

2.2 Personal protective equipment

Wear protective equipment during all work in the vicinity of the fan.
• protective working clothes
• protective working shoes
• protective working gloves
• helmet
• goggles
• hearing protection

2.3 5 rules of electrical safety

1. Disconnect (disconnection of the electrical system from live components at all terminals)
2. Prevent reactivation
3. Test absence of voltage
4. Ground and short-circuit
5. Cover or restrict adjacent live parts

3 Warranty

For the assertion of warranty claims, the products must be correctly connected and operated, and used in accordance with the data sheets. Further prerequisites are a completed maintenance plan with no gaps and a commissioning re­port. Systemair will require these in the case of a warranty claim. The commissioning report is a component of this document. The maintenance plan must be created by the operator, see section 12.2 Maintenance, page 13.

4 Delivery, transport, storage

Safety information
Warning: Risk from rotating fan blades
Prevent access by unauthorised persons by safety personnel or access protection.
Warning: Suspended loads
Do not walk under suspended loads.Make sure that there is nobody under a suspended load.
Delivery
Each fan leaves our plant in an electrically and mechanically proper condition. We recommend transporting the fan to the installation site in the original packaging.
Checking delivery
Check the packaging and the fan for transport damage. Any findings should be noted on the cargo manifest.Check completeness of the delivery.
| 004
Description
Unpacking
When opening the transport packaging, there is a risk of damage from sharp edges, nails, staples, splinters etc.
Unpack the fan carefully.Check the fan for obvious transport damage.Only remove the packaging shortly before assembly.
Transport
Safety information
Warning: Electrical or mechanical hazards due to fire, moisture, short circuit or malfunction.
Never transport the fan by the connecting wire, terminal box, impeller, protection grille, inlet cone or silencer.In open transport, please make sure that no water can penetrate into the motor or other sensitive parts.We recommend transporting the fan to the installation site in the original packaging.
Caution: If transported without care during loading and unloading, the fan may be damaged.
Load and unload the fan carefully.Use hoisting equipment that is suitable for the weight to be hoisted.Observe the transportation arrows on the packaging.Use the fan packaging exclusively as transport protection and not as a lifting aid.
Storage
Store the fan in the original packaging in a dry, dust-free location protected against weather.Avoid the effects of extreme heat or cold.
|
3
Hazard due to loss of function of the motor bearing
Avoid storing for too long (recommendation: max. 1 year).Check that the motor bearing functions properly before installation.

5 Description

5.1 Intended use

All KBR- versions:
• The fan is intended for installation in ventilation systems.
• The fans are exclusively intended for extract air applications.
KBR
• The fan is suitable for extracting contaminated air (dust, kitchen exhaust).
Incorrect use
Incorrect use refers mainly to using the fan in another way to that described. The following examples are incorrect and hazardous:
KBR/F
• The fan is suitable for conveying contaminated air.
• The smoke extraction units KBR/F are used in case of fire to extract smoke gases, as well as in normal working conditions of up to 200°C.
• Conveying of explosive and combustible media
• Conveying of aggressive media
• Operation in an explosive atmosphere
| 004
• Operation without duct system
• Operation with the air connections closed
• Installation outside without weather protection
Description
50
L
50
J
K
A
F
B
29
D
E
G
C
38
H
M
G
E
|
4

5.2 Technical data

Max. ambient temperature [°C] see data sheet, available in our online catalogue.
Sound pressure [dB] see data sheet, available in our online catalogue.
Voltage, current, frequency, enclosure class, weight see name plate of the fan
The motor data can be found on the name plate of the motor, or in the technical documents of the motor manufacturer.
The data on the name plate of the fan apply to "standard air" according to ISO 5801.
KBR
• Temperature range [°C] of transported air = -20 to 120 (This is the maximum range. For the temperature range of your fan, please check the data sheet.)
KBR/F
• Temperature range [°C] of transported air = -20 to 200 or up to 400°C/120 min (once)

5.3 KBR and KBR/F

Table 2 Dimensions
KBR
KBR/F
A B C D E F F
KBR/F
G H J K K
280 171,5 537 295 360 625 125 60 280 234 291 70 8 620 315 187,5 600 339 398 690 125 60 315 249 307 70 8 770 355 206,7 655 372 451 770 125 60 355 273 331 70 8 770
KBR/F
M
L
55 55 55
| 004

6 Name plate and type key

1
2 3
4 5
6
7
Name plate and type key |
5
1
Type designation
2
Voltage/current/frequency
3 Input power 7 4
Enclosure class/fan impeller speed/ weight
Table 3 Type key
KBR 355 EC -L
-L
-K
EC
E4
DV
D2
D2–4
5
Insulation class
6
Article number/production number/manufacturing date
Certifications
More power version
Normal power version Less power version
Motor type
Electronically commutated/1 phased or 3 phased
4 poled/controllable by frequency converter/1 phased
4 poled voltage controllable/3 phased
2 poled/controllable by frequency converter/3 phased
2–4 poled/controllable by frequency converter/3 phased
Duct Diameter
Fan type
KBR KBR/F Thermo fan — Smoke extraction fan
Thermo fan
| 004
Accessories
1
2
3
3
8
1
2
3
3
4
4
5
5
6
6
7
8
|
6

7 Accessories

For details of the accessories, please check our online catalog or contact Systemair.
Accessories KBR
Accessories KBR/F
Table 4 Accessories
1 ALS-KBR
2 WSD-KBR-2 3 ASF
4 UGF
Drain plug
Weather roof for motor Flexible connection
Transition flange
5 EVH
6 RSA 7 LRK
WBK
Flexible connection AXC 400°C
Silencer Air-operated damper
Wall bracket

8 Installation

Safety information
Observe 2 Important safety information, page 1Use installation material with fire resistance classes that meet temperature requirements.Provide contact and intake protection and ensure safety distances according to DIN EN ISO13857 and DIN 24167-1.To reduce transmission of vibration to the duct system, we recommend flexible connections from our accessory
range, see chapter Accessories.
Preconditions
Ensure that the fan and all its components are
undamaged.
Fit the fans in such a way that there is sufficient
access for installation, troubleshooting, maintenance
Protect against dust and moisture when installing.Ensure that the information on the name plates (fan
and motor) matches up with the operating conditions.
and repair.
Important
Damage to the bearings or other parts of the fan can occur.
Do not place a duct bend directly before or after the fan!Ensure a smooth and constant air flow to the device.
| 004
Important
Ø D
min.
2,5x Ø D
min.
2,5x Ø D
1
2
3
4
5
6
6
87
Damage to the bearings or other parts of the fan can occur.
Do not place a duct bend directly before or
after the fan!
Ensure a smooth and constant air flow to the
device.
• Round duct system: D = Nominal diameter
• Rectangular duct system: D = Hydraulic diameter
Installation positions
Important
Damage to the fan if condensation water cannot drain.
Ensure that the drain plug is always at the lowest point of the fan to ensure that the condensation water
can drain.

8.1 Assembly/Disassembly impeller — Internal rotor motor

If an external rotor motor is used, the motor and impeller can`t be seperated.
Important
Installation |
7
Damage to the motor and impeller.
The ball bearing of the motor and the balanced impeller may be damaged by forceful impacts.
Attach the impeller and/or the shaft extension to the shaft or the rotor without forceful impacts.
Do not separate the impeller and the hub. They were balanced as one unit by Systemair.
Note:
The hub can be heated for easier assembly and disassembly, for example with a hot-air blower.
• Precondition for assembly: the wedge is in the intended groove.
• Tools: hexagon socket wrench and suitable tool for removal, torque wrench for the taper clamping bush.
1 Motor 2
Motor shaft
3
Sleeve (not available at every fan)
4
Shaft extension (not available at every fan)
5
Hexagon socket screw
6
Impeller
7
Steel hub
8
Aluminium hub
The hub is shown without impeller due to better lucidity.
| 004
| Installation
1.
2.
1.
2.
=
2.
1.
8
1. Aluminium hub 1. Steel hub
1. 2. 3. 4.
Disassembly
2. 3. 4.
Assembly
Use screw locking The set screw must push on the wedge
of the shaft.
5. Aluminium hub
Use screw locking
5. Steel hub 6. Steel hub
Tighten the two
screws evenly with
the tightening torque
according to table 5.
Tighten the screws
slightly
Table 5 Tightening torques for various types of bush
Type of bush
Tightening
1008 1108 1210 1215 1310 1610 1615 2012 2517 3020
5.7 5.7 20 20 20 20 20 31 49 92
torque [Nm]
| 004

9 Electrical connection

S-5EC/FRQ
10V
GND
A
EC-Vent
IN/10V
OUT/PWM
GND
IN/RPM TAC H
+10V
0...10V/PWM
GND
optional
PWM
Safety information
Observe 2 Important safety information, page 1Prevent the ingress of water into the connection box.
Connection
Electrical connection |
9
Check if the data on the nameplate matches the
connection data.
Complete the electrical connection according to the
circuit diagram.
Connect the cable end in a dry environment.Install a circuit breaker in the permanent electrical
installation, with a contact opening of at least 3 mm at each pole.
Fans with EC- motors must be switched on/off via the
control input.
Protective grounding wire
The protective grounding must have a cross-section equal to or greater than that of the phase conductor.
Residual current circuit breaker
All-current-sensitive residual current circuit breakers are required for use in alternating-current systems with 50/60 Hz, in combination with electronic devices such as EC motors, frequency converters or uninterruptible power supplies (UPS).

9.1 Electrical connection accessories

The following wiring diagrams show the electrical connections between accessories and fans (with EC motor) or frequency converters (e.g. FRQ, FRQS, FXDM) which can be controlled with a 0–10V signal. If you are not sure if your fan is equipped with an EC- motor please see chapter 6 Name plate and type key, page 5.
Wire- colours of motors with carried out cables: +10V = red 0..10V/PWM =
yellow
motor/frequency
converter
GND = blue
Controll via 0–10V signal
MTP 10 MTP 20
EC-Basic
MTV—1/10
S-5EC/FRQ
EC-Vent
| 004
| Electrical connection
24V AC
CO2RT-R-D
Supply
Neutral
Common
Relay NO
Relay NC
+10V
0...10V
GND
Din1
24V AC or DC
IR24-P
24V
Neutral
Common
Relay NO
Relay NC
+10V
0...10V
GND
Din1
10
Controll via switching on / off
The following fans are equipped with a DIN1 connection:
KBR 355EC-L
Din1: enable electronics
• enable: pin open or voltage 5–50 V DC
• disable: bridge to GND
CO2RT-R(-D)

9.2 Protecting the motor

Note:
In fans equipped with an EC motor, there is no additional motor protection needed. The motor protection is integrated in the electronics of the motor.
Important
Damage to motor due to overcurrent, overload or short circiut.
Lead-out temperature monitors must be integrated in the control circuit in such a way that, if a fault
occurs, the motor cannot switch on again automatically after it has cooled down.
Motor lines and temperature monitor lines should be laid separately on principle.Without thermal protection: Use a motor protection switch!
IR24–P

9.3 Variable-speed fans

Warning
Resonant frequencies may result in increased vibration in certain speed ranges. These vibrations may destroy components.
Only operate the fan outside these speed ranges.Pass through these speed ranges so quickly that any vibration cannot exceed the admissible resonant
frequency values.
Observe the operating instructions of the frequency converter.
| 004
Commissioning
Caution
Damage as a result of incorrect commissioning of the frequency converter.
Install the fan and frequency converter as near as possible to one another.Use shielded cables.All components (fan, frequency converter and motor) must be grounded.Avoid running the fan via the frequency converter below 10 Hz.Heating of the motor due to use of a variable frequency drive must be checked in the application by the
customer.
Never exceed the maximum impeller rotation speed indicated on the name plate of the fan.In any case Systemair recommends an all-pole sine filter if the fan is operated with a frequency
converter.

10 Commissioning

Warranty claims can only be made if commissioning work is carried out correctly and written evidence thereof is provided.
Safety information
Observe 2 Important safety information, page 1
Preconditions
|
11
Installation and electrical connection have been
correctly performed.
Before switching the fan on, check for externally
visible damage and ensure that the protective equipment functions properly.
Commissioning of speed-controlled fans
Check the fan for vibrations at all normal operation speeds during commissioning. Determine and evaluate vibrations on the housing and bearing areas in accordance with DIN ISO 14694 depending on motor power and positioning.
Measurable vibration velocities depend e.g. on following factors:
• positioning
The working point of the fan, as well as used external devices and accessories, also influence the running characteristics.
Tests
Do the tests requested in the commissioning report (16 Commissioning Report, page 15)
• bottom section/foundation state • flow conditions
Inlet and outlet are free.Cable glands are tight.Safety devices have been fitted.

11 Operation

Safety information
Observe 2 Important safety information, page 1
| 004
| Troubleshooting/maintenance/repair
12

12 Troubleshooting/maintenance/repair

Safety information
Observe 2 Important safety information, page 1

12.1 Troubleshooting

Table 6 Troubleshooting
Fan does not run smoothly
Air output of fan too low
Grinding sounds when starting or operating the fan
Impeller imbalance
Soiling on the impeller Clean carefully, rebalance
Material decomposition on the impeller due to aggressive material conveyed.
Impeller rotates in wrong direction.
Deformation of impeller due to excessive temperature.
Vibrations, oscillations
Fan operation in resonant frequency range
Impeller rotates in wrong direction.
Wrong wiring configuration (e.g. Y instead of Delta).
Pressure losses too high. Optimize the line routing.
Flow regulators not or only partly open.
Intake or pressure ducts are blocked.
Check if the duct connections of the fan are strained.
Rebalancing by a specialist company if possible, otherwise contact Systemair.
Contact Systemair
Change direction of rotation (swap two phases in case of a 3– phase motor). Contact Systemair
Ensure that the temperature does not exceed the certified value/Install new impeller.
Check the installation of the fan/check the duct system, see 8 Installation, page 6.
Consider chapter 9.3 Variable-speed fans, page 10
Change direction of rotation if possible, otherwise contact Systemair.
Check and possibly correct the wiring configuration.
Check opening position on site.
Remove the blockage.
Loosen the duct connections and realign it.
Thermal contacts/ resistors have triggered
Fan does not reach nominal speed
Impeller rotates in wrong direction.
Missing phase
Motor overheated
Capacitor (if used) not or not correctly connected.
Motor blocked
Defective motor winding
Control units (if used) such as frequency converter or transformer are set incorrectly.
Mechanical blockage Remove the blockage.
Change direction of rotation (swap two phases in case of a 3– phase motor).
In case of a 3 phase standard motor (not EC), check if all 3 phase are present.
Check the cooling impeller (if used), measure the motor winding (if possible) / contact Systemair.
Connect the capacitor correctly.
Contact Systemair
Check the winding by resistance measurement (if possible). Contact Systemair
Correct the settings of the control units.
| 004
Troubleshooting cont'd
Troubleshooting/maintenance/repair |
Faulty supply voltage Check the supply voltage, re-establish the voltage supply.
13
Motor does not rotate
Electronics/motor overheated
Faulty connection
Temperature monitor has responded.
Insufficient cooling Improve cooling.
Overloaded motor Ambient temperature too high Check if the correct fan is used for your application.
Allow the motor to cool down, find and resolve the cause of the fault.
Allow the motor to cool down, find and resolve the cause of the fault.
Check if the correct fan is used for your application.
Note:
For all other damage/defects, please contact Systemair.

12.2 Maintenance

Warranty claims can only be made if maintenance work is carried out correctly and written evidence thereof is provided.
We recommend regular maintenance intervals to ensure continuous fan operation. These maintenance intervals are specified in the “Activities” table below. In addition, the operator must carry out follow-up activities such as cleaning, replacing defective components or other corrective measures. For traceability reasons, a maintenance plan must be created which documents the work carried out. This must be created by the operator. If the operating conditions are "extreme", the maintenance intervals must be reduced so that maintenance is carried out more frequently. Examples of extreme operating conditions:
• Kitchen exhaust fans
• Durable ambient temperature > 30 ºC or < -10 ºC, or temperature fluctuations > 20 K
Table 7 Activities
Activity
Check the fan and its components for visible damage, corrosion and contamination.
Check the impeller for damage and imbalance.
Check the condensate drain is working correctly.
Clean the fan/ventilation system (see 13 Cleaning, page
14).
Check the screwed connections for damages/defects and check that they are firmly seated.
Check the fan intake is free from contamination. Check that the fan and its components are being used
correctly.
Check the current consumption and compare this with the rated data.
Check the vibration dampers (if used) are working correctly and check for visible damage and corrosion.
Check the electrical and mechanical protective equipment is working correctly.
Check the fan’s rating plate is legible.
Normal operating
conditions
Every six
months
X X
X
Annually Quarterly
X X
X X
X X
X
X X
X X
X
X
X X
Extreme operating
conditions
Every six
months
See normal operating
conditions
See normal operating
conditions
See normal operating
conditions
See normal operating
conditions
| 004
| Cleaning
14
Activities cont'd
Check the connection clamps and screwed cable connections for damage/defects, and check that they are firmly seated.
Check the flexible connectors for damage.
Spare parts
Use original spare parts from Systemair only.When ordering spare parts, please specify the serial number of the fan. This can be found on the name plate.
X
X
See normal operating
conditions
See normal operating
conditions

13 Cleaning

Safety information
Observe 2 Important safety information, page 1
Procedure
Keeping the fan clean extends its service life.
• Install a filter monitor.
• Change the filters of the ventilation system.
• Do not use steel brushes or sharp-edged objects.
• Do not use a high-pressure cleaner (steam jet cleaner) under any circumstances.
• Do not bend the fan blades when cleaning.
• When cleaning the impeller, pay attention to balance weights that have been positioned
• Keep the airways of the fan clear and clean them if necessary with a brush.

14 Deinstallation/dismantling

Deinstall and dismantle the fan in reverse order of installation and electrical connection.

15 Disposal

Ensure material is recycled. Observe national regulations.The device and the transport packaging are predominantly made from recyclable raw materials.Disassemble the fan into its components.Separate the parts according to:
• reusable material
• material groups to be disposed of (metal, plastics, electrical parts, etc.)
| 004
Commissioning Report

16 Commissioning Report

Warranty claims can only be made if commissioning work is carried out correctly and written evidence thereof is provided.
Fan
Description:
Article no.: Manufacturing order no.:
Installer
Company: Contact person:
Company address:
Tel. no.: Email:
Operator (Place of installation)
Company: Contact person:
Company address:
Tel. no.: Email:
|
15
Type of connection
Directly to mains
0-10 V signal (EC motor)
via contactor control Transformer Frequency converter
Sinus filter Shielded cables
Motor protection
Motor protection switch or motor protection relay PTC resistor
Resistance value [Ω]:
Thermal contact Electrical motor protection
Others:
Functional check
Impeller easily rotatable (by hand)
Rotation direction acc. to directional arrow Smooth running without unusual noise/
vibrations
Yes No
Yes No
Yes No
Nominal data - Fan (name plate on fan housing)
Voltage [V]: Current [A]:
Frequency [Hz]: Power [kW]:
Fan impeller speed [rpm]:
Measured data at commissioning
Voltage [V]: Temp. of transported air [°C]:
| 004
| EU Declaration of conformity
16
Current L1 [A]*:
Current L2 [A]: Air volume [m3/s]:
Current L3 [A]:
*For single-phase fans, fill in line “Current L1 [A]” *Δ- Pressure between suction-side and discharge of the fan
If an air flow measurement is not possible, this value can be calculated using the following formula:
X
Duct cross-section [m²]
Commissioning of the fan successful?
Date, installer's signature
Date, operator's signature
Flow speed [m/s]
Grille measurement acc. to VDI 2044
Fan impeller speed [rpm]:
Differential pressure [Pa]*:
=
Air volume [m³/s]:

17 EU Declaration of conformity

Yes No
The manufacturer: Systemair GmbH
Seehöfer Straße 45 97944 Boxberg Germany
Product designation: Thermo fans
Type designation: AxZent; KBR; MUB-K; MUB/T; MUB/T-S; DVN; DVNI
Since year of manufacture:
The manufacturer declares that the above mentioned products in their design and construction and the version marketed by us complies with the harmonization legislation listed below:
EU directives: 2006/42/EC Machinery directive
2018
2014/30/EU Directive electromagnetic compatibility (EMC)
2011/65/EU RoHS directive

18 EU Declaration of conformity — Smoke extract fans

The manufacturer: Systemair GmbH
Seehöfer Straße 45 97944 Boxberg Germany
Product designation: Smoke extract fans
Type designation: KBR/F; MUB/F
The manufacturer declares that the above mentioned products in their design and construction and the version marketed by us complies with the harmonization legislation listed below:
EU directives: 2006/42/EC Machinery directive
2014/30/EU Directive electromagnetic compatibility (EMC)
2011/65/EU RoHS directive
| 004
| 004
Systemair GmbH Seehöfer Str. 45
97944 Boxberg Germany
Tel.: +49 (0)7930/9272-0 Fax: +49 (0)7930/9273-92
info@systemair.de www.systemair.de
Thermo box · Installation and Operating Instructions · · en_GB · 2020-03-12 · 004