Systemair AB reserves the rights to alter their products without notice.
This also applies to products already ordered, as long as it does not affect the previously agreed specifications.
| 003
Contents
1General information ......... .... ......... .... .... ......... ..1
16 EU Declaration of conformity... .... ............. .... ....18
| 003
1General information
1.1Notice symbols
General information |
1
Danger
Direct hazard
Failure to comply with this warning will lead
directly to death or to serious injury.
Warning
Potential hazard
Failure to comply with this warning may lead to
death or serious injury.
Note:
Useful information and instructions
1.1.1Instruction symbols
Instruction
♦ Carry out this action
♦ (if applicable, further actions)
Caution
Hazard with a low risk
Failure to comply with this warning may lead to
moderate injuries.
Important
Hazard with risk of damage to objects
Failure to comply with this warning will lead to
damage to objects.
Instruction with xed sequence
1. Carry out this action
2. Carry out this action
3. (if applicable, further actions)
2Important safety information
Planners, plant builders and operators are responsible for the proper assembly and intended use.
♦ Read the operating instructions completely and carefully.
♦ Keep the operating instructions and other valid documents, such as the circuit diagram or motor instructions, with
the fan. They must always be available at the place of use.
♦ Observe and respect local conditions, regulations and laws.
♦ Only use the fan in a awless condition.
♦ Provide generally prescribed electrical and mechanical protective devices.
♦ During installation, electrical connection, commissioning, troubleshooting, and maintenance, secure the location and
premises against unauthorised access.
♦ Do not circumvent any safety components or put them out of action.
♦ Keep all the warning signs on the fan complete and in a legible condition.
♦ The device is not to be used by persons (including children) with reduced physical, sensory or mental capabilities, or
lack of experience and knowledge, unless they have been given supervision or instruction.
♦ Do not allow children to play with the device.
2.1Personnel
The fan may only be used by qualified, instructed and trained personnel. The persons must know the relevant safety directives in order to recognise and to avoid risks. The individual activities and qualifications can be found in Table 1 Qual-ifications, page 1.
Table 1 Qualifications
Activities
Storage, operation, transport, cleaning, disposalTrained personnel (see following note)
Installation, disassemblyFitter or matching qualification
Maintenance
Repair
Electrical expert or matching
qualification
Electrical expert or matching
qualification
Smoke extraction fans and EX fans only by agreement with
Systemair.
Note:
The operator is responsible for ensuring that personnel are instructed and have understood the contents of
the operating instructions. If something is unclear, please contact Systemair or its representative.
2.2Personal protective equipment
Wear protective equipment during all work in the vicinity of the fan.
• protective working clothes
• protective working shoes
• protective working gloves
• helmet
2.35 rules of electrical safety
• Disconnect (disconnection
of the electrical system from
live components at all
terminals)
• Prevent reactivation
• Test absence of voltage
Fitter or matching
qualification
Fitter or matching
qualification
• goggles
• hearing protection
• Ground and short-circuit
• Cover or restrict adjacent live parts
3Warranty
For the assertion of warranty claims, the products must be correctly connected and operated, and used in accordance
with the data sheets. Further prerequisites are a completed maintenance plan with no gaps and a commissioning report. Systemair will require these in the case of a warranty claim. The commissioning report is a component of this
document. The maintenance plan must be created by the operator, see section 11.4 Maintenance, page 15.
4Delivery, transport, storage
4.1Safety information
Warning: Risk from rotating fan blades
♦ Prevent access by unauthorised persons by safety personnel or access protection.
Warning: Suspended loads
♦ Wear protective equipment during all work in the vicinity of the fan, details see 2.2 Personal protective equipment,
page 2.
♦ Do not walk under suspended loads.
♦ Make sure that there is nobody under a suspended load.
4.2Delivery
Each fan leaves our plant in an electrically and mechanically proper condition. We recommend transporting the fan to
the installation site in the original packaging.
Checking delivery
♦ Check the packaging and the fan for transport damage. Any findings should be noted on the cargo manifest.
♦ Check completeness of the delivery.
Unpacking
| 003
Warning
When opening the transport packaging, there is a risk of damage from sharp edges, nails, staples,
splinters etc.
♦ Unpack the fan carefully.
♦ Check the fan for obvious transport damage.
♦ Only remove the packaging shortly before assembly.
♦ Wear protective equipment during all work in the vicinity of the fan, details see 2.2 Personal protective
equipment, page 2.
4.3Transport
4.3.1Safety information
Description IV Smart
|
3
Warning: Electrical or mechanical hazards due to fire,
moisture, short circuit or malfunction.
♦ Never transport the fan by the connecting wire,
terminal box, impeller, protection grille, inlet cone or
silencer.
♦ In open transport, please make sure that no water can
penetrate into the motor or other sensitive parts.
♦ We recommend transporting the fan to the
installation site in the original packaging.
Caution: If transported without care during loading and
unloading, the fan may be damaged.
♦ Load and unload the fan carefully.
♦ Use hoisting equipment that is suitable for the weight
to be hoisted.
♦ Observe the transportation arrows on the packaging.
♦ Use the fan packaging exclusively as transport
protection and not as a lifting aid.
4.4Storage
♦ Store the fan in the original packaging in a dry, dust-free location protected against weather.
♦ Avoid the effects of extreme heat or cold.
Important
Hazard due to loss of function of the motor bearing
♦ Avoid storing for too long (recommendation: max. 1 year).
♦ Check that the motor bearing functions properly before installation.
5Description IV Smart
5.1IV Smart EC equipped with an EC motor
The fans are driven by two EC motors. These motors are delivered with a pre-wired potentiometer (0–10 V) that allows
you to easily find the required working point of the fan. All motors are suitable for 50/60 Hz. The input voltage for single-phase units can vary between 200 and 277 V.
5.2IV Smart AC — equipped with an AC motor
The fans are driven by two AC motors. All motors are suitable for 50/60 Hz.
5.3IV Smart EC—CO — equipped with a carbon monoxide control unit
The fans are driven by two EC motors (see 5.1 IV Smart EC equipped with an EC motor, page 3). The fan and the control
unit are pre—wired and ready for use.
5.3.1Carbon monoxide control unit
The CO control unit controls two EC fans with a 0–10 V control signal originating from a CO sensor. Both fans are controlled with the same 0–10 V signal and monitored for fan failure. The CO alarm is triggered based on the threshold and
time specifications of DIN EN 50291-1.
| 003
Description IV Smart
169
760
36140
150
800
700
8
503
173360
20
|
4
5.3.2Information on the effects of CO on humans
Warning
This CO control unit is designed to protect people from the acute effects of carbon monoxide. It cannot
prevent the chronic effects of carbon monoxide exposure. The CO control unit can not fully protect people at
special risk, such as those with particular medical conditions. In cases of doubt, consult a doctor.
The table below sets out the symptoms, the corresponding CO concentrations and lengths of time that a person needs
to be exposed to this concentration until symptoms occur.
Table 2 Influence of carbon monoxide on the human body
CO concentration
30 ppm
100 ppm
200 ppm
300 ppm
400 ppm
800 ppm
1600 ppm
3200 ppm
8000 ppm
5.4Dimensions
Symptoms
Maximum workplace concentration for 8 hours of
Time until occurrence of symptoms
-
work, no symptoms
Even after a prolonged period, no symptoms
-
Headache2…3 h
Mild headache, dizziness, weakness, nausea2…3 h
Frontal headache
Life-threatening
1…2 h
3 h
Headache, dizziness, nausea, convulsionsWithin 45 min
Headache, dizziness and nausea
Loss of consciousness
Possible death
Headache, dizziness and nausea
Death
Within 20 min
Within 2 h
Within 1 h
Within 5…10 min
Within 25…30 min
DeathA few minutes
Fig. 1 Dimensions IV Smart
| 003
5.5Technical data of the fan
• IV Smart AC: Temperature range [°C] of transported air = -25 to 55
• IV Smart EC: Temperature range [°C] of transported air = -25 to 55
• IV Smart EC CO: Temperature range [°C] of transported air = -20 to 40
• Voltage/current/enclosure class/weight/impeller diameter = see name plate
• Sound pressure [dB(A)] = see data sheet
Note:
Further technical data can be found on the data sheet of your fan.
5.6Technical data of the controller
Voltage = 100…240 VAC
Frequency = 50…60 Hz
Table 3 CO control unit components
Description IV Smart
|
5
Component
Fan
CO sensor
External alarm device (optional)
Function
Two fans with a 0-10 V control input and hall output, for ventilation of the
room being monitored.
CO sensor with 4…20 mA measuring signal output that reflects a 0…300
ppm CO concentration.
Connection of an alarm siren or alarm light
5.7Motor data
The motor data can be found on the name plate of the motor, or in the technical documents of the motor
manufacturer.
5.8Intended use of all IV Smart versions
• The fans are intended for installation in underground and above-ground parking structures, to facilitate ventilation
and cold smoke extraction.
• For optimum operation, the jet fan must be suspended horizontally from the ceiling in such a position that intake and
outlet are unobstructed.
• The maximum admissible operating data on the name plate apply to an air density of 1.2 kg/3³ (sea level) and a
maximum air humidity of 80%.
• The fan is suitable for conveying clean air, with a density of 1.3 kg/m3 and a max. air humidity of 95%.
5.9Incorrect use
Incorrect use refers mainly to using the fan in another way to that described. The following uses are incorrect and
hazardous:
• Conveying of explosive and combustible media
• Conveying of aggressive media
• Installation outside
• Operation in an explosive atmosphere
5.10 Terminal boxes
IV Smart ACIV Smart ECIV Smart CO
| 003
| Name plate and type key
Serial.no: 84543/1002773290-001/20170131
IV Smart EC
230 V~
50 Hz
IP54
䰊
2510 min ¹
17kg
0,35 kW
Made in GERMANY
INS.CL.B
2,6 A
www.systemair.com
1
2
3
4
5
6
7
6
6Name plate and type key
1
Type designation
2
Voltage/current/frequency
3Input power7
4
Enclosure class/fan impeller speed/
weight
Table 4 Type key
IV SmartEC
-
CO
EC
AC
Induction fan Smart
5
Insulation class
6
Article number/production number/manufacturing date
Certifications
No controller
Equipped with a carbon monoxide control unit
Motor type
Electronically commutated/1 phased
2 poled/voltage controllable/1 phased
Fan type
7Installation
Warning: Danger from falling fan or fan parts.
♦ Check the surface before installation for load bearing capacity.
♦ Consider all static and dynamic loads when selecting hoisting equipment and fastening components.
General safety information
♦ Installation may only be carried out by adequately qualified persons, details see Table 1 Qualifications, page 1.
♦ Wear protective equipment during all work in the vicinity of the fan, details see 2.2 Personal protective equipment,
page 2.
♦ Abide by the system-related conditions and requirements of the system manufacturer or plant constructor.
♦ Do not dismantle or circumvent safety elements, or put them out of function.
♦ Provide contact and intake protection and ensure safety distances according to DIN EN ISO13857 and DIN 24167-1.
♦ Prevent the possibility of foreign bodies being drawn in.
7.1Preconditions
♦ Ensure that the fan and all its components are
undamaged.
♦ Ensure that there is enough space to install the fan.
♦ Protect against dust and moisture when installing.
♦ Ensure that the information on the name plates (fan
and motor) matches up with the operating conditions.
♦ Fit the fans in such a way that there is sufficient
access for troubleshooting, maintenance and repair.
| 003
7.2Installation on the ceiling
4x
Installation IV Smart
Electrical connection |
7
8Electrical connection
8.1Safety information / Preconditions
Warning: Danger from electrical voltage!
♦ Observe the 5 rules of electrical safety, see 2.3 5 rules of electrical safety, page 2.
♦ Prevent the ingress of water into the connection box.
♦ Electrical connection may only be carried out by adequately qualified persons, details see Table 1 Qualifications, page
1.
♦ Observe and respect local conditions, regulations and laws.
♦ Wear protective equipment during all work in the vicinity of the fan, details see 2.2 Personal protective equipment,
page 2.
8.2Preconditions
♦ Abide by the system-related conditions and requirements of the system manufacturer or plant constructor.
♦ Safety elements may not be dismantled, circumvented or deactivated.
♦ Install a circuit breaker in the permanent electrical installation, with a contact opening of at least 3 mm at each pole.
8.3Connection
♦ Check if the data on the nameplate matches the
connection data.
♦ Complete the electrical connection according to the
circuit diagram.
♦ Lay the connection cables in the terminal box in such
a way that allows the cover of the terminal box to be
closed without resistance.
♦ Use all of the locking screws.
♦ Insert the screws by hand to avoid damaging the
thread.
♦ Tighten all glands well in order to guarantee
protection class IP.
♦ Screw the lid of the terminal box/inspection switch
evenly tight.
♦ Connect the cable end in a dry environment.
♦ Check if the data on the nameplate matches the connection data.
♦ Complete the electrical connection according to the circuit diagram.
♦ Lay the connection cables in the terminal box in such a way that allows the cover of the terminal box to be closed
without resistance.
| 003
| Electrical connection
8
♦ Use all of the locking screws.
♦ Insert the screws by hand to avoid damaging the thread.
♦ Tighten all glands well in order to guarantee protection class IP.
♦ Screw the lid of the terminal box/inspection switch evenly tight.
♦ Connect the cable end in a dry environment.
8.3.1Wiring diagram IV Smart AC
ColorFunction/pin assignment
Black
Blue
Green/Yellow
L
Power supply 230 V AC, 50...60 Hz
N
Neutral conductor
PE
Protective conductor
| 003
8.3.2Wiring diagram IV Smart EC
0-10V
+10V
blau / blue / bleu
rot / red / rouge
gelb / yellow / jaune
GND
TACHO / Motor 1
weiß / white / blanc
TACHO / Motor 2
weiß / white / blanc
N
L
grün/gelb / green/yellow
vert/jaune
schwarz / black / noir
blau / blue / bleu
1
2
The connection cables of the two motors of the IV Smart are carried out in the terminal boxes.
Terminal assignment terminal boxes (Client side)
1
Terminal box — Power supply
2
Terminal box — Control interface
Terminal assignment motor
Electrical connection |
9
Adjustable speed through PWM
Wire no.ConnectionColor
CON10L
CON11N
CON12PE
20...10 V PWM
4
310 V
1GND
Max. speed
1...10 KHz
100 % PWM –> n = max
10 % PWM –> n = min
< 10 % –> 0
Tachowhite
Adjustable speed
10V –> n = max
1V –> n = min
<1V –> 0
Adjustable speed through potentiometer
Function/assignment
black
blueNeutral conductor
green/yellow
yellowController input 0...10 V or PWM
red
blueGND-connection of the controller interface
Power supply 230 V AC, 50...60 Hz, see name plate for
voltage range
GND-connection
Speed output: Open Collector, 1 impulse per revolution,
electrically isolated, Isink_max = 10 mA
Voltage output 10 V, Imax. 10 mA, short-circuit-proof,
power supply for external devices.
| 003
| Electrical connection
10
8.3.3Wiring IV Smart EC-CO
The wiring diagram of the IV Smart EC-CO fan is not included in this document, but within this delivery.
Table 5 Electrical connections
NameOccupancy
1. L
X1
X2
X3
X4
X5
X6
X7
2. N
3. PE
1. L
2. N
3. PE
1. L
2. N
3. PE
1. 10 V
2. 0-10 V
3. HALL
4. GND
1. 10 V
2. 0-10 V
3. HALL
4. GND
1. 24 V
2. 4-20 mA
3. EARTH
1. NC
2. COM
3. NO
DesignationDescription
X1 SUPPLY
X2 FAN1
X3 FAN2
X4 FAN1
X5 FAN2
X6 SENSOR
X7 ALARM
Supply connection to the control unit
Supply connection to fan 1. Voltage corresponds to the control unit's
supply voltage
Supply connection to fan 2. Voltage corresponds to the control unit's
supply voltage
Control connection to fan 1. Speed specification and speed
feedback. If the fan has a 10 V output, it can be connected to
terminal X4.1.
Control connection to fan 2. Speed specification and speed
feedback. If the fan has a 10 V output, it can be connected to
terminal X5.1.
Connection for CO sensor supply connection and measuring signal
connection
Potential-free alarm contact connection option for controlling an
alarm siren or other auxiliary device.
8.3.3.1Fan speed specification
The minimum fan speed can be set via a potentiometer in the range from 20 % to 40 %. The potentiometer is only accessible once the housing cover has been removed. The fan speed increases proportionately to the CO concentration
until the maximum speed at 50 ppm. If a fault is detected, the fans operate at maximum speed in order to remove any
| 003
Commissioning
raised CO concentrations in the air. The following table provides information about the control unit's speed specifications to the fans.
Table 6 Fan speed specification
|
11
CO concentration
CO < 15 ppm Switch-off hysteresis 10
ppm
CO = 15 ppm
15 ppm < CO ≤ 50 ppmMin.…10 V
50 ppm < CO10 V
Fault
Speed specification values
0 V
2 V…4 V (min.)
10 V
Comment
Fan standstill
Speed depending on set value
Linear rise in the characteristic curve
analogue to the CO concentration
starting with the minimum through to
the maximum fan speed
Maximum fan speed
Maximum fan speed
8.4Protective grounding wire
The protective grounding must have a cross-section equal to or greater than that of the phase conductor.
8.5Residual current circuit breaker
All-current-sensitive residual current circuit breakers are required for use in alternating-current systems with 50/60 Hz,
in combination with electronic devices such as EC motors, frequency converters or uninterruptible power supplies
(UPS).
8.6Protecting the motor
Note:
In fans equipped with an EC motor, there is no additional motor protection needed. The motor protection is
integrated in the electronics of the motor.
Important
Damage to motor due to overcurrent, overload or short circiut.
♦ Use (all-pole) circuit breaker (characteristic C or K) or motor protection switches.
♦ Always connect thermo-contacts or cold conductors to a motor protection switch.
9Commissioning
Warranty claims can only be made if commissioning work is carried out correctly and written evidence thereof is
provided.
It is recommended to fill out the commissioning report 15 Commissioning Report, page 17.
9.1Safety information
♦ Commissioning may only be carried out by adequately qualified persons, details see Table 1 Qualifications, page 1.
♦ Wear protective equipment during all work in the vicinity of the fan, details see 2.2 Personal protective equipment,
page 2.
9.2Preconditions
♦ Installation and electrical connection have been
correctly performed.
♦ Residual material from installation and foreign objects
have been removed from the fan and ducts.
♦ Inlet and outlet are free.
♦ Safety devices have been fitted.
| 003
♦ Ground cable is connected.
♦ Cable glands are tight.
♦ Nominal current (from the name plate) is not
exceeded.
♦ Data on the name plate corresponds with the
connection data.
Commissioning
|
12
9.3Tests
♦ Before switching the fan on, check for externally visible damage and ensure that the protective equipment functions
properly.
AC motorEC motor
1. Switch the fan on.
2. Checks:
♦ Direction of rotation/conveyance. The direction of
rotation always applies looking at the rotor
• The direction of rotation is best observed just
before the fan stops.
♦ Smooth running (any vibrations and noise)
♦ Current consumption
♦ Compare the current consumption with the
nominal consumption on the name plate.
♦ Tightness of all connections
3. Switch the fan off.
When the mains are switched on, the motor starts an
initialization (a few seconds). After the initialization the
control input is active.
1. Switch the fan on via the control input.
2. Checks:
♦ Direction of rotation/conveyance. The direction of
rotation always applies looking at the rotor
• The direction of rotation is best observed just
before the fan stops.
♦ Smooth running (any vibrations and noise)
♦ Current consumption
♦ Compare the current consumption with the
nominal consumption on the name plate.
♦ Tightness of all connections
3. Switch the fan off via the control input.
9.4Tests when activated EC CO version
9.4.1Function test
A function test is carried out once the voltage supply is connected, with the displays, the potential-free contact and the
fans being switched on briefly. The control unit has been installed correctly if the power display lights up permanently,
the CO alarm and fault display goes out after 2 seconds and the audible display does the same after 1 second. The potential-free contact must tighten after 1 second and therefore establish a connection between X7.2 and X7.3. In addition, no faults must be displayed after around 15 seconds. In the Chapter 9.4.3 Visual and audible display, page 12 the
meaning of the different signal types are explained.
9.4.2Warm-up time
Once the operating voltage has been connected, the control unit is in a warm-up state for around 6.5 minutes. During
this time, no CO measurements are carried out and no CO alarms are triggered. To ensure basic ventilation and to remove any raised CO concentrations in the air, the fans are controlled at a minimum speed. The warm-up time is needed
to give the CO sensor enough time for the CO measuring transducer's warm-up phase. Once the warm-up time has
elapsed, the control unit switches to its normal operating state (ready) and CO analysis takes place.
9.4.3Visual and audible display
The table below distinguishes between the displays based on the control unit's four operating modes.
Table 7 Visible and audible display
Operating modeAudible signal
generator
Warm-up time
Ready
CO alarm
Fault2 fast sounds / min
NoNoOnNo
NoNoOnNo
On
CO alarm
Red LED
Rapid flashing 2 Hz
NoOn
Operation
Green LED
OnNo
Fault
Yellow LED
Rapid flashing 2 Hz
Table 8 Carbon monoxide alarm thresholds
CO concentration for activation of
the CO alarm
30 ppm
50 ppm
Control unit trigger timesCO concentration for resetting of the
No alarmNo alarm
After around 75 min
active CO alarm
< 40 ppm
| 003
Operation
Carbon monoxide alarm thresholds cont'd
100 ppm
300 ppm
After around 25 min
After around 1 min
< 40 ppm
< 40 ppm
10Operation
10.1 Safety information
Warning: Hazard from electrical voltage or moving components.
♦ The device may only be operated by adequately qualified persons, details see Table 1 Qualifications, page 1.
♦ Abide by the system-related conditions and requirements of the system manufacturer or plant constructor.
10.2 Preconditions
♦ Ensure access only to persons who can safely handle the device.
♦ Only use the fan in accordance with the operating instructions and the operating instructions for the motor.
♦ Do not dismantle or circumvent safety elements, or put them out of function.
11Troubleshooting/maintenance/repair/CO alarm
|
13
11.1 Safety information
♦ Troubleshooting/maintenance/repair may only be carried out by adequately qualified persons, details see Table 1
Qualifications, page 1.
♦ Wear protective equipment during all work in the vicinity of the fan, details see 2.2 Personal protective equipment,
page 2.
♦ Observe the 5 rules of electrical safety, see 2.3 5 rules of electrical safety, page 2.
♦ Abide by the system-related conditions and requirements of the system manufacturer or plant constructor.
♦ The impeller must be at a standstill.
11.2 Troubleshooting Fan
Table 9 Troubleshooting
ProblemPossible causesRemedy
Fan does not run
smoothly
Air output of fan too
low
Impeller imbalanceRebalancing by a specialist company if possible,
otherwise contact Systemair.
Soiling on the impellerClean carefully, rebalance
Material decomposition on the
impeller due to aggressive
material conveyed.
Impeller rotates in wrong
direction.
Deformation of impeller due to
excessive temperature.
Vibrations, oscillationsCheck the installation of the fan.
Impeller rotates in wrong
direction.
Mechanical blockageRemove the blockage
Contact Systemair
Contact Systemair
Ensure that the temperature does not exceed the certified
value/Contact Systemair.
Contact Systemair
Motor does not
rotate
| 003
Faulty supply voltageCheck the supply voltage, re-establish the voltage supply
Faulty connectionDisconnect from the power supply, correct the
connection, see circuit diagram.
Temperature monitor has
responded
Allow the motor to cool down, find and resolve the cause
of the fault.
| Troubleshooting/maintenance/repair/CO alarm
14
Troubleshooting cont'd
Electronics/motor
overheated
Insufficient coolingImprove cooling.
Overloaded motorCheck if the correct fan is used for your application.
Ambient temperature too highCheck if the correct fan is used for your application.
Note:
For all other damage/defects, please contact Systemair. Defective safety-relevant fans (for Ex and smoke
extraction applications) must be replaced completely.
11.3 Alarm and fault handling Carbon monoxide control unit
The control unit continuously monitors the sensor's function, as well as the function of the fans. The following subpoints describe the the meaning of the fault and CO-Alarm display and the way in which they should be responded to.
11.3.1Thresholds for fault displays
The control unit distinguishes between two fault types, which are specified in more detail in the table below.
Table 10 Fault display thresholds
Fault typeSetting thresholdReset threshold
Fan failureRPM < 130 rpm /
min
I
Sensor fault
< 3.0 mAI
4-20mA
RPM ≥ 180 rpm / minFan fault or fault with the fan supply cables
≥ 3.5 mA
4-20mA
Comment
–> Signalled after 10 seconds
Short circuit or break in the sensor cable
–> Signalled after 3 seconds
11.3.2Potential-free alarm contact
The illustration below explains the alarm contact's switching states.
Control terminals e.g. to connect an alarm signal
CO alarm — fault or voltage freeOperating ok
11.3.3Behaviour in the event of a CO alarm and fault handling
The control unit distinguishes between two fault types, which are specified in more detail in the table below.
| 003
Table 11 Behaviour in the event of a CO alarm and faults
No.
1
ProblemPossible causeRemedy / suggested solution
CO alarm
Critical CO concentration
reached
Troubleshooting/maintenance/repair/CO alarm |
1. If the fan and control unit is installed in a garage
and your vehicle engine is idling, switch the engine
off.
2. Leave the room immediately and seek fresh air.
Check that everyone is present. Do not go back
into the room before it has been ventilated and the
CO alarm has stopped.
3. If the alarm triggers again after 24 hours, repeat
steps 1-2 and call the emergency gas services
(please check you have their number now) and if
necessary notify the relevant gas fitter.
15
2
Fault
- Fan failure
- Sensor fault
Contact Systemair
11.4 Maintenance
Warranty claims can only be made if maintenance work is carried out correctly and written evidence thereof is
provided.
We recommend regular maintenance intervals to ensure continuous fan operation. These maintenance intervals are
specified in the “Activities” table below. In addition, the operator must carry out follow-up activities such as cleaning,
replacing defective components or other corrective measures. For traceability reasons, a maintenance plan must be
created which documents the work carried out. This must be created by the operator. If the operating conditions are
"extreme", the maintenance intervals must be reduced so that maintenance is carried out more frequently. Examples
of extreme operating conditions:
• Ambient temperature > 40 ºC or < -10 ºC, or temperature fluctuations > 20 K
Table 12 Activities
Extreme operating
conditions
Every six
months
Activity
Check the fan and its components for visible damage,
corrosion and contamination.
Check the impeller for damage and imbalance.
Check the condensate drain is working correctly.
Clean the fan/ventilation system (see 12 Cleaning, page
16).
Normal operating
conditions
Every six
months
XX
AnnuallyQuarterly
XX
XX
XX
Check the screwed connections for damages/defects and
check that they are firmly seated.
Check the fan intake is free from contamination.
Check that the fan and its components are being used
correctly.
Check the current consumption and compare this with the
rated data.
Check the vibration dampers (if used) are working
correctly and check for visible damage and corrosion.
Check the electrical and mechanical protective equipment
is working correctly.
Check the fan’s rating plate is legible.
| 003
X
XX
X
XX
X
X
XX
See normal operating
conditions
See normal operating
conditions
See normal operating
conditions
See normal operating
conditions
| Cleaning
16
Activities cont'd
Check the connection clamps and screwed cable
connections for damage/defects, and check that they are
firmly seated.
Check the flexible connectors for damage.
X
X
See normal operating
conditions
See normal operating
conditions
Note:
For all other damage/defects, please contact Systemair. Defective safety-relevant fans (for Ex and smoke
extraction applications) must be replaced completely.
11.5 Spare parts
♦ Use original spare parts from Systemair only.
♦ When ordering spare parts, please specify the serial number of the fan. This can be found on the name plate.
12Cleaning
12.1 Safety information
♦ Cleaning may only be carried out by adequately qualified persons, details see Table 1 Qualifications, page 1.
♦ Wear protective equipment during all work in the vicinity of the fan, details see 2.2 Personal protective equipment,
page 2.
♦ Observe the 5 rules of electrical safety, see 2.3 5 rules of electrical safety, page 2.
♦ Ensure that the power supply has been switched off (all-pole circuit breaker).
♦ The impeller must be at a standstill.
12.2 Procedure
Important
Keeping the fan clean extends its service life.
♦ Install a filter monitor.
♦ Do not use steel brushes or sharp-edged objects.
♦ Do not use a high-pressure cleaner (steam jet cleaner) under any circumstances.
♦ Do not bend the fan blades when cleaning.
♦ When cleaning the impeller, pay attention to balance weights that have been positioned
♦ Keep the airways of the fan clear and clean them if necessary with a brush.
13Deinstallation/dismantling
Deinstall and dismantle the fan in reverse order of installation and electrical connection.
14Disposal
♦ Ensure material is recycled. Observe national regulations.
♦ The device and the transport packaging are predominantly made from recyclable raw materials.
♦ Disassemble the fan into its components.
♦ Separate the parts according to:
• reusable material
• material groups to be disposed of (metal, plastics, electrical parts, etc.)
| 003
Commissioning Report
15Commissioning Report
Warranty claims can only be made if commissioning work is carried out correctly and written evidence thereof is
provided.
Fan
Description:
Article no.:Manufacturing order no.:
Installer
Company:Contact person:
Company address:
Tel. no.:Email:
Operator (Place of installation)
Company:Contact person:
Company address:
Tel. no.:Email:
|
17
Type of connection
Directly to mains
0-10 V signal (EC motor)
via contactor control
Transformer
Frequency converter
Sinus filter
Shielded cables
Motor protection
Motor protection switch or motor protection relay
PTC resistor
Resistance value [Ω]:
Thermal contact
Electrical motor protection
Others:
Functional check
Impeller easily rotatable (by hand)
Rotation direction acc. to directional arrow
YesNo
□□
□□
□□
□□
□□
□□
□□
YesNo
□□
□□
□□
□□
YesNo
□□
□□
Nominal data - Fan (name plate on fan housing)
Voltage [V]:Current [A]:
Frequency [Hz]:Power [kW]:
Fan impeller speed [rpm]:
Measured data at commissioning
Voltage [V]:Temp. of transported air [°C]:
Current L1 [A]*:
| 003
Fan impeller speed [rpm]:
| EU Declaration of conformity
18
Current L2 [A]:Air volume [m3/s]:
Current L3 [A]:
*For single-phase fans, fill in line “Current L1 [A]”*Δ- Pressure between suction-side and discharge of the fan
Differential pressure [Pa]*:
If an air flow measurement is not possible, this value can be calculated using the following formula:
The manufacturer declares that the above mentioned products in their design and construction and the version
marketed by us complies with the Harmonization legislation listed below:
EU directives:2006/42/ECMachinery directive
AJR; AJ8; AJR (B); AJ8 (B); AJ (F); AJR-TR; IV; IV smart; prioJet
2016