SystemAir E 28 Operator's Manual

Callender and temperature settings
LEDs and buttons – navigating the menus – (change parameters) .................. 2
Operator's level - tree structure ..................................................................................... 3
Running mode – Auto/On/O ........................................................................................ 3
Alarm – cancel, acknowledge ......................................................................................... 4
Setting of temperature ...................................................................................................... 5
Modication of outdoor compensated supply temperature .............................. 5
Setting of ows - Flow control ........................................................................................6
Setting of ows - Pressure control .................................................................................7
Schedule settings ................................................................................................................ 8
Calender settings (time, date, weekday) .....................................................................8
Setting of holidays .............................................................................................................. 9
Setting of extended running........................................................................................... 9
Setting of min/max supply air temperature ...........................................................10
Restore Systemair factory settings or latest user parameters
and settings ......................................................................................................................... 11
Annex 1A7 for the User manual
Software versions 3.2 , 3.3, 3.4 and 3.6
Operator's Guide for Systemair E 28 Controller
in large air handling units type: Geniox, DV, TIME, DV Compact
2
LEDs and buttons – navigating the menus – (change parameters)
UP: Move to a higher menu line (Increase value of the parameter)
The menus are organised in a horizontal tree structure – upper left corner is start
DOWN: Move to a lower menu line (Decrease value of the parameter)
RIGHT: Move right to a lower menu level (Move the curser to the right in the para­meter)
LEFT: Move left to a higher menu level.
(Move
the curser to the left in the parameter)
OK/ENTER: Open/activate a selected menu/setting (Conrm a parameter value)
ALARM: Press for alarm list
CLEAR: Abort a parameter setting and restore the original value, if ”OK/EN­TER” not yet has been pressed.
ALARM LED: Red light is ashing for unacknowledged alarm. Permanent red light for acknowledged alarm, but the alarm is still active, because the reason is not yet eliminated.
"WRITE ENABLE" LED: Yellow light – slow ashing indicates that a parameter can be selected for changes, when the OK/EN­TER button is pressed. Yellow light – fast ashing indicates that the parameter is activated for changes. Permanent yellow light indicates that the changes are going on.
Hand terminal – Systemair Control Panel LED's and buttons
3
Start display
Unit
Date - running mode
Running mode
Running mode On / O / Auto
Temperature Code - Setpoint
Selected functions
and actual values
Air control Code - Supply air
m3/h or Pa
Possibly CO2-
control
Code - Extract air
m3/h or Pa
Time settings Set time and date
Scedules
Start / Stop
Extended running
Access rights
Change level
Code - 1111
Operator's level - tree structure
Running mode – Auto/On/O
The display
shows
x 1
x 1
1.
2.
3.
4.
To select Auto, Manual Normal, Manual Reduced or O
5.
6.
The display is lit up
Running mode
Actual running mode
Conrm selected value with OK. The system will automatically return to the start menu after some minutes.
To return to the start menu at once – press and several times
x 2
Running mode Auto Manuel reduced run Manuel normal run O
Unit Date, time Syst: Running mode (Auto, Ma­nual reduced, Man. norm., O)
Start menus
Follow the steps
below
4
Alarm – cancel, acknowledge
The display
shows
x 2
1.
3.
4.
5.
Conrm with OK. Class A alarm is always triggered by the system, when the reason for alarm is hazardous, and it is only pos­sible to restart the unit, when the reason for the alarm has been solved. The Class A alarm can be triggered by the temperature sensor inside the water heating coil if the temperature falls below the set point value, or the class A alarm can be triggered by the re thermostats when the temperature rises above the set point values, indicating risk of re.
6.
7.
Press the alarm button twice to see the alarms logged in the alarm list
Select – Cancel. Never select Block, Block is only for test purposes during maintenance work.
To return to the start menu at once – press and several times
Conrm selected value with OK. The system will automatically return to the start menu after some minutes.
When the reason for the alarm has been solved, pressing the OK button will activate the menu - Conrm - and the unit starts. The alarm indication disappears from the display.
2.
Example: Low frost guard temp Date, time, Class:A Cancel
Example: Low frost guard temp Acknowledge Block Cancel
Example: Low frost guard temp Date, time, Class:A
Follow the steps
below
5
The display
shows
1.
2.
3.
6.
1.
2.
3.
4.
5.
6.
The display is lit up
Temperature
The system is congured to control a certain temperature. The actual value and set point for this temperature is shown. Access code 1111 may be necessary.
Set point temperatures for outdoor tempe­rature compensation are shown. The control curve is dened with 8 node points. Only 2 or 3 node points are shown in the display, and the remaining node points are displayed by scrolling and .
Temperatur
To return to the start menu at once – press and several times.
Select and conrm new set point tempera­ture. The system will automatically return to the start menu after some minutes.
x 1
x 2
x 1
x 1
x 1
x 2
4.
5.
Setting of temperature
Value to be changed ashes.
Value to be changed ashes.
Select one new set point temperature for each outdoor temperature shown on the curve and conrm selected value with OK.The system will automatically return to the start menu after some minutes.
Act: xx.x ˚C Setp Setp: yy.y ˚C
Setp: yy.y ˚C
Outdoor comp Setp. xx ˚C = zz.z ˚C yy ˚C = vv.v ˚C
Outdoor comp. Setp xx ˚C = zz.z. ˚C yy ˚C = vv.v ˚C
Unit Date, time Syst: Running mode (Auto, Ma­nual reduced, Man. norm., O)
To return to the start menu at once – press and several times.
Modication of outdoor compensated supply temperature
Follow the steps
below
6
The display
shows
x 1
x 1
x 2
x 1
x 3
1.
2.
10.
11.
12.
3.
4.
5.
Value to be changed ashes. Change of set point for normal ow (1/1) and for reduced ow (1/2). Access code 1111 may be necessary.
6.
7.
The display is lit up
Air control
Selection of supply air fan (SAF) or exhaust air fan (EAF).
Supply air fan selected as example.
Conrm change of the set point value with OK. Value to change is ashing.
Conrm selected value with OK
Conrm change of the set point value with OK. Value to change is ashing.
Outdoor compensation of the airow is able to reduce the air ow when the out­door temperature is low. Two node points
- outdoor temperature/airow denes the reduction of airow by declining outdoor temperature. The temperature compensa­tion between the 2 node points is linear.
Select and conrm new value for normal air ow (1/1) and for reduced air ow (1/2)
To return to the start menu at once – press and several times.
8.
9.
Setting of ows - Flow control
SAF (SAF = Supply air fan) EAF (EAF = Extract air fan)
Flow control SAF Setp. 1/1: xx.xxx m³/h Setp. 1/2: yy.yyy m³ /h
Setp. 1/1: x.xxx m³/h Setp. 1/2: y.yyy m³/h
Setp. 1/1: xx.xxx Setp. 1/2: yy.yyy
Outdoor comp. setp aa ˚C = bb.bbb m3/h cc ˚C = dd.ddd m3/h
Unit Date, time Syst: Running mode (Auto, Ma­nual reduced, Man. norm., O)
Follow the steps
below
Flow control (control of the ow through the fans)
7
The display
shows
x 1
x 1
x 2
x 1
x 3
1.
2.
10.
11.
12.
3.
4.
5.
Value to be changed ashes. Change of set point for normal ow (1/1) and for reduced ow (1/2). Access code 1111 may be necessary.
6.
7.
The display is lit up
Air control
Selection of supply air fan (SAF) or exhaust air fan (EAF).
Supply air fan selected as example.
Conrm change of the set point value with OK. Value to change is ashing.
Conrm selected value with OK
Conrm change of the set point value with OK. Value to change is ashing.
Outdoor compensation of the airow is able to reduce the air ow when the outdoor temperature is low. Two node points - outdoor temperature/pressure in ducts denes the reduction of airow by declining outdoor temperature. The temperature compensation between the 2 node points is linear.
Select and conrm new value for normal air ow (1/1) and for reduced air ow (1/2)
To return to the start menu at once – press and several times.
8.
9.
Setting of ows - Pressure control
Pressure control SAF (SAF = supply air fan) EAF (EAF = extract air fan)
Pressure control SAF Setp. 1/1: xxx Pa Setp. 1/2: yyy Pa
Setp. 1/1: xxx Pa Setp. 1/2: yyy Pa
Setp. 1/1: xxx Setp. 1/2: yyy
Outdoor comp. setp
aa ˚C = bbb Pa cc ˚C = ddd Pa
Unit Date, time Syst: Running mode (Auto, Ma­nual reduced, Man. norm., O)
Follow the steps
below
Pressure control
8
The display
shows
x 4
x 1
x 1
x 1
x 4
x 1
x 1
1.
1.
2.
2.
3.
3.
4.
4.
5.
5.
6.
6.
7.
7.
8.
8.
9.
The display is lit up
The display is lit up
Time settings
Time settings
Select Timer Normal speed (example). (Do not select Time/Date, because this is the Calendar setting – time, date, weekday of the internal clock in the controller)
Conrm selected value with OK. Value to be changed ashes.
Return to menu to select: Timer Normal Speed or Timer Reduced Speed and so on.
Conrm selected value with OK. The system will automatically return to the start menu after some minutes.
Select Time/Date (this menu permits the setting of time and date in the internal clock)
Time: aa:aa is activated for changes. Value to be changed ashes
Conrm with OK when all values are OK. The system will automatically return to the start menu after some minutes..
To select the correct value.
Conrm with OK.
Schedule settings
Normal Speed Monday Per 1: 09:00 - 16:00 (Periode 1) Per 2: 16:00 - 21:00 (Periode 2)
Monday Per 1: 07:00 - 1700 (Periode 1) Per 2: 17:00 - 07:00 (Periode 2)
Time: aa:aa Date: bbbb-bb-bb Weekday: Xxxxxxxxx
Unit Date, time Syst: Running mode (Auto, Ma­nual reduced, Man. norm., O)
Unit Date, time Syst: Running mode (Auto, Ma­nual reduced, Man. norm., O)
Time/Date Timer Normal Speed Timer Reduced Speed Extended running Holidays
Time/Date Timer Normal Speed Timer Reduced Speed Extended running Holidays
Calender settings (time, date, weekday)
To return to the start menu at once – press and several times.
Follow the steps
below
9
The display
shows
1.
1.
2.
2.
3.
3.
4.
4.
The display is lit up
The display is lit up
Time settings
Time settings
Select Holidays (Do not select Time/Date, because this is for setting the internal clock)
Select Extended running (Do not select Time/Date, because this is for setting the internal clock)
Conrm selected value (example). Value to be changed ashes.
Extended running is activated for changes. Value to be changed ashes
To select the correct value
Conrm with OK.
Conrm with OK when all values are OK. The system will automatically return to the start menu after some minutes
Conrm with OK when all values are OK. The system will automatically return to the start menu after some minutes.
x 4
x 1
x 1
x 1
x 4
x 1
x 1
7.
7.
8.
Setting of holidays
x 4
x 3
5.
6.
5.
6.
Holidays (MM:DD) 1: 01:01 - 01:03 2: 02:14 - 01:21 and so on - up to 24 holiday periods
Holidays (MM:TT) 1: 01:01 - 01:03 2: 02:14 - 02:21 and so on - up to 24 holiday periods
Unit Date, time Syst: Running mode (Auto, Ma­nual reduced, Man. norm., O)
Unit Date, time Syst: Running mode (Auto, Ma­nual reduced, Man. norm., O)
Time/Date Timer Normal Speed Timer Reduced Speed Extended running Holidays
Time/Date Timer Normal Speed Timer Reduced Speed Extended running Holidays
Extended running xx min Time in ext. Running: yy (minutes already spent of the total exten­ded running time)
Setting of extended running
8.
9.
To return to the start menu at once – press and several times.
To return to the start menu at once – press and several times.
x 1
Follow the steps
below
10
The system is now logged on at the Admin level and unskilled persons could change important parameters and settings to values that will cause malfunction of the system. Go to the start menu to return the system immediatlely to the lowest access level – Operator.
Digit to be changed ashes. Factory logged password, exclusively for service partners.
The display
shows
1.
2.
3.
4.
8.
7.
9.
10.
The display is lit up
Access rights
Select - Log on
Return to start menu
Temperature If the system is congured for cascaded
room temperature control, this menu with max/min supply air temperature is displayed.
Value to be changed ashes. Conrm se­lected value with OK
Access rights
Select - Log o and select the answer – Yes
System returns to the start menu and is now logged on at the Operator-level.
Select and conrm new set point temperature.
11.
12.
x 5
x 1
x 6
x 2
6.
x 6
Setting of min/max supply air temperature
x 2
x 2
x 2
5.
13.
Unit Date, time Syst: Running mode (Auto, Ma­nual reduced, Man. norm., O)
Log on Log o Change password
Log o? No Actual level: Admin
Log on Enter password **** Actual level: Operator
Actual level: Admin
With Caskaded control max/min supply air setp Max: xx ˚C Min: yy ˚C
Running mode Temperature Air control Time settings Manuel/Auto Settings Conguration Access Rights
Access to this menu requires log on at the high-authority level – ”Admin”.
Follow the steps
below
11
Digit to be changed ashes. Factory logged password, exclusively for service partners.
The display
shows
1.
2.
3.
4.
8.
9.
13.
10.
11.
12.
The display is lit up
Access rights
Select Log on
Return to start menu
Settings
Menus in settings
Select: – Restore factory settings: Yes/No – Restore user settings: Yes/No
Conrm with OK for selected alternative. Values to be changed ashes.
To select menu: – Save user setings: Yes/No
Value to be changed ashes. Conrm selected value with OK.
Select and conrm new setpoint.
The system is now logged on at the Admin level and unskilled persons could change important parameters and settings to values that will cause malfunction of the system. Go to the start menu to return the system immediatlely to the lowest access level – Operator
System returns to the start menu and is now logged on at the Operator-level.
Select - Log o and select the answer – Yes
Access rights
Save user settings: No
14.
15.
16.
x 5
x 2
x 1
x 1
x 2
x 1
x 3
x 1
x 2
6.
7.
Restore Systemair factory settings or latest user parameters and settings
x 2
x 2
5.
Unit Date, time Syst: Running mode (Auto, Ma­nual reduced, Man. norm., O)
Log on Log o Change password
Log o? No Actual level: Admin
Log on Enter password **** Actual level: Operator
Actual level: Admin
Running mode Temperature ... Access rights
Control temp Control ow Alarm settings
Restore factory settings: No Restore user settings: No
Access to this menu requires log on at the high-authority level – ”Admin”.
Follow the steps
below
12
Systemair A/S Systemair UAB Ved Milepælen 7 Linu 101 DK-8361 Hasselager LT-20174 Ukmergé
Tel. +45 87 38 75 00 Tel. +370 340 601 65 Fax +370 340 601 66
mail@systemair.dk info@systemair.lt www.systemair.dk www.systemair.lt
Systemair A /S – January 2018
Loading...