Page 1
DVCompact
WithReversibleHeatPumpSection
OperationandMaintenanceInstructions
©2016CopyrightUABSystemair
UABSystemaircanacceptnoresponsibilityforpossibleerrorsincatalogues,brochuresandotherprinted
material.UABSystemairreservestherighttoalteritsproductswithoutnotice.Thisalsoappliesto
productsalreadyonorderprovidedthatsuchalterationscanbemadewithoutsubsequentialchanges
beingnecessaryinspecicationsalreadyagreed.
Allrightsreserved.
Documentinoriginallanguage
2016-08-31 A001
211118-EN_GB
Page 2
Contents
1Warnings...................................................................................................................................1
2Refrigerantcontrol/reporting.......................................................................................................1
3Service......................................................................................................................................2
4Productdescription....................................................................................................................2
4.1Descriptionofcomponents................................................................................................3
4.1.1Supplyandextractairfans......................................................................................4
4.1.2Supplyandextractairlters.....................................................................................4
4.1.2.1Pressureguardlters.....................................................................................4
4.1.3Differentialpressuretransmitters..............................................................................4
4.1.4Rotaryheatexchanger............................................................................................4
4.1.4.1Rotormotor...................................................................................................4
4.1.4.2Rotationguard...............................................................................................5
4.1.5Compressors..........................................................................................................5
4.1.6Condenser/evaporatorcoil.......................................................................................5
5Unitcontrol................................................................................................................................6
5.1Heatpumpcontrol............................................................................................................6
5.1.1Mainscreen............................................................................................................7
5.1.2Basicinformationaboutdevices...............................................................................7
5.1.3Informationmenu....................................................................................................9
5.1.4Servicemenu.........................................................................................................11
5.1.4.1Manualmode................................................................................................11
5.1.4.2Othersettings................................................................................................12
5.1.5Alarms—Heatpumpsystem..................................................................................12
5.1.5.1Alarmdatalog...............................................................................................13
5.1.5.2Resetalarms.................................................................................................13
5.1.5.3Alarmlist.......................................................................................................13
5.2Controloftheairhandlingunit...........................................................................................15
5.2.1Controlpanel..........................................................................................................15
5.2.1.1OperatingtheControlpanel...........................................................................15
5.2.2Commissioning.......................................................................................................16
5.2.2.1BeforeStartingtheSystem.............................................................................16
5.2.2.2Initialsetupoftheunit....................................................................................16
5.2.2.3MenuoverviewOPERATOR/SERVICELEVEL................................................17
5.2.2.4Freecoolingdescription.................................................................................29
5.2.3Alarms...................................................................................................................29
6Maintenance..............................................................................................................................30
6.1Important.........................................................................................................................30
6.2MaintenanceIntervals.......................................................................................................30
6.3Cleaningtheunit..............................................................................................................31
6.4ChangingSupply/Extractairlter.......................................................................................32
6.5Checkingtherotatingheatexchanger................................................................................32
6.6Checkingthefans.............................................................................................................33
6.6.1Cleaning.................................................................................................................33
6.6.2Inspection...............................................................................................................33
6.7Checkingthecompressor.................................................................................................34
6.7.1Inspection...............................................................................................................34
6.8Checkingtheevaporatorandcondenser............................................................................34
6.8.1Cleaning.................................................................................................................34
6.8.2Inspection...............................................................................................................34
7Troubleshooting.........................................................................................................................35
8Additionalinformationonpersonnelsafetyandprotectivemeasures.............................................35
8.1Informationonairbornenoiseemissions............................................................................35
8.2Personnelsafetymeasures...............................................................................................35
9Disposalandrecycling...............................................................................................................36
9.1Disposaloftheheatpumpunit..........................................................................................36
9.2Disposaloftheairhandlingunit.........................................................................................36
Page 3
1Warnings
Theheatpumpunitcancausepersonalinjuryifinstalledorusedincorrectly.Readthedocumentationfor
theproductcarefullybeforeitisinstalledorcommissioned.
Danger
•MakesurethattheMainssupplytotheunitisdisconnectedbeforeperforminganymaintenanceor
electricalwork!
•Allelectricalconnectionsmustbecarriedoutbyanauthorizedinstallerandinaccordancewith
localrulesandregulations.
•Whencarryingoutwork/serviceonthecoolingcircuit(s),thepowermustbedisconnected,andthe
workonlyperformedbyauthorisedpersonnel.
Warning
•Bewareofsharpedgesduringmountingandmaintenance.Useprotectiveclothing.
•Skincontactwiththerefrigerantmustbeavoided.Useprotectiveequipmentsuchasprotective
goggles,glovesandsuitableclothing.Goodventilationmustbearranged.
•Ifrefrigerantmakescontactwithskin,carefullywashtheexposedpartofthebody .
•Incaseoffrostbite,treatanydamagedskinareaandseekmedicaltreatment.
•Ifrefrigerantmakescontactwiththeeyes,immediatelyuseeyewashorlukewarmwaterandvisita
doctor.
•Astherefrigerantisheavierthanair,therefrigerantmaydisplacetheairandcauseasphyxiationin
unfavorableconditions.
Important
•Forsafetyreasons,onlypersonnelwithrelevanttechnicalcompetencemayperforminstallationwork.
Theinstallationinstructionssuppliedmustbefollowed.
•TherefrigerantforthiscoolingunitisR410Aandcannotbereplacedwithanyothertypeofrefrigerant
withoutwrittenapprovalfromthesupplier.
•Serviceswitchesarelockedtopreventunauthorizedstart-upduringmaintenancework.Where
condensationwaterneedstobedrainedaway,correctconnectiontothedrainmustensurethis.The
installermustequiptheunitwithoperatingandmaintenanceinstructions.
•ThesesafetyregulationsonlyapplytoproductssuppliedbySystemairUAB.Itistheinstaller’s
responsibilitytocarryoutacomprehensivesafetyassessmentoftheunit,aswellaspreparing
safetyregulationssothatuserisabletosecuretheunitsuchthatitdoesnotcauseharmtopeople,
animals,materialorenvironment.Ifthereisanydoubtabouthowtointerprettheregulationscovering
safety,installation,operationandmaintenance,itisoftheutmostimportancethatadviceissought
fromSystemairUABoritsdistributors.
CarefortheEnvironment!
•Therefrigerantundernocircumstancesmustbereleasedintotheenvironment.
2Refrigerantcontrol/reporting
DVCompactDXRcomespre-lledwithR410A(50%R-32/50%R-125)refrigerant.
DVCompactDXRunitsbelongtothegroups“pieceunitscontainingmorethan3kgrefrigerantspercircuit“
and“equipmentthatcontainsuorinatedgreenhousegasesinquantitiesof5tonesofCO
ormore”anditmustbecheckedforleaks.Leakagecontrolwithrecordkeepingshallbedoneonce
DVCompact OperationandMaintenanceInstructions
211 118
1
2
SystemairSverigeAB
equivalent
Page 4
peryear.Refrigerantcontrolreportmustbealwaysestablishedbyacoolingcertiedpersonbefore
commissioningoftheunit.Anyquantitiesaddedorrecoveredduringmaintenance,servicingandnal
disposalwillneedtoberecordedalongwith:
•leakchecks
•actionstaken
•thenameoftheserviceCompany ,theengineer/technicianwhoperformedtheservicingand
maintenance
•dates
•resultsofinspections
Theserecordshavetobemadeavailabletothecompetentauthorityuponrequest.Differentregulations
canbevalidindifferentcountries.Checkwithyourlocalgovernment.
3Service
Beforecallingyourservicerepresentative,makeanoteofthespecicationandproductnumberfrom
thetypelabel(gure1).
Fig.1Typelabel
Position Description
1 Productordernumber
2
3
Productcode(productspecication)
Productitemnumber/productionnumber/consecutivenumber/date
(YYYYMMDD)
4Productdescription
DVCompactDXRairhandlingunitcontainsacompletestand-alonereversibleheatpumpsystem(heating
andcooling)witharotatingheatexchangerandtwofansections.Thesystemistestedandoptimized
beforedelivery.
TheheatpumpsystemisdeliveredwiththeR–410arefrigerantinthecircuit.InternalcontrollerpCOOEM
controlsallsafetyfunctionsandcapacityofdigitalscrollcompressors(DVCompactDXR–10,DVCompact
DXR–15comesonlywithonecompressor).Signalstostartheatingorcooling,aswellacapacitysignal,
DVCompact OperationandMaintenanceInstructions
211 118
2
SystemairSverigeAB
Page 5
aresenttopCOOEMcontrollerdirectlyfromthemainairhandlingunitcontrollerCorrigowhenthereisa
demandforheatingorcooling.
Capacityisregulatedaccuratelybytherstdigitalscrollcompressor.Whenthereisanincreasingcapacity
demand(morethan50%),therstcompressorspeedsuptothemaximumbeforethesecondcompressor
getsastartsignaltooperateatthemaximumcapacity.Thenthespeedoftherstcompressorwillbe
reducedtoaminimumtocontinueaccuratelyregulatecapacityabove50%.
Signalsfromthehighandlowpressuretransmittershelptoensuremaximumperformancewithout
exceedingsetvaluesandtherebypreventsafetyswitchesfromdisconnectingcoolingandheating.
Thissafetysystemensuresmaximumperformanceunderthegivenowsandtemperaturesofsupply
andexhaustair.
Heatpumpsystemhavetwoelectronicexpansionvalves.Oneexpansionvalveforheatingandanother
oneforcooling.Superheatiscontrolledbyabuilt-incontroller.Abuilt-incontrollerreceivessignalsfroma
Lowpressuretransmitterandtemperaturesensorplacedinthecommonsuctionline.Thisensuresavery
accurateandefcientperformanceofthesystemunderalloperatingconditions.
A4–wayvalvechangesfunctionofthesystembetweenheatingandcoolingmode.
4.1Descriptionofcomponents
Fig.2Leftmodel,size20
Note:
ThelocationofcomponentsinRightmodelismirrored.Startingsize50,theelectricconnectionboxofthe
heatpumpisinstalledinsidetheunitandnotmountedonthedoors.
Position Description
1
2
3
4
5
6
7
DVCompact OperationandMaintenanceInstructions
211 118
Extractairfan
Supplyairfan
Extractairlters
Supplyairlters
Frequencyconverter,supplyairfan
Frequencyconverter,extractairfan
Differentialpressuretransmitter(CAV),extractair
3
SystemairSverigeAB
Page 6
Position Description
8
9
10
11
12
13
14 Rotaryheatexchanger
15 Rotormotor
16 Rotorbelt
17 Rotorguard
18 Drainpipe
Differentialpressuretransmitter(CAV),supplyair
Electricconnectionboxoftheairhandlingunit,Corrigocontroller
Electricconnectionboxoftheheatpump,Carelcontroller
Compressors
Evaporator/Condensercoilintheextractaircompartment
Evaporator/Condensercoilinthesupplyaircompartment
4.1.1Supplyandextractairfans
Fansandmotorsinunitsaremountedonvibrationdampers.Dustanddirtcanbuildupontheimpellers,
whichcancreateimbalanceandvibration.Theimpellersshouldbecheckedannuallyandcleanedwhen
necessary.Atthesametimevibrationdampersshouldbechecked.Damagedvibrationdampersmust
bereplaced.
Thedrivemotorshavepermanentlylubricatedbearingsthatshouldnotbegreased.
4.1.2Supplyandextractairlters
TheltersareofbagltertypewithlterqualityM5,M6orF7forthesupply-andextractairlter.Thelters
needtobereplacedwhenpolluted.Newsetsoflterscanbeacquiredfromyourinstallerorwholesaler.
4.1.2.1Pressureguardlters
Apressureguardmeasuresthedifferentialpressureoverthesupplyandextractairlters.Whenthe
pressuredropreachesthesetvalueanalarmistriggeredinthemaincontroller.Thedifferentialpressure
canbesetbetween40and300Pa.Thepressureswitchispresetfromfactoryto200Pa.
4.1.3Differentialpressuretransmitters
2builtinpressuretransmittersmaintaintheairowataconstantlevelbymeasuringthedifferential
pressureovertheinletconeofthefanimpellers.Thepressuretransmittersareinstalledfromfactoryin
allunitswithenclosedcontrolandCAVcontrol.InV AVunitspressuresensorswillbedeliveredloosely
withtheunittobemountedinthesupplyandextractairducts,see“Installationinstructions”formore
informationconcerningV AVinstallations.Thebuiltinpressuretransmitterswillthenworkasmonitorsof
theactualairow.
4.1.4Rotaryheatexchanger
DVCompactDXRunitisequippedwithahigh-efciency,rotaryheatexchangerwhichisusedtotransfer
theheatbetweenextractandsupplyairstreams.Operationoftherotaryheatexchangerisautomaticand
dependsonthesettemperature.Theheatexchangerisremovableforcleaningandmaintenance.
4.1.4.1Rotormotor
Themotoriscontrolledbya0–10Vanalogcontrolsignal.
DVCompact OperationandMaintenanceInstructions
211 118
4
SystemairSverigeAB
Page 7
4.1.4.2Rotationguard
Asensorbuilt in the rotor motor registerstherotationoftheheatexchangerrotor.It’sconnectedtothe
mainregulator,whichgivesanalarmiftherotorstopswhilethereisaheatdemand.
4.1.5Compressors
ThecompressorinDVCompactDXRunitisahigh-efciency ,variablespeedscrollcompressor .Itis
designedespeciallyforspeedcontrolandcannotrunwithoutfrequencyconverter.Speedandbythat
capacityisregulatedbychangingtheoperatingfrequency.Controlofthecompressoriscompletely
automaticaccordingtotheneedofthepremisesandthesignalthatcomesviathecontrollerpCOOEMto
thefrequencyconverter.
Theheatpumpsystemcomespre-lledwithR410Arefrigerantandtestedatthefactory.
4.1.6Condenser/evaporatorcoil
Theevaporator/condensercoilismadeofcoppertubeswithaluminiumnsandisusedtotransferthermal
energybetweenoutdoorandindoorairstreams.Condenser/evaporatorcoilchangesitsfunctionbasedon
theactivemode:
•Heatingmode—coilintheextractaircompartmentisanevaporator,coilinthesupplyaircompartment
isacondenser.
•Coolingmode—coilintheextractaircompartmentisacondenser,coilinthesupplyaircompartment
isanevaporator.
DVCompact OperationandMaintenanceInstructions
211 118
5
SystemairSverigeAB
Page 8
5Unitcontrol
5.1Heatpumpcontrol
HeatpumpiscontrolledviapGD1controlpanel.ThecontrolpanelpGD1has6buttonswiththefollowing
functions:
Fig.3ControlpanelpGD1
Position
1
2
3
4
5
6
Symbol
Description
•Alarmsymbol
Displaythelistofactivealarms
•Prg—programmingkey
Accessthemainmenu
•Esc
Returntothepreviousscreen
•Enterarrow
Switchfromparameterdisplaytoedit
Conrmvalueandreturntotheparameterlist
•Uparrow
Navigatebetweenthedisplayscreensorincreasethevalueshownon
thedisplay
•Downarrow
Navigatebetweenthedisplayscreensordecreasethevalueshownon
thedisplay
DVCompact OperationandMaintenanceInstructions
211 118
6
SystemairSverigeAB
Page 9
5.1.1Mainscreen
Thefollowingillustrationisanexampleofthemainscreenwithanactiveunit:
31/03/2016
Comps:
ExV:
Req: 50%→ 17%
Regulating
Thu
CntDwn:
0°0K
Fig.4Mainscreen
1.Dateandtime.
2.Currentstatusoftheunit:
Summer
UnitOFF
3.Statusofinternaldevices:
•Compressorsinoperationandtheircapacity.
•Countdown,minimumtimebetweenon/off.
•SuperheattemperatureinKandexpansionvalveopeningin%.
4.Systemcapacityrequestandactualpoweroutput:
•SystemOFF
•ONbyinput(butnocapacitysignal)
•Regulating
•Pump-Down(timerisactive)
•Manualmode
•OFFalarm
mode
(cooling)
11:56
35%
11s
0%
Wintermode
(heating)
Defrostingin
progress
5.Indicatesaccesstotheinformationmenu.Use
toconrm.
, arrowkeysforselectionand arrowkey
5.1.2Basicinformationaboutdevices
Informationaboutthestatusoftheunitisaccessibledirectlyfromthemainmenu,withoutneedtoaccess
submenus.Use , arrowkeystogothroughloopofscreenswhichcontaindetailedinformation
aboutdevices.
Theindividualscreensareshownbelow:
BSynoptic—Circ. 1
DZ2:Prev—10%
5.6barg→
EZ8:LoDscgP
5.6barg→
Fig.5Compressorstatus
1.Dischargetemperaturezoneandpreventiveaction.
2.Dischargetemperature.
DVCompact OperationandMaintenanceInstructions
211 118
70.0°
10.0°
50%
60s
70.2°
10.0°
7
SystemairSverigeAB
Page 10
3.Condensingpressureandtemperature.
4.Statusofcompressorsandcapacity.
5.Envelopezoneandtime:
•EZ1:Ok-zonewithinoperatinglimits.
•EZ2:HiDP-Highcompressionratio.
•EZ3:HiDPscgP-Highcondensationtemperature.
•EZ4:HiCurr-Highmotorcurrent.
•EZ5:HiSuctP-Highsuctionpressure.
•EZ6:LoDP-Lowdifferentialpressure.
•EZ7:LoPRat-Lowcompressionratio.
•EZ8:LoDscgP-Lowcondensationpressure.
•EZ9:LoSuctP-Lowevaporationpressure.
6.Suctiongastemperature.
7.Evaporatingpressureandtemperature.
BSynoptic—ExV1A
SH:5.0K
5.0°C
300stp
70%-Heat.
EEV:
Close
10.0barg
0.0°C
Fig.6Expansionvalveoverview
1.Superheatandactualsetpoint.
2.Suctiongastemperature.
3.V alveopeningmode,percentageandsteps.
4.Statusoftheexpansionvalve:
•Close-valveclosed.
•Std-by-valveinstandbyposition.
•Pos-valveinpositioning.
•Wait-afterpositioningandincaseofchangeofcoolingcapacitygreaterthan10%,theexpansion
valvehavetodoalargemovementthatcantakesomeseconds.Waitingtimewillbedisplayed
duringthisphase.
•On-valveinregulation.
•Init-driverinitialization.
5.Evaporatingpressureandtemperature.
DVCompact OperationandMaintenanceInstructions
211 118
8
SystemairSverigeAB
Page 11
Info
PressENTERtocheck
advanceddevicesinfo
→I/Ostatus
→Workinghours
→Devicesinmanual
→Systeminfo
Fig.7Screentoadvancedinformationmenus
Inthisscreen,press
5.1.3Informationmenu.
Digitalandanalogueinputs/outputs,alsoinformationaboutrmwareandhardwarearedisplayedin
thesescreens.
arrowkeytoaccessadvancedinformationsubmenus.Moredetailsinsection
5.1.3Informationmenu
Use
Info—Output
Comp.1–Digitalscroll
NO11
NO2Digitalvalve
Power:
Hours:
Info—Output
Compressor2
NO12
, arrowkeystogothroughloopofscreenswhichcontainadvancedinformationaboutdevices.
Showsthestatusoftherstcompressor.
ShowsthestatusofNO2digitalvalve.
On
Off
100.0%
0000/030000h
Showstheloadofthecompressorin%.
Showsremainingtimeuntilmaintenanceofthe
compressor.
Showsthestatusofthesecondcompressor.
Showsremainingtimeuntilmaintenanceofthe
compressor.
Off
Hours:
Info—Output
NO3–Oilvalve:
NO4–4watvalve:
NO5–Lowpressureal.:
NO6–ExValarm:
NO7–Generalalarm: Off
NO9–Defrost:
NO10–Dischargeal.:
Info—Output
Y1–Envelop:
Y2–Comp.fbk: 100%
Y3–ExVperc. 0%
DVCompact OperationandMaintenanceInstructions
211 118
0000/030000h
Off
Heat
On
Off
Off
Off
0.0%
Showsdigitaloutputsfromdevicesandalarms.
Showsoutofenvelopepositionin%.
Showscompressorspeedin%.
Showsexpansionvalveopeningin%.
9
SystemairSverigeAB
Page 12
Info—Input
Suctionpressure
U6: 0.0barg
Evap.temp.:
Suctiontemperature
U2:
Shows suctionpressure,evaporatingtemperatureand
suctiontemperature.
0.0°C
0.0°C
Info—Input
Defrost
Evap.temp:
Filtered:
CntDwn: 2990 0
Defroststatus:
Checkstart 5s
Info—Input
Dischargepressure
U5:
Evap.temp:
Dischargetemperature
U4:
Subcool.temp.
Subcooling
Info—Input
Dischargetemperature
U11Comp.2:
U12Comp.3:
Optionalprobes
U8:
U9:
U10:
Info—Input
Capacityreference
0.0°C
0.0°C
0.0barg
0.0°C
15.7°C
5.7°C
0.0°C
0.0°C
0.0°C
0.0°C
0.0°C
0.0°C
Showsinformationaboutdefrostinganditsstatus.
Showsdischargepressure,condensing,dischargeand
subcoolingtemperatures.
Shows temperaturereadingsfromdischargeandoptional
probes.
Shows currentcapacity.
U7
Info—Input
ID1–Alarmreset:
ID2–Cooling:
ID3–Defrost:
ID4–RemoteON:
Info—Dig.In
ID7–Comp.alarm:: Ok
ID8–Phasealarm:
ID9–Lowpress.:
ID10–Highpress.
48.5%
Showsdigitalinputs
Off
Cool
Ok
On
Showsthestatusofalarms.
Ok
Ok
Ok
DVCompact OperationandMaintenanceInstructions
211 118
10
SystemairSverigeAB
Page 13
Information
ShowsuserinterfacecodeandpGD1terminalversion.
NOSTDmCOMM
Version: 2.1.009
Date:
Bios: 6.27
Boot: 5.00
Information
Boardtype:
Boardsize:
Totalflash:
RAM:
Built-Intype:
Maincycle:
4.8cycle/s
06/05/15
09/07/04
09/07/04
2048KB
1024KB
0.0°C
Showssoftwarereleasedate.
ShowssystembootandBIOSversions.
Showsinformationaboutcontrollerboard.
5.1.4Servicemenu
Important
•Servicemenuisprotectedwithapasswordandshouldbeaccessedonlybyauthorizedpersonnel.
•Authorizedpersonnelisfullyresponsibleforanychangesintheservicemenu.
•Improperchangesintheservicemenucanresultinmalfunctionoftheunit.
Regardlessofthedisplayedscreen,pressingthe programmingkeyaccessesthepasswordentry
screenwhichallowsaccessservicelevelmenus.Press
toselectadigitandconrmeachdigitwithan
Theuserwillbeautomaticallyloggedoutfromservicemenuafter5minutesofinactivity.Itispossibleto
logoutwithoutwaiting5minutesinLog-Outmenu.
Servicelevelgivesaccesstoreadallparameterswiththepossibilitytoeditsomeofthem.Theaccess
levelneededtoeditvaluesisshownonthetopleftcornerofthescreenoncesettingforeditingisselected.
Asettingwithaashing“S ”letterisintendedtobeusedforserviceandasettingwithashing“M ”is
intendedtobeusedbyamanufactureronly.Examplesbelow:
S Manualmode
Comp.1circuit1
Hours:
Nextthr.:
Status:
Manual
0001h
30000h
100%
AUTO
arrowkey.Insertthecorrectpassword(default1 111).
keyoncontrolpanel,use , arrowkeys
M ExV
Enablepumpdown:
Type: ATSTOP
YES
5.1.4.1Manualmode
SettingsinManualmodemenuallowtocontrolcomponentsmanually.Onlyauthorizedpersonnelshould
performchangesinManualmode.Manualcontrolofcomponentsisnecessaryforannualmaintenance
totestsafetyandcontrolfunctionsorafterreplacementofcomponents.
DVCompact OperationandMaintenanceInstructions
211 118
11
SystemairSverigeAB
Page 14
S Manualmode
Comp.1circuit1
Hours:
Nextthr.:
Status:
Manual
Showsoperatinghoursoftherstcompressor.
Setnextthresholdofoperatinghoursuntilmaintenance.
0001h
30000h
100%
AUTO
Showscurrentstatus.
SetcompressorcontroltoAUTOormanualoutput
0-100%.
S Manualmode
Comp.2circuit1
Hours:
Nextthr.:
Status:
Manual
S Manualmode
ExVcirc.1heating
Enablemanual
valveposition:
Manualvalve
position:
S Manualmode
ExVcirc.1cooling
Enablemanual
valveposition:
Manualvalve
position:
S Manualmode
Showsoperatinghoursofthesecondcompressor.
Setnextthresholdofoperatinghoursuntilmaintenance.
0001h
30000h
Off
AUTO
B
IIIIstep
B
IIIIstep
Showscurrentstatus.
SetcompressorcontroltoAUTOormanualoutput
0-100%.
Set manualpositionofexpansionvalveforheating.The
expansionvalvehave0–480steps.
Set manualpositionofexpansionvalveforcooling.The
expansionvalvehave0–480steps.
Set dateandtimeoftheunit.
Day:
Month:
Year:
Hour:
Minute: 56
S Manualmode
Language ENGLISH
ENTERtochange
ESCtoconfirm
17
02
16
Monday
13
Shows currentlanguageofthecontrolpanel.
OnlyEnglishlanguageiscurrentlyavailable.
5.1.4.2Othersettings
Settingsthatarenotshownorexplainedinthisdocumentarepre-conguredatthefactoryandmust
notbechanged.
5.1.5Alarms—Heatpumpsystem
Activealarmscanbecheckedbypressing
DVCompact OperationandMaintenanceInstructions
211 118
alarmbutton.
12
SystemairSverigeAB
Page 15
Itpossibletocheckthealarmdatalogbypressing arrowkey .Ifthereisatleastonealarm,thescreen
ofalarmsisdisplayedandalarmsaresortedbycodefromlessertogreater.
Eachalarmcontainstheinformationneededtounderstandthecauseofthealarm:
Alarms 001/002
07/05/2015
Lowpressure
bypressostat
Evap.temp.1:
Cond.temp.1:
ENTERforDataLog
AL018
13:28
0°C
45°C
Fig.8Alarmsscreen
1.Alarmnumber/totalalarmsanduniquealarmcode.
2.Alarmdateandtimeofoccurrence.
3.Shortalarmdescription.
4.V alueoftheprobelinkedtothealarm.
TheredLEDunderthe
•Off:noactivealarm.
•Flashing:thereisatleastoneactivealarmandthedisplayshowsascreenthatisnotpartofthe
alarmsloop.
•On:thereisatleastoneactivealarmandascreenthatispartofthealarmsloopisdisplayed.
alarmbuttoncanbe:
5.1.5.1Alarmdatalog
Thealarmdatalogcanbedisplayedbypressing
Thealarmdatalogmemorizestheunitoperationstatuswhenthealarmsaretriggered.Eachlogentryis
aneventhatcanbedisplayedfromamongalloftheeventsavailableinthememory.Theinformation
savedinthescreenofalarmswillalsobesavedinthealarmdatalog.Themaximumnumberofevents
thatcanbesavedis100.Oncethelimitisreached,themostrecentalarmwilloverwritetheoldestone.
arrowkeywhileinthealarmscreen.
5.1.5.2Resetalarms
Thealarmscanberesetmanually,automaticallyorautomaticallywithretries:
•Manualreset:whenthecauseofthealarmhasstopped,theuserhastoenteralarmmenuand
acknowledgethealarmbypressing
•Automaticreset:whenthecauseofalarmissolved,thesystemwillrestartautomatically.
•Automaticresetwithretries:thenumberofinterventionsperhourischecked.Ifthatnumberislessthan
thesetmaximum,thealarmisonautomaticreset,oncethelimitisexceededitswitchestomanualreset.
alarmbutton.Theunitwillrestart.
5.1.5.3Alarmlist
Code
AL001
AL002
AL003
AL004
Descriptionondisplay Reset
ProbeU1brokenordisconnected
ProbeU2brokenordisconnected
ProbeU4brokenordisconnected
ProbeU5brokenordisconnected
1
Action Delay
A None 10s
A
A
A
CircuitOFF
CircuitOFF
CircuitOFF
No
10s
No
DVCompact OperationandMaintenanceInstructions
211 118
13
SystemairSverigeAB
Page 16
Code
AL005
AL006
AL007
AL008
AL009
AL010
AL011
AL012
AL013
AL014
AL015
AL016
AL017
AL018
AL019
AL020
AL021
AL022
AL023
AL024
AL025
AL026
AL027
AL028
AL029
AL030
AL031
Descriptionondisplay Reset
ProbeU6brokenordisconnected
ProbeU7brokenordisconnected
ProbeU8brokenordisconnected
ProbeU9brokenordisconnected
ProbeU10brokenordisconnected
ProbeU11brokenordisconnected
ProbeU12brokenordisconnected
LowSHalarm
LOPalarm
MOPalarm
Lowsuctiontemp.
Highdischargepress.
Lowsuctionpressure
Lowpressurebypressostat
(pressureswitch)
Envelopealarm
Motorphasealarm
Highpressurebypressostat
(pressureswitch)
Highdischargetemp.
compressor1
Highdischargetemp.
compressor2
Highdischargetemp.
compressor3
Pump-downendformaxtime
circuit1
Maintenancerequestcompressor
1
Maintenancerequestcompressor
2
Maintenancerequestcompressor
3
Clockalarm
Memoryexpansiondamaged
BMSOffline
1
Action Delay
A
CircuitOFF
A None No
A None 10s
A None 10s
A None 10s
A
A
M
A
A
A
M
A
A
A
A
M
A
A
A
Compressor2
OFF
Compressor3
OFF
CircuitOFF
CircuitOFF
CircuitOFF
CircuitOFF
CircuitOFF
CircuitOFF
CircuitOFF
CircuitOFF
CircuitOFF
CircuitOFF
CircuitOFF
Compressor2
OFF
Compressor3
OFF
A None No
A None Parameter
A None Parameter
A None Parameter
A None No
A None No
A
50%
10s
10s
10s
180s
180s
180s
180s
3retries
3retries
3s
300s
No
3retries
60s
No
No
60s
1.A—automatic,M—manual
DVCompact OperationandMaintenanceInstructions
211 118
14
SystemairSverigeAB
Page 17
5.2Controloftheairhandlingunit
Note:
IfDVCompactDXRunitwasorderedanddeliveredwithairhandlingsectionswithoutanyenclosedcontrol
orwiring,itwillnothavecontrolpanelandalternativecontrolmethodhavetobeprovidedbytheinstaller!
5.2.1Controlpanel
TheSCPcontrolpanelisdeliveredwitha10mcablethatisconnectedtothepanelandwithafastcoupling
contact,connectedtotheDVCompactDXRunit.ThecontactisconnectedtotheCorrigocontrollerinthe
electricalconnectionbox.Thecablecanbeunscrewedinthebackofthecontrolpanel(gure9).
Generalinformationisshowningure9.
5.2.1.1OperatingtheControlpanel
Fig.9Thecontrolpanel
Posi-
tion
1
2
3
4
5
6
7
8
9
10
11
12
13
DVCompact OperationandMaintenanceInstructions
211 118
Explanation
Alarmbutton:Givesaccesstothealarmlist
AlarmLED:Indicatesalarmbyashingredlight
WriteLED:Indicatesbyashingyellowlightthatparameterscanbesetorchanged
OKbutton:Pressthisbuttontobeabletochangeorsetparameterswheneverpossible.Also
usedtomovebetweenchangeableparametersinonedialoguewindowframe
Cancelbutton:Usedtoabortachangeandreturntotheinitialsetting
Right/Left&Up/Downbuttons:Usedtomoveup,down,left&rightinthemenutree.Up/Down
buttonsarealsousedtoincreaseordecreasevalueswhensettingorchangingparameters
Mountingholes
Connectionblock
Connectiontoyellowcable
Connectiontoorangecable
Connectiontoredcable
Connectiontobrowncable
Connectiontoblackcable
15
SystemairSverigeAB
Page 18
5.2.1.1.1NavigatingtheMenus
Thestartdisplay(thedisplaynormallyshown)isattherootofthemenutree.PressingDOWNwillmove
youthroughthemenuoptions.UPwillmoveyoubackthroughtheoptions.T oenterahighermenulevel,
useUPorDOWNtoplacethecursoratthemenuyouwishtoaccessandpressRIGHT .Ifyouhave
sufcientlogonprivilegesthedisplaywillchangetothemenuyouhavechosen.
AteachleveltheremaybeseveralnewmenuswhichyoumovethroughusingUP/DOWN.Sometimes
therearefurthersubmenuslinkedtoamenuormenuitem.Thisisindicatedbyanarrowsymbolatthe
right-handsideofthedisplay.T oenteramenu,pressRIGHTagain.Tostepbacktopreviousmenu
level,useLEFT .
5.2.2Commissioning
5.2.2.1BeforeStartingtheSystem
Whentheinstallationisnished,checkthat:
•Theunitisinstalledinaccordancewiththeinstallationinstructions
•Theunitiscorrectlywired
•Theductsystemiscorrectlyconnectedtotheunit
•Outdoorairintakeispositionedwithsufcientdistancetopollutionsources
•Allexternalequipmentareconnected
•Thefollowingdataisavailable:
•Intendedconguration,forexampletemperaturecontrolfunctions,fancontrol,externalcontrol
functionsetc.
•Howtheunitissupposedtooperateaccordingtoaweeklyschedule(normalandreducedspeed).
5.2.2.2Initialsetupoftheunit
Ontherststart-up,thecontrollerwillstartaspecialprogramforsettinglanguage,supplyairtemp
setpoint,Time&dateandweekschedulefornormalspeed.Usethe“OK”buttontomovebetween
changeableparametersandtheUP/DOWNarrowstoseethedisplayedalternatives.Conrmbypressing
“OK”oncemore.MoveondowninthemenustructurebyuseoftheUP/DOWNarrows.
Thefollowingwillbedisplayed:
1
Selectlanguagebypressing“OK”andthenmove
betweenthealternativeswiththeUP/DOWN
buttons.Conrmbypressing“OK”.Movetothe
nextlevelbypressingthe“DOWN”button.
gure
2
Showstheactualextractairtemperature
Setthesupplyairsetpoint.Defaultis18°C(logon
toservicelevelneeded,code2222,tochange
defaultsetting)
gure
3
Checkandmakesurethatcorrecttimeanddateis
displayed,ifnotchangethesettings
ChooseLanguage
English
Extractairtemp
Actual:.... ºC
Setp.: 18ºC
Time: 12.46
Date: 2010–03–12
Weekday: Friday
gure
DVCompact OperationandMaintenanceInstructions
211 118
16
SystemairSverigeAB
Page 19
4
Settheweekscheduleforhowit’sintendedforthe
unittooperateatnormalspeedduringMondayto
Friday.It’spossibletoset2periodsperday .
gure
Normalspeed
Monday→Friday
Per1: 07:00–16:00
Per2: 00:00–00:00
5
Settheweekscheduleforhowit’sintendedforthe
unittooperateatnormalspeedduringSaturdays
andholidays.It’spossibletoset2periodsperday.
gure
6
Settheweekscheduleforhowit’sintendedforthe
unittooperateatreducedspeedduringMondayto
Friday.It’spossibletoset2periodsperday
gure
7
Settheweekscheduleforhowit’sintendedforthe
unittooperateatreducedspeedduringSaturdays
andholidays.It’spossibletoset2periodsperday.
gure
Normalspeed
Saturday→Holiday
Per1: 00:00–00:00
Per2: 00:00–00:00
Reducedspeed
Monday→Friday
Per1: 00:00–00:00
Per2: 00:00–00:00
Reducedspeed
Saturday→Holiday
Per1: 00:00–00:00
Per2: 00:00–00:00
8
Select“Yes”or“No”
gure
Afternishingthesetupthemenusystemfor“Operatorlevel”willbeavailable.
SeebelowmenuoverviewthatdisplaystheavailablemenusintheOperatorlevelfollowedbythe
“Servicelevel”manual.
ToenterServicelevelusecode2222inthe“Accessrights”menu.Foroperatorlevelusecode1 111.
EndWizard
No
Note:
ToperformmoreadvancedsettingspleaseseetheenclosedCDwheretheCorrigoE–manualcan
befound.
5.2.2.3MenuoverviewOPERATOR/SERVICELEVEL
BelowmenuoverviewshowsboththeOperatorandServicelevel.Theoverviewofthepartsuniqueto
theServicelevelinbelowtablearemarkedwithgreybackgroundcolor.T ologontotheServicelevel
usecode2222underAccessrights.
DVCompact OperationandMaintenanceInstructions
211 118
17
SystemairSverigeAB
Page 20
Mainmenuitem
SystemairAS
Sub-menuitem1 Sub-menuitem2
Explanations
Startscreenheadline
2010–03–1509:00
System:Stopped
Sp:18.0Act: ºC
→Runningmode →Runningmode Runningmode
Auto
Runningtime
SAF:0.0h
EAF:0.0h
→ Selected
functions
Control
function
Extractair
control
Fancontrol
Flowcontrol
Heating: Water
Exchanger:
Rot. Excha
Canbesetto5differentlayouts
(Changeableat“systemlevel”
undertheconfiguration
menu).
Set RunningmodetoAuto,
OnorOff
Shows thetimeinhoursthat
themotorshavebeenoperating
SAF=Supplyairfan
EAF=Exhaustairfan
Shows typeofairtemperature
controltheunitisconguredfor.
Shows typeoffanspeed
controltheunitisconguredfor
Showstypeofheatingselected
Showstypeofexchanger
selected
Cooling: Water
Freecool
active: No
Supportcontrol
Active: No
CO2/VOCactive
Never
Firedamper
function
Notactive
Operationwhen
alarm
Stopped
Frost
protection
Active
Cooling
recovery
No
Externalset
point
Showstypeofcoolingselected
Showsthestatusofthefree
coolingfunction
Shows thestatusofthesupport
controlfunction
Shows thestatusofthe
demandventilation(CO2/VOC)
function
Shows thestatusofthere
damperfunction
Shows thestatusofthefrost
protectionfunction
Shows thestatusofthecooling
recoveryfunction
Shows thestatusofthe
externalsetpoint
Notactive
DVCompact OperationandMaintenanceInstructions
211 118
18
SystemairSverigeAB
Page 21
Mainmenuitem
→Temperature
Sub-menuitem1 Sub-menuitem2
→Alarmevents
→Input/Output
→Analogue
inputs
→ Digital
inputs
→ Universal
inputs
→ Analogue
outputs
→ Digital
outputs
Extractair
temp
Act.: ºC
Setp: 18.0ºC
Explanations
Showsallregisteredalarms
alongwiththetimeanddate
theyoccurred
Movedownandupinthelistby
pressing↑↓
Shows thestatusofthe
Ananlogueinputs
Shows thestatusoftheDigital
inputs
Shows statusofUniversal
Analogueinputs
Shows statusofUniversal
Digitalinputs
Shows thestatusofthe
Analogueoutputs
Shows thestatusoftheDigital
outputs
Shows thecongured
temperaturecontrol(Defaultis
Extractairtemp )
Shows theactualtemperature
inthechosencontrolmode
Outdoortemp:
ºC
Supplyairtemp
Actual: ºC
Setp: 18ºC
Frost
protection
Actual: ºC
Exhaustair
temp
Ifcascade
control
Max/minsupply
setp.
Max: 30ºC
Min: 12.0ºC
Set thetemperatureforthe
chosencontrolmode
Set themaximumandminimum
allowedsupplyairtemperature
incaseofcascadecontrol
Logontoservicelevelneeded
tochangesettings
Showstheactualoutdoorair
temperature
Shows theactualsupplyair
temperature
Shows thecalculatedsupply
airsetpoint.Theexhaust
aircontrolleroutputsignal
generatesthesupplyair
controller’ssetpointvalue
Shows theactualwater
temperatureinthewater
heatingbattery .(Onlyvisiblefor
HWunits)
Shows theactualexhaustair
temperature.
Actual: ºC
DVCompact OperationandMaintenanceInstructions
211 118
19
SystemairSverigeAB
Page 22
Mainmenuitem
→AirControl
Sub-menuitem1 Sub-menuitem2
Efficiency
Exchanger
Actual: %
Flowcontrol
SAF
Explanations
Showstheactualheatrecovery
efciency
Thefunctioncalculatesthe
heatexchangerstemperature
efciencyin%whenthe
outputsignaltotheexchanger
ishigherthan98%andthe
outdoortemperatureislower
than10°C.
Whenthecontrolsignalis
lowerthan98%ortheoutdoor
temperatureishigherthan10°C
thedisplaywillshow0%.
Thismenuoptionbecomes
visibleiftheunitiscongured
for"Flowcontrol"or"Pressure
control"
Shows airowforthesupplyair
fan(constantairowcontrol)
Actual: m³/h
Setp.: m³/h
Flowcontrol
EAF
Flowcontrol
SAF
Setp1/1: 1100
m³/h
Setp1/2: 550
m³/h
Outdoor
comp.Setp. 1
—20°C=10m³/h
0°C=0m³/h
Act. Comp: 0
m³/h
Onlyvisibleiftheunitis
conguredforFlowcontrol
Set thenormal(1/1)and
reduced(1/2)airowforthe
supplyairfan
Set theSAFairow
compensationforthesettable
outdoortemperature.The
outdoorcompensationislinear
andissetusingtwoparameter
pairswhichgivethevalueofthe
compensationattwodifferent
outdoortemperatures.The
compensationcanbepositive
ornegative.
Shows theactualairow
compensation.
Shows airowfortheextract
airfan(constantairowcontrol)
Actual: +INF
m³/h
Onlyvisibleiftheunitis
conguredforFlowcontrol
Setp.: m³/h
Flowcontrol
EAF
Setp1/1: 1100
Set thenormal(1/1)and
reduced(1/2)airowforthe
extractairfan
m³/h
Setp1/2: 550
m³/h↓
DVCompact OperationandMaintenanceInstructions
211 118
20
SystemairSverigeAB
Page 23
Mainmenuitem
Sub-menuitem1 Sub-menuitem2
Outdoor
comp.Setp. 1
—20°C=10m³/h
0°C=0m³/h
Act. Comp: 0
m³/h
Pressure
controlSAF
Actual: Pa
Setp.: Pa
Pressure
controlSAF
Setp1/1: 250
Pa
Explanations
SettheEAFairow
compensationforthesettable
outdoortemperature.The
outdoorcompensationislinear
andissetusingtwoparameter
pairswhichgivethevalueofthe
compensationattwodifferent
outdoortemperatures.The
compensationcanbepositive
ornegative.
Shows theactualairow
compensation.
Shows theactualexternal
pressureandsetpointforthe
supplyairfan.
Onlyvisibleiftheunitis
conguredfor"Pressure
control"(VAV)
Settheexternalpressureset
pointfornormalspeed(1/1)
andreducedspeed(1/2)forthe
supplyairfan.
Pressure
controlEAF
Actual: Pa
Setp.: Pa
Setp1/2: 100
Pa
Outdoor
comp.Setp. 1
—20°C=0Pa
10°C=0Pa
Act. Comp: 0
Pa
Pressure
controlEAF
Setp1/1: 250
Pa
Set theSAFpressure
compensationforthesettable
outdoortemperature.The
outdoorcompensationislinear
andissetusingtwoparameter
pairswhichgivethevalueofthe
compensationattwodifferent
outdoortemperatures.The
compensationcanbepositive
ornegative.
Shows theactualpressure
compensation.
Shows theactualexternal
pressureandsetpointforthe
extractairfan.
Onlyvisibleiftheunitis
conguredfor"Pressure
control"(VAV)
Settheexternalpressureset
pointfornormalspeed(1/1)
andreducedspeed(1/2)forthe
supplyairfan.
Setp1/2: 100
Pa
DVCompact OperationandMaintenanceInstructions
211 118
21
SystemairSverigeAB
Page 24
Mainmenuitem
→Timesettings
Sub-menuitem1 Sub-menuitem2
Outdoor
comp.Setp. 1
—20°C=0Pa
10°C=0Pa
Act. Comp: 0
Pa
→Time/Date
→Timernormal
speed
→ Timerreduced
speed
Explanations
SettheEAFpressure
compensationforthesettable
outdoortemperature.The
outdoorcompensationislinear
andissetusingtwoparameter
pairswhichgivethevalueofthe
compensationattwodifferent
outdoortemperatures.The
compensationcanbepositive
ornegative.
Shows theactualpressure
compensation.
Setcorrecttimeanddate.
SetweekscheduleMondayto
Sunday+Holidayfornormal
speed.Possibletoset2periods
perday.
00:0024:00forcontinuous
running.00:0000:00
inactivatestheperiod.
Notethesettingsinthe
commissioningrecord
Set weekscheduleMondayto
Sunday+Holidayforreduced
speed.Possibletoset2periods
perday.
00:0024:00forcontinuous
running.00:0000:00
inactivatestheperiod.
Notethesettingsinthe
commissioningrecord
→Extended
running
Extended
running
60min
Timeinext.
running
0min
Setthetimeforextended
running.Digitalinputscanbe
usedtoforcetheunittostart
orincreasetoNormalrunning
althoughthetimersaysthe
runningmodeshouldbeOffor
Reduced .
Iftherunningtimeissetto0
theunitonlyrunsaslongasthe
digitalinputisclosed.
Thetimetheextendedrunning
isactiveismonitoredin"Time
inext.Running".
It'salsopossibletosetatime
hereaswellinordertoshorten
theinitialsetperiod.
DVCompact OperationandMaintenanceInstructions
211 118
22
SystemairSverigeAB
Page 25
Mainmenuitem
Sub-menuitem1 Sub-menuitem2
→ HolidaysHolidays
(mm:dd)
Explanations
Setupto24separatepossible
holidayperiodsforafullyear.
1:01–01—01–02
2:09–04—09–10
3:01–05—01–05
Aholidayperiodcanbeany
numberofconsecutivedays
fromoneandupwards.
Thedatesareintheformat:
MM:DD.
Whenthecurrentdatefalls
withinaholidayperiod,the
schedulewillusethesettings
fortheweekday“Holiday”.
→Manual/Auto
Inthismenutherunningmode
ofalltheconguredoutput
signalsandanumberofcontrol
functionscanbemanually
controlled.
Thesupplyaircontroller's
outputsignalcanbemanually
set(Manual/Auto)toanyvalue
between0and100%.The
temperatureoutputsignalswill
changeaccordinglyiftheyare
inAutomode.Itisalsopossible
tomanuallycontroleachof
thetemperatureoutputsignals
individually.
Supply
Temperature
contr.
Auto
Manualset:
0.0
SAF:Auto
Manualset:
0.0
EAF:Auto
Manualset:
0.0
Heating
Auto
Manualset:
100.0
Sinceleavinganyofthe
outputsinmanualcontrolwill
disruptthenormalcontrol,
analarmwillbegeneratedas
soonasanyoutputissettoa
manualmode.
Setthesupplyairtemperature
to"Auto","On"or"Off".
Set theoutputsignalbetween
0-100%.
TheoutputsY1,Y2andY3,if
inAuto-mode,willfollowthe
signalaccordingtothesetsplit
values.
Set thestartsignalforSAF
(supplyairfan)&EAF(exhaust
airfan)to"Auto ,Manual
fullspeed,Manualhalf
speedorManual
Set theheatingtoAuto,
ManualorOff
Set themanualoutput0-100%
DVCompact OperationandMaintenanceInstructions
211 118
23
SystemairSverigeAB
Page 26
Mainmenuitem
Sub-menuitem1 Sub-menuitem2
Exchanger
Auto
Manualset:
0.0
Cooling
Auto
Manualset:
0.0
Explanations
Settheexchangerrotorcontrol
toAuto,ManualorOff
Setthemanualoutput0-100%
SetthecoolingtoAuto,
ManualorOff
Setthemanualoutput0-100%
Note:
Needstobeactivatedinorder
tobevisiblehere
P1–Heating
Auto
P1–Exchanger
Auto
P1–Cooling
Auto
Firedamper
Auto
Freshair
damper(Outdoor
airdamper)
Auto
Exhaustair
damper
Set thepumpcontrolforthe
heatingcoiltoAuto,OnorOff
Set thepumpcontrolfora
possiblerunaroundcoilto
Auto ,OnorOff
Set thepumpcontrolforthe
coolingcoiltoAuto,OnorOff
Set theFiredampertoAuto,
OpenorClose
Note:
Needstobeactivatedinorder
tobevisiblehere
Congurationofredamper
functionsaremadeatSystem
level
SettheOutdoorairdamperto
Auto,OpenorClose
SettheExhaustairdamperto
Auto,OpenorClose
Auto
→Settings
→Controltemp
DVCompact OperationandMaintenanceInstructions
211 118
Supplyair
control
P-band:
33.0°C
I-time: 100.0
sec
24
Inthismenugroupthesettings
fortheactivatedfunctionsare
available.Dependingonwhich
choiceshavebeenmadeinthe
congurationmenusomeofthe
possiblealternativesmaynot
bedisplayed.
Set P-bandandI-timeforthe
Supplyaircontrolfunction
Note:
SeeCorrigoEventilation2.3
manualfordeeperexplanation
SystemairSverigeAB
Page 27
Mainmenuitem
Sub-menuitem1 Sub-menuitem2
Roomcontrol
P-band:
100.0°C
I-time: 300.0
sec
Explanations
SetP-bandandI-timeforthe
Roomcontrolfunction
Note:
SeeCorrigoEventilation2.3
manualformoreinfo
→Controlflow
Shutdownmode
P-band:
100.0°C
I-time: 100.0
sec
→ Frost
protection
Active
Setpshutdown:
25.0°C
P-bandactive:
5.0°C
Faststop
atfrost
protection
alarm
Yes
Flowcontrol
SAF
P-band:
10000.0m³/h
I-time: 10.0
sec
Set P-bandandI-timeforthe
Shutdownfunction
Note:
SeeCorrigoEventilation2.3
manualfordeeperexplanation
P-bandactive5°Cmeansthat
thefrostprotectioncontroller
willstartoverridingtheheating
outputwhenthefrostprotection
temperatureislessthan5
degreesabovethesetfrost
alarmdefaultalarmlimitis7°C
Set thefaststopoftheunitin
caseoffrostprotectionalarmto
Yes orNo.
AlternativelyPressure
control ifchoseninthe
congurationoftheunitfrom
factory
Set P-band,I-timeandMin.
outputforthesupplyair
fanwhentheunitcomes
conguredasFlowcontrol
fromfactory .Alternatively
Pressurecontrol ifthat
congurationischosen
Min. output:
0%
Flowcontrol
EAF
P-band:
10000.0m³/h
I-time: 10.0
sec
Set P-band,I-timeandMin.
outputfortheExtractair
fanwhentheunitcomes
conguredasFlowcontrol
fromfactory .Alternatively
Pressurecontrol ifthat
congurationischosen
Min. output:
0%
→ Alarm
settings
→ Alarmlimits
Set thealarmlimitsandallowed
deviationsforthedifferent
functions
DVCompact OperationandMaintenanceInstructions
211 118
25
SystemairSverigeAB
Page 28
Mainmenuitem
→Configuration
Sub-menuitem1 Sub-menuitem2
→ Alarmdelays
Restorefactory
settings: No
Restoreuser
settings: No
Saveuser
settings
No
→ Control
function
Control
function
Mode:
Roomcontrol
Explanations
Setthealarmdelaysand
alloweddeviationdelaysforthe
differentfunctions
Inthismenu,itispossibleto
restoreallparameterstotheir
factorysettingsortotheuser
settingstheyweresavedas
earlier.
SelectYesorNo
Thecurrentcongurationcan
besavedinaseparatememory
areaandcanlaterberestored
usingthepreviousmenu,
Restoreusersettings.Select
Yes orNo
Set typeoftemperaturecontrol
functionyouwanttheunit
tooperateunder.Choose
between
Extractaircontrol,
"Roomcontrol,Outdoor
comp. Supply,Supply
aircontrol,
Extract/supplyair
→(possibletoswitchbetween
thetwodependingonoutdoor
temp.),
Room/supplyair
→(possibletoswitchbetween
thetwodependingonoutdoor
temp.),
→Freecooling
Freecool
active: No
Outd. temp
activation
22°C
Set freecoolingactiveto"Yes
orNo.
Set theloweroutdoorday
temperaturelimitforthe
activationofthefreecooling
function.Thetemperatureof
thepreviousdayneedstobe
overthesettemperaturein
orderactivatethefreecooling
function.
Outd. temp
night
High: 15.0°C
Low: 5.0°C
Roomtempmin.
18°C
Set theupperoutdoornight
temperaturelimitforthe
activationofthefreecooling
function
Set theloweroutdoornight
temperaturelimitforthe
activationofthefreecooling
function
Set thelowerroomtemperature
limit.Thetemperatureneedsto
beabovethisvalueforthefree
coolingfunctiontostayactive
DVCompact OperationandMaintenanceInstructions
211 118
26
SystemairSverigeAB
Page 29
Mainmenuitem
Sub-menuitem1 Sub-menuitem2
Hourfor
start/stop
Explanations
Setthestartandstoptimefor
thefreecoolingfunction
Freecooling
Start: 0
Stop: 7
Forexample Start:0 and
Stop: 6
meansthatthefreecooling
sequenceisactivebetween
00.00and06.00h.
Timetoblock
heatoutput
afterFree
cooling
60min
Set thedelayinminutesfrom
thetimewherethefreecooling
sequencehasstoppeduntila
possibleheatingsequenceis
initiated,i.e.howlongacooler
roomtemperaturethanset
temperaturecanbeaccepted
Fanoutputwhen
freecooling
SAF:0%
Set thefanspeedinpercentage
ofthenormalspeedforeach
fanindividuallyduringthefree
coolingsequence
EAF:0%
Outdoorsensor
placedin
Set iftheoutdoorsensoris
placedintheintakeductornot.
intakechannel
(intakeduct)
No
→ Support
Supportcontrol
control
Active: No
EAFrunning
duringSupport
contr.: Yes
ChoosebetweenNoandYes
PresetisNo.
Whenusingthecontrol
functionroomcontrolor
extractairtemperature
control,itispossibleto
utilizesupport-heatingand/or
support-cooling.Minimum
runningtimeissettable0…720
minutes.(factorysetting20
minutes).Choosebetween
“Active:YesorNo”.
(Forstartandstoptemperatures
seethe"T emperature"menu)
Min. runtime
forsupport
Set theminimumrunningtime
inminutesforsupportcontrol
ctrl: 60min
→ CO2/VOC
Control
CO2/VOCactive
Never
Type: Fan
Min. time: 60
min
Inapplicationswithvarying
occupancythefanspeeds
ormixingdamperscan
becontrolledbytheair
qualityasmeasuredbya
CO2/VOC-sensor.Seeencl.
corrigomanual(CD)fordet.
explanation
Set activetoNever,Always
orIftimechanneloff.
Setwhatshouldberegulated.
SelecttypebetweenFanor
Mixingdampers
Set themin.timetheunitis
activatedbytheCO2/VOC
demandfunction
DVCompact OperationandMaintenanceInstructions
211 118
27
SystemairSverigeAB
Page 30
Mainmenuitem
Sub-menuitem1 Sub-menuitem2
Activation
level
Explanations
Settheactivationlevelat1/2
speed
1/2–speed: 800
ppm
1/1–speed:
Set theactivationlevelat1/1
speed
Set alloweddiff.value
1000ppm
diff: 160ppm
→ Humidity
control
Humidity
control
Notactive
Sartlimit:
15%
Stoplimit: 5%
Set thehumidity
controltoHumid-
/Dehumidification,
Dehumidification,
HumidificationorNot
active.
Set thestartlimitandstoplimit
in%RH
Applicableforexternal
Humidicationor
Dehumidicationdevice.
→Cooling
recovery
Cooling
recovery
No
Coolinglimit:
2.0°C
Set thecoolingrecoverytoYes
orNo.
Set thecoolinglimit(the
differenceintemperature
betweenextractairandoutdoor
airthatactivatesthecooling
recovery).
→Enthalpy
control
Cooling
recoveryrun
whenenthalpy
isgreater
outdoorthan
indoor: Not
active
Coolingrecoveryfunction
basedontheenthalpy
differencebetweenoutdoors
andindoors.Startsthe
coolingrecoveryfunctionifthe
calculatedenthalpyisbigger
outdoors.
Set thefunctiontoActiveor
Notactive
→ Minlim.
dampers
Minlimit
dampers
Notactive
Min.limit.:
5.0%
Applicableforexternalmixing
dampers(re-circulatedair)
Set thisfunctiontoActiveor
Notactive
Set theminimumoutdoor
airlimit(settablebetween
0-100%).
→Accessrights
→Logon Logon
Enterpassword
xxxx
Actuallevel:
None
Logon toservicelevelby
enteringa4-digitcode.After
reachingthedesiredlevelgo
backwith“LEFT”arrow(press
2times)onthecontrolpanel.
Standardcodefromfactory
toenterservicelevelis2222.
Backtooperatorlevel:1111
DVCompact OperationandMaintenanceInstructions
211 118
28
SystemairSverigeAB
Page 31
Mainmenuitem
Sub-menuitem1 Sub-menuitem2
→ LogoffLogoff
No
Actual
level:None
→ Change
password
Changepassword
for
Explanations
Logofffromsystemlevelby
changing"No"to"Yes"withthe
"OK"and"UP/DOWN"buttons
Automaticlogoffafter6minutes
ofinactivity.
Set anewpasswordforthe
levelofyourchoice.
level:None
Newpassword
xxxx
Canonlybedoneoncelogged
ontotheservicelevel.
5.2.2.4Freecoolingdescription
Thisfunctionisusedduringthewarmperiodtosaveenergybyusingcoldoutdoorair,e.g.duringnight
time,tocooldownthebuilding.
Note:
ThefollowingisonlyvalidifthefreecoolingfunctionissettoActiveintheprogrammenu.
Freecoolingisonlyactivatedwhenthefollowingstartingconditionsaremet.
Startingconditions:
•Lessthan4dayshavepassedsincetheunitwaslastinrunningmode
•Theoutdoortemperatureduringthepreviousrunningperiodexceededasetlimit(+22°C)
•Itisbetween00:00and07:00:00intheday(settable)
•Thetimeroutputsfornormalspeed,ExtendedrunningnormalandExternalstopareOff
•AtimechannelwillbeOnsometimeduringtherecentlystarted24hours.
Theunitchecksthenighttemperature(indoorandoutdoortemperature)during3minutesattheset
startinghourwhenthefansarestartedsothatthesensorscanperformatemperaturemeasurement.If
aboveconditionsaremetthefreecoolingfunctionisstarted,ifnottheunitgoesbacktoOFFposition.
Iftheoutdoorsensorisnotlocatedintheoutdoorairinletductandaroomsensorhasbeenselected,
theunitwillnotstartfreecoolingaslongasallthetemperaturesarenotwithinthestartandstop
temperatureintervals.
Stopconditions:
•Outdoortempabovethesetmaxvalue(+18°C)orbelowthesetminvalue(condensationrisk,+10°C)
•Theroomtemp/extractairtempisbelowthesetstopvalue(+18°C)
•Oneofthetimeroutputsfornormalspeed,ExternalstoporExtendedrunningnormalisOn
•Thetimehaspast07:00:00.
Whenfreecoolingisactive,thefansrunatnormalspeedorthesetvalueforpressure/owcontroland
thedigitaloutputFreecoolingisactive.TheoutputsY1-Heating,Y2-Heatexchangerand
Y3-Cooling areshutdown.Afterfreecoolinghasbeenactivated,theheatingoutputisblockedfor60
minutes(congurabletime).
5.2.3Alarms
Thealarmbutton(pos.1,gure9)opensthealarmqueue.Whenpressingthisbuttonactiveand
non-acknowledgedalarmswillbedisplayedinthemenuwindow.Thealarm-LED(pos.2,gure9)is
ashingiftherearenon-acknowledgedalarmsandsteadyifthealarmsarestillactivebuthavebeen
acknowledged.Iftherearemultiplealarms,useUP/DOWNtomovebetweenthem.Analarmcanbe
acknowledgedorblockedbyusingOKandUP/DOWN.T oabortandgobacktostartmenupresscancel
andthenpressLEFT .
SeeCommissioningrecordforanoverviewofpossiblealarms.
DVCompact OperationandMaintenanceInstructions
211 118
29
SystemairSverigeAB
Page 32
6Maintenance
MaintenanceoftheDVCompactDXRisofgreatimportanceforthewholeinstallationsenvironmental
inuence,operatingeconomy,durability,securityandfunctions.
Important
•ReadtheWarnings(chapter1)andRefrigerantControl/Reporting(chapter2)beforedoingany
workontheDVCompactDXRunit.
Maintenanceshouldbecarriedatleastonceayear,apartfromgeneralcleaningthefollowingshouldbe
done:
1.Leakagecontrolwithregistration
Differentregulationscanbevalidindifferentcountries.Checkwithyourlocalgovernment.
2.Generalcontrol.
Whenunitisrunninglistenforabnormalsoundsandvibrations.Inspectoccurrenceofoilleakage(can
beasymptomonrefrigerantleakage).Inspectoccurrenceofcorrosion,frettingdamages,loosen
pipesuspensions.
3.Controlofthecoolingcoil(evaporatorcoil)andcondensercoil.
Afteralongtimeofusethecoilscanobtainadepositthatobstructstheheattransferandairow.
Vacuumcleanthecoilscarefullyfromthedirtyside.
4.Controlofthedriptray.
Afteralongtimeofusethedriptrayandthedraincanobtainadepositthatobstructsthedrainofthe
condensationwater.Cleanthedriptray,drain,watersealandpipesfromdirtanddeposits.
6.1Important
Danger
•MakesurethattheMainssupplytotheunitisdisconnectedbeforeperforminganymaintenanceor
electricalwork!
•Allelectricalconnectionsmustbecarriedoutbyanauthorizedinstallerandinaccordancewith
localrulesandregulations.
Warning
•AlthoughtheMainssupplytotheunithasbeendisconnectedthereisstillriskforinjuryduetorotating
partsthathavenotcometoacompletestandstill.
•Bewareofsharpedgesduringmountingandmaintenance.Useprotectiveclothing.
6.2MaintenanceIntervals
Thetablebelowshowsrecommendedmaintenanceintervalsfortheunitandtheinstallation.T o
ensurealongoperationlifetimefortheunititisimportanttoperformmaintenanceaccordingtobelow
recommendationsandthattheyareperformedaccordingtotheoperationandmaintenanceinstructions.A
thoroughandrecurrentmaintenanceisamustforavalidguarantee.
DVCompact OperationandMaintenanceInstructions
211 118
30
SystemairSverigeAB
Page 33
Typeofmaintenance Onceayear
Unit
•Cleaningtheunit
•Inspectionofsealsandlocks
Filters
•Replacinglters
Fans
•Cleaningthefan
•Inspectionofvibrationdampersandexibleconnections
RotatingHeatexchanger
•Cleaningtheheatexchanger
•Inspectionofsealsandbrushes
•Inspectionoftherotorregulation
Heatpump
•Checkingthecompressor
•Checkingtheevaporatorforpotentialleakage
•Checkingthecondenserforpotentialleakage
Re-heaterbattery
•Venting
•Checkingthestatusofthebattery
•Inspectionoftheoverheatprotectionthermostat(EL
battery)
Coolingbattery
•Venting
•Cleaningthedrainpan
•Checkingthestatusofthebattery
•Inspectionofthedropletseparator
Cleaningsupplyairdiffusers
Cleaningtheoutdoorairintake
Cleaningtheductsystem
Cleaningthecondenser/driptray
Dampers
•Checkingthedampers
•Cleaningthedampers
Whennecessary
X
X
X
X
X
X
X
X
X
1
X
X
X
1.Orinaccordancewithlocalrulesandregulations
6.3Cleaningtheunit
Duringlongtermoperationdustandgreasemayslowlybuildupinsidetheunit.Theunitshouldbecleaned
onceayearwhenoperatingundernormalairconditionswithnospecialhygienerequirements.Cleanthe
unitwithadryclothorusewatermixedwithnoncorrosivecleaningmedium.Anycorrosionshouldbe
cleanedoffimmediatelyandthesurfacetreated.Inspecialoperatingconditionstheunitshallbecleaned
morefrequencythanrequired.Cleaningmediumandmethodshouldbeadaptedtotherelevantconditions.
Closingmechanismsshouldbelubricatedatleastonceayear.Syntheticdoorhingesareservicefree.
Sealsaroundinspectiondoorsshouldbecleanedatleastonceayear.Itisrecommendedtotreattheseals
DVCompact OperationandMaintenanceInstructions
211 118
31
SystemairSverigeAB
Page 34
withamoistureofrepellentagent.Connectingpiecesfortheunitsections,includingthedisc-locktypes
aretobecheckedfortightnessatleastonceareyear.Allsealshavetobeinspectedatleastoneayear.
6.4ChangingSupply/Extractairlter
Thebagltercannotbecleanedandmustbechangedwhennecessary.
ThefactoryinstalledltersareoflterqualityM6orF7forboththesupplyairandextractairlter.Thelter
typeislabelledonthetopofthelter.NewlterscanbeorderedfromSystemairUAB.
Operationtimebetweenlterchangesdependsontheairpollutionattheinstallationsite.Adifferential
pressureswitchindicateswhenit’stimetochangethelters.Thiswilltriggeranalarminthecontrolpanel.
Whenthisoccursdothefollowing:
1.Replacethelterswithnewonesasdescribedbelow
2.Acknowledgethealarmbypressingtheredbuttononthecontrolpanel(pos.1gure9)followedbyOK
(pos.4gure9)
3.Choose→AcknowledgebypressingOK
Theltersaretakenoutbypullingthemoutformthelterrailandreplaced(gure10).
Gasketsbetweeneachltershallalsobereplaced.
Fig.10Changinglters
6.5Checkingtherotatingheatexchanger
Afteralongtimeofusedustmaybuildupintheexchangerandblocktheairow.Itisimportanttoclean
theexchangerregularlytomaintainhighefciency .Thecompleterotatingheatexchangerblockcanbe
takenoutoftheunit(gure11)inthesmallermodelstofacilitatecleaningandmaintenance.Washinhot
soapywaterorusepressureair.Donotusedetergentcontainingammonia.
Checkatleastonceayearthattheexchangerrotorrotateseasily.Checkthisbyremovingthedriving
beltandmovetherotorbyhand.Checkalsothatthebrushesareundamaged.Therotorbearingsare
permanentlylubricatedfromfactoryandshouldnotbere-greased.
Check4timesperyearthatthedrivingbeltissufcientlytense,thatitfollowsthetracksandthatitis
undamaged.Ifthebelttensionistoolowitneedstobeshortened.
DVCompact OperationandMaintenanceInstructions
211 118
32
SystemairSverigeAB
Page 35
Fig.11Dismountingtherotatingheatexchanger
Note:
Makesurethattherotormotorisnotexposedtomoisture.
6.6Checkingthefans
6.6.1Cleaning
Eveniftherequiredmaintenance,suchaschangeoflters,iscarriedoutdustandgreasemayslowly
buildupinsidethefans.Thiswillreducetheefciency.Thefanmotorcanoverheatifathicklayerofdust
preventstheairfromenteringthemotortocooldownthestatorstructure.
• Theexternalsurfacesmaybecleanedwitha
clothorasoftbrush.Iftheyareseverelyfouled,
useanenvironmentallyfriendlyde-greasing
agent.Donotusewater.Whitespiritcanbe
usedtoremoveobstinatesettlements. Allow
dryingproperlybeforestartingtheunit.
•Wipethefanimpellerbladestoremoveany
coatings.Useonlytheenvironmentallyfriendly
de-greasingagent.
6.6.2Inspection
•Checkifthefanimpellerrotateseasily,isinbalanceanddoesnotvibrate.
•Checkifthefanimpellerisxedandoverlapsinletcone.
•Listentothesoundcomingfromthemotorbearings.Itshouldmakeaslightpurringsound.Ascraping
orpoundingsoundcanindicatethatthebearingsaredamagedandshouldbechanged.
•Checkiftherubberanti-vibrationmountingsarenotdamagedandintact.
DVCompact OperationandMaintenanceInstructions
211 118
33
SystemairSverigeAB
Page 36
•Checkthemountingscrewsandtightenifnecessary.
6.7Checkingthecompressor
Mandatoryannualcontrolmustbedonebytrainedservicepersonnel.Theserviceissuedbythepump
manufacturermustbefollowed.Thepressureexpansionsystemmustbecheckedonceayear.If
necessary,thepressuremustbeincreasedtothecorrectlevel.
6.7.1Inspection
Suggestionforchecksmayinclude:
•Anyabnormalnoisesfromthecompressor;
•Oilleaksfrompipesorcompressor;
•Anycorrosiononsolderingorpipes;
•AnyrellingwithrefrigerantR410A;
•Visualchecksinsightglass.
6.8Checkingtheevaporatorandcondenser
Theevaporator/condenserwillhavereducedcapacityifdustformsacoatingonthecoilsurfaceand
increasesthepressuredropontheairside.EveniftheDVCompactDXRisttedwiththeextractair
lters,dusteventuallywilldepositonthecoilns.
6.8.1Cleaning
•Usethevacuumcleanertoremovedustfromthe
inletsideofyoucanblowthemwithcompressed
airfromtheoutletside;
•Usehotwatermixedwithnoncorrosivecleaningmediumandrinseusingwater.Anycorrosionshouldbecleanedoffimmediatelyandthe
surfacetreated.
6.8.2Inspection
•Checkthecoilnsforanydamage;
•Checkifrefrigerantisnotleaking;
•Checkthedipdrayanddrain,cleanifnecessary;
DVCompact OperationandMaintenanceInstructions
211 118
34
SystemairSverigeAB
Page 37
7Troubleshooting
Shouldproblemsoccur,pleasecheckorcorrectthefollowingbeforecontactingyourservicerepresentative.
Alwayscheckifthereareanyalarmsactiveinthecontrolpanel.
1.Fan(s)donotstart
•Checkifthereareanyalarmmessages
•Checkthatthefusesarenotdefect
•Checkthesettingsinthecontrolpanel(times,weekschedule,auto/manualoperationetc.)
2.Compressordonotstart
•Checkifthereareanyalarmmessages
•Checkifmainssupplytotheheatpumpsectionisnotmissing.Inspectexternalfusesandsafety
switch
3.Reducedairow
•Checkthesettingsformediumandlowfanspeed
•Checkthattheoutdoor/exhaustairdamper(ifused)opens
•Checkifltersneedchanging
•Checkifdiffusersandlouvresneedcleaning
•Checkdiffuser/louvreopenings
•Checkiffansandexchangerblockneedcleaning
•Checkiftheroofunitorairintakeisclogged
•Checkductsforvisibledamageand/orbuildupofdust/pollution
4.Coldsupplyair
•Checkthecontroltemperatureonthecontrolpanel
•Checkiftheoverheatingthermostathastripped.Ifnecessaryresetthemanualoverheatprotection
situatedontheelectricalheaterframe
•Checkiftheextractlterneedstobechanged
•Checkifthefanshavestoppedduetooverheating.Ifsothethermalcontactmighthavetripped
(showsasFanalarminthecontrolpanel)
5.Noise/vibrations
•Checkthattheunitiscompletelylevelled
•Cleanthefanimpellers
•Checkthatthescrewsholdingthefansaretightenedproperly
•Checkantivibrationpadsandexibleconnections
8Additionalinformationonpersonnelsafetyand
protectivemeasures
8.1Informationonairbornenoiseemissions
DuetothedesignandconstructionoftheunitstheA-weightedsoundpressurelevelfromthefanandother
componentsdonotexceed70dB(A)outsidetheunits.
8.2Personnelsafetymeasures
Adjustmentsandmaintenancemustbedoneonlybytrainedservicepersonnel.Thepotentialsourcesof
harmarethefanswithfastrotatingimpellers,heatexchangerrotorandthehotsurfaceoftheheating
battery.Theimpellersarestillapotentialhazardevenafterpowercut-offbecauseofafter-runthatcanlast
upto5minutes.
DVCompact OperationandMaintenanceInstructions
211 118
35
SystemairSverigeAB
Page 38
Inordertoensurepersonnelsafetytheinspectiondoorsareprovidedwithalock.
9Disposalandrecycling
Disposalmustbecarriedoutprofessionallyandenvironmentallyfriendlyinaccordancewiththelegal
stipulations.
ThisproductareapplicabletotheWEEEdirective.Whendisposingtheunit,follow
yourlocalrulesandregulations.
Thisproductpackingmaterialsarerecyclableandcanbereused.Donotdisposein
householdwaste.
9.1Disposaloftheheatpumpunit
PriortothedisposaloftheDVCompactDXRunittherefrigerantintheheatpumpsystemmustbedrained
offbytrainedservicepersonnelfromacertiedcompany.Aftercorrectevacuationoftherefrigerantthe
disposaloftheunitsectionissimilartothedisposaloftherestoftheairhandlingunit.
Note:
Differentregulationscanbevalidindifferentcountries.Checkwithyourlocalgovernmentbeforedisposal
ofthecompressor.
9.2Disposaloftheairhandlingunit
Noadditionalsafetymeasuresarerequiredforthedisposaloftheairhandlingunit.Contactyourlocal
wastemanagementcompanyformoreinformation.
DVCompact OperationandMaintenanceInstructions
211 118
36
SystemairSverigeAB
Page 39
lastpage
SystemairSverigeABreservestherighttomakechangesandimprovementstothe
contentsofthismanualwithoutpriornotice.
SystemairUAB
Linųst.101
LT–20174Ukmergė,LITHUANIA
Phone+37034060165
Fax+37034060166
www.systemair.com