
INSTALLATION MANUAL
KNX gateway
CWC 01
Thank you very much for purchasing our product.
Before using your unit, please read this manual carefully and keep it for future reference.

● This manual gives detailed description of the precautions
that should be brought to your attention during operation.
● In order to ensure correct service of
SYSCONTROL CWC 01
please read this manual carefully before using the unit.
● For convenience of future reference, keep this manual
after reading it.

Table of Contents
I. Safety precautions........................................................................................ 1
II. Other precautions ....................................................................................... 3
III. Installation procedure................................................................................. 5
IV. ETS database group objects introduction
................................................. 8

I. Safety precautions
The following contents are stated on the product and the operation
manual, including usage, precautions against personal harm and
property loss, and the methods of using the product correctly and safely.
After fully understanding the following contents (identifiers and icons),
read the text body and observe the following rules.
Identifier description
Identifier Meaning
Means improper handling may lead to
personal death or severe injury.
Means improper handling may lead to
personal injury or property loss.
[Note]: 1. “Harm” means injury, burn and electric shock which need
long-term treatment but need no hospitalization
2. “Property loss” means loss of properties and materials.
Icon description
Meaning lcon
It indicates forbidding. The forbidden subject-matter is
indicated in the icon or by images or characters aside.
It indicates compulsory implementation. The compulsory
subject-matter is indicated in the icon or by images or
characters aside.
1

WARNING
Please entrust the distributor or professionals to install the unit.
Installation by other persons may lead to imperfect installation, electric shock or fire.
Strictly follow this manual.
Imporper installation may lead to electric shock or fire.
Reinstallation must be performed by professionals.
improper installation may lead to electric shock or fire.
Do not disassemble your air conditioner at will.
A random disassembly may cause abnormal operation or heating, which may result in fire.
CAUTION
Do not install the unit in a place vulnerable to leakage of flammable gases.
Once flammable gases are leaked and left around the wire controller, fire may occure.
The wiring should adapt to the wire controller current.
Otherwise, electric leakage or heating may occur and result in fire.
The specified cables shall be applied in the wiring. No external force may
be applied to the terminal.
Otherwise, wire cut and heating may occur and result in fire.
Do not place the wired remote controller near the lamps, to avoid the remote
signal of the controller to be disturbed. (refer to the right figure)
2

3
II. Other precautions
● Installation Location
Do not install the unit in a place with much oil, steam, sulfide gas. Otherwise, the
product may be deformed and failed.
● Preparation before installation
1
2
3
4
1
3
2
1
GB950-86 M4X20 (For Mounting on the Wall)
M4X25 GB823-88
(For Mounting on the Electrical Switch Box)
6
7
3
2
1
No. Name Qty. Remarks
SYSCONTROL CWC 01
Installation Manual
For Mounting on the Wall
Plastic screw bar
Cross round head wood
mounting screw
Cross round head
mounting screw
3-core shielded cable
Plastic expansion pipe
For fixing on the 86 electrician box
For connecting the AC unit and MD-KNX-01
1. Check whether the following assemblies are complete.
3
5

9
10
1
2
3
1
1
1
RVVP-0.5mm
2
x2
2. Prepare the following assemblies on the site.
2-core shielded cable
86 Electrician box
Qty.(embeded
into wall)
Note to installation of SYSCONTROL CWC 01:
No.
Name
Remarks
Specification
(only for reference)
Max 350m
1. One KNX module can only connect with one indoor unit;The KNX module should
connect to indoor XYE ports, can’t connect to outdoor XYE ports.
2. Circuit of CWC 01 is low voltage circuit. Never connect it with a standard
220V/380V circuit or put it into a same Wiring Tube with the circuit.
3. Do not attempt to extend the shield cable by cutting, if it is necessary, use
Terminal Connection Block to connect.
4. After finishing connection, do not use Megger to have the insulation check to the
signal wire.
5. The default physical address of the CWC 01 is 15.15.255,If there are two or
more KNX modules, then the physical addresses can not repeat.The physical
address can be changed by ETS software.
Wiring Tube(Insulating
Sleeve and Tightening
Screw)
4
KNX power module
1
4
5
Communicate module
1

III. Installation procedure
1.The product parameters
5
1
2
3
Dimensions
Power supply
No.
Name
Remarks
85*51*16mm
29VDC 10mA,Supplied through KNX bus
LED indicator
Push button
KNX programming
KNX programming button
Configuration
Configuration with ETS software.
4
5
2.The product parameters
①
②
③
④

3. Wiring installation instruction
The Wiring diagram follows,the CWC 01 connect to the AC Unit and KNX Power.
Fig.3-2
6
+
-
E
Y
X
E
Y
X
AC unit
MD-KNX-01
KNX TP-1
(EIB)bus
MAX 500m
● CWC 01 is completely in conformity with EIB/KNX standard. ETS software
must be used by integrator to carry out configuration and project design.
For detailed information of ETS software, please contact knx association:
www.knx.org.
● ETS database (*.vd*)of SYSCONTROL CWC 01 consult our company.
① Bus interface:Power supply DC 29V, 10mA and connect to KNX bus;
② KNX programming button:press once to enter the programming mode,
press it again will exit.
③ KNX programming statues lamp:when it is light up means programming
status and can write data to the module by KNX bus
④ RS485 communication ports:Communication port between KNX module
and indoor unit.
●

7
● CWC 01 allows monitoring and control, fully bi-directionally, of all the functioning
parameters of Systemair Air Conditioners from KNX installations.
● Simple installation.
Can be installed inside the own AC indoor unit, it connects directly in one side to
the electronic circuit of the AC indoor unit (cable supplied) and in the other side to the
KNX TP-1 (EIB) bus.
● Great flexibility of integration into your KNX projects.
Configuration is made directly from ETS, the database of the device comes with a
complete set of communication objects allowing, from a simple and quick integration
using the basic objects, to the most advanced integration with monitoring and control
all the AC unit’s parameters. Also available specific device’s communication objects,
as for example save and execute scenes.
● Allows the use of a KNX temperature sensor for the air conditioning control.
Introduction of SYSCONTROL CWC 01:

8
IV.ETS database group objects introduction
Fig.4-1

9
The AC unit temperature value corresponding to ETS temperature value:
1
2
3
17
18
No.
Temp. value(℃)
0B 52
0B 84
19
20
0B B6
0B E8
21 0C 1A
22 0C 4C
4
5
6
ETS value
8
9
10
No.
11
12
13
7 14
23
24
25
26
27
28
29
30 0C 7E
0C B0
0C E2
0D 14
0D 46
0D 78
0D AA
0D DC
Temp. value(℃)
ETS value
The instruction as follow:
0: set mode; database type: DPT_20.102 HVAC mode;
set value:0-Auto ; 1-Cool; 2-Heat; 3-Fan only ; 4-OFF
1: set temp; database type: DPT_9.001 temperature(°C).
2: Set Fan speed; data type: DPT_5.001 percentage(0..100%).
Set value:0-auto; 2-low speed; 3-mid speed; 4-high speed.
3: Set Heat/Cool mode data type: DPT_1.100 heating/cooling.
Set value: 0-Cool mode;1-Heat mode.
4: Set swing on/off; data type: DPT_1.002 boolean.
Set value:0-OFF; 1-ON.

10
5: Set Auxiliary Heater ON/OFF; Data type: DPT_1.002 boolean.
Set value: 0-Auxiliary Heater ON; 1-Auxiliary Heater OFF.
This function is only available for heat mode.
6: Mode status read; data type: DPT_20.102 HVAC mode
Read value: 1-Cool mode; 2-Heat mode; 3-Fan mode; 4-OFF.
7: Set temperature read; data type: DPT_9.001 temperature(°C) .
8: Fan speed read; data type: DPT_5.001 percentage(0..100%).
Read value: 33%-low speed,67%-medium speed,100%-high speed,2%-OFF.
9: Fan swing status read; data type: DPT_1.002 boolean
Read value: 0-swing OFF,1-swing ON
10:Auxiliary Heater status read; data type: DPT_1.002 boolean.
Read value: 0-Auxiliary Heater OFF,1-Auxiliary Heater ON
11:Indoor unit ambient temp. read; data type: DPT_9.001 temperature(°C)
12:Alarm state read; data type: DPT_1.005 alarm
Read value: 0-no alarm; 1-alarm
14:ON/OFF; data type: DPT_1.001 switch
Set value: 0-OFF; 1-ON
15:Set auto mode; data type: DPT_1.002 boolean
Set value: 1-set as auto mode
16:set Cool mode; data type: DPT_1.002 boolean
Set value: 1-set as Cool mode
17:Set Heat mode; data type: DPT_1.002 boolean
Set value: 1-set as Heat mode

11
18:Set Dry mode; data type: DPT_1.002 boolean
Set value: 1-set as Dry mode
19:Set Fan mode; data type: DPT_1.002 boolean
Set value: 1-set as Fan mode
20:Set mode circulation; data type: DPT_1.007 step
Set value: 0-Decrease Reverse cycle
1-Increase Positive cycle
Cool Heat FAN only Shut down
Low speed medium speed High speed
21: Set temperature increase and decrease; data type: DPT_1.007 step
Set value: 0-decrease; 1-increase
22: Set Fan low speed; data type: DPT_1.002 boolean
Set value: 1-set as low speed
23: Set Fan medium speed; data type: DPT_1.002 boolean
Set value: 1-set as mid fan speed
24: Set Fan high speed; data type: DPT_1.002 boolean
Set value: 1-set as high fan speed
25: The fan speed circle setting;data type: DPT_1.007 step
Set value:0 -decreas Reverse cycle
Set value:1 -increase Positive cycle
26: ON/OFF status; data type: DPT_1.001 switch
Read value: 0-OFF, 1-ON