SystemAir RETP6, 32293, RETP10, 32294, 303612-42 Operating Instructions Manual

...
RETP6 / RETP10
Multipurpose controller for variable voltage 1 ~ fans
Operating Instructions
Software version: B1061AA from version 1.01
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
english
1 General notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1 Structure of the operating instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2 Target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3 Exclusion of liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4 Copyright . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2 Explanations of symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.3 Product safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.4 Requirements placed on the personnel / due diligence . . . . . . . . . . . . . . . . . . . . . . . . 5
2.5 Start-up and during operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.6 Work on the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.7 Modications / interventions in the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.8 Operators obligation of diligence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.9 Employment of external personnel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3 Product overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.1 Operational area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.2 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.3 Transport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.4 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.5 Disposal / recycling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.1 General notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.2 Minimum space requirement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.3 Outdoor installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.4 Installation location for agriculture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4.5 Temperature inuences during commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5 Electrical installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.1 Safety precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.2 EMC-compatible installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.2.1 Motor cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.2.2 Signal cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.2.3 Harmonics current for devices 16 A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.3 Mains connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.4 Motor connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.4.1 Running noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.5 Motor protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.6 Signal or sensor connection (E1 = Analog In 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.7 Output voltage 0 - 10 V (A1 = Analog Out 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.8 Voltage supply for external devices (+24V, GND) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.9 Digital input (Digital In 1 = D1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.9.1 Enable, device ON / OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.9.2 Reverse action of control function (only for P-Controller / PI-Controller) . . . . . . . . . . 11
5.10 Relay output (K1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.11 Potential at control voltage connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6 Operating and display elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6.1 Main switch and potentiometer with integrated light signal . . . . . . . . . . . . . . . . . . . . . . 12
6.2 Internal Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Operating Instructions RETP6 / RETP10
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
2/31
7 Base setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
7.1 Programming of the desired function (Speed controller / P-Controller, PI-Controller) . . 14
7.2 Select operation mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
7.3 Function of dipswitches for operation as Speed controller
1.01 (DIP 1 = |OFF|) . . . . 15
7.4 Function of dipswitches for operation as P-Controller, PI-Controller,
2.01 , 3.01 , 4.01
(DIP 1 = |ON|) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
7.5 Minimum speed cut off DIP 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
7.5.1 For mode Speed controller
1.01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
7.5.2 For operation as P-Controller, PI-Controller
2.01 , 3.01 , 4.01 . . . . . . . . . . . . . . . . 16
7.6 Hardstart function DIP 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8 Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
8.1 Prerequisites for commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
9 Setting for operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
9.1 Speed controller
1.01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
9.1.1 Setting for operation as Speed controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
9.1.2 Diagram: setting signal and speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
9.1.3 Operation with two variable output voltages (two steps) . . . . . . . . . . . . . . . . . . . . . 18
9.2 Temperaturre control (P-Controller)
2.01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
9.2.1 Setting for operation as Temperature controller . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
9.2.2 Example Temperature control Cooling function (factory setting) . . . . . . . . . . . . . . 20
9.2.3 Example Temperature control Heating function . . . . . . . . . . . . . . . . . . . . . . . . . . 20
9.3 Pressure control condensers (P-Controller)
3.01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
9.3.1 Setting for operation as Pressure controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
9.3.2 Example Pressure control condensers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
9.3.3 Setting with refrigerant medium table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
9.4 Pressure control, Air velocity control (PI-Controller)
4.01 . . . . . . . . . . . . . . . . . . . . . . 24
9.4.1 Setting for operation as Pressure and air velocity controller . . . . . . . . . . . . . . . . . . 24
9.4.2 Example: Pressure control for ventilation systems . . . . . . . . . . . . . . . . . . . . . . . . 24
9.4.3 Example: Air velocity control for clean rooms . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
10 Diagnostics / Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
10.1 If controller doesn´t work correctly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
11 Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
11.1 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
11.1.1 Performance reduction during elevated ambient temperatures . . . . . . . . . . . . . . . . 27
11.2 Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
11.3 Dimensions [mm] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
11.4 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
11.5 Manufacturer reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Operating Instructions RETP6 / RETP10
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
3/31
1 General notes
1.1 Structure of the operating instructions
Before installation and start-up, read this manual carefully to ensure correct use! We emphasize that these operating instructions apply to specic units only, and are in no way valid for the complete system!
Use these operating instructions to work safely with and on the device. They contain safety instruc­tions that must be complied with as well as information that is required for failure-free operation of the device. Keep these operating insturctions together with the device. It must be ensured that all persons that are to work on the device can refer to the operating instructions at any time. Keep the operating instructions for continued use. They must be passed-on to all successive owners, users and nal customers.
1.2 Target group
The operating instructions address persons entrusted with planning, installation, commissioning and maintenance and servicing and who have the corresponding qualications and skills for their job.
1.3 Exclusion of liability
Concurrence between the contents of these operating instructions and the described hardware and software in the device has been examined. It is still possible that non-compliances exist; no guarantee is assumed for complete conformity. To allow for future developments, construction methods and technical data given are subject to alteration. We do not accept any liability for possible errors or omissions in the information contained in data, illustrations or drawings provided. We accept no liability for damage caused by misuse, incorrect use, improper use or as a consequence of unauthorized repairs or modications.
1.4 Copyright
These operating instructions contain copyright protected information. The operating instructions may be neither completely nor partially photocopied, reproduced, translated or put on data medium without previous explicit consent. Infringements are liable for damages. All rights reserved, including those that arise through patent issue or registration on a utility model.
2 Safety instructions
This chapter contains instructions to prevent personal injury and property damage. These instructions do not lay claim to completeness. In case of questions and problems, please consult our company technicians.
2.1 Intended use
The equipment is to be used solely for the purposes specied and conrmed in the order. Other uses which do not coincide with, or which exceed those specied will be deemed unauthorised unless contractually agreed. Damages resulting from such unauthorised uses will not be the liability of the manufacturer. The user will assume sole liability. Reading these operating instructions and complying with all contained instructions - especially the safety notications contained therein - are considered part of intended use. To consider is also the manual of attached components. Not the manufacturer, rather the operator of the device is liable for any personal harm or material damage arising from non-intended use!
2.2 Explanations of symbols
Safety instructions are highlighted with warning triangles and are depicted according to the degree of hazard as follows.
Attention!
General hazardous area. Death or severe injury or signicant property damage can occur if the corresponding precautions are not taken!
Operating Instructions RETP6 / RETP10 General notes
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
4/31
Danger due to electric current
Warning of dangerous voltage or dangerous current.
Information
Important additional information and advice for user.
2.3 Product safety
The device conforms to the state of the art at the time of delivery and is fundamentally considered to be reliable. The device and its accessories must only be used in a flawless condition and installed and operated in compliance with the assembly instructions and/or operating instructions. Operating out­side the device's technical specications (
rating plate and attachment / technical data) can lead to
a defect in the device and additional damage!
In the case of a malfunction or a failure of the equipment check all functions with alarms in order to prevent injury to persons or property. Note possibility of back-up operation. If used in intensive animal environments, any malfunctions in the air supply must be detected as soon as possible to prevent the development of a life-threatening situation for the animals. The design and installation of the system must comply with local regulations and directives. In Germany these include DIN VDE 0100, the animal protection and the keeping of working animals ordinance and the pig-keeping ordinance etc. Also note the instructions of AEL, DLG, VdS.
2.4 Requirements placed on the personnel / due diligence
Persons entrusted with the planning, installation, commissioning and maintenance and servicing in connection with the frequency inverter must have the corresponding qualications and skills for these jobs. In addition, they must be knowledgeable about the safety regulations, EU directives, rules for the prevention of accidents and the corresponding national as well as regional and in-house regulations. Personnel to be trained or instructed and apprentices are only permitted to work on the device under the supervision of an experienced person. This also applies to personnel undergoing general training. Comply with the legal minimum age. This device is not intended to be used by people (including children) who have restricted mental, sensory or intellectual abilities or who have a lack of experience and/or knowledge.
2.5 Start-up and during operation
Attention!
During commissioning, unexpected and hazardous conditions can arise in the entire installation due to defective adjustments, defective components or incorrect electrical connections. Remove all persons and objects from the hazardous area.
During operation, the device must be closed or installed in a control cabinet. Fuses may only be replaced by new ones and must not be repaired or bypassed. The data for the maximum line fuse are to be considered absolutely (
Technical data). Use only fuses specied in schematic
diagrams.
Any faults detected in the electric system/modules/operating equipment must be corrected immediately. If these faults are not corrected, the device/system is potentially very dangerous. The device/system must therefore not be operated when it is faulty.
Pay attention to smooth, low vibration running of the motor/fan, the appropriate instructions in the drive documentation must be observed!
2.6 Work on the device
Information Mounting, electrical connection, and start-up operation may only be carried out by an electrical specialist in accordance with electrotechnical regulations (e.g. EN 50110 or EN 60204)!
Operating Instructions RETP6 / RETP10 Safety instructions
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
5/31
Danger due to electric current It is generally forbidden to carry out work on electrical live parts. Protection class of the device when open is IP 00! It is possible to touch hazardous voltages directly! The safe isolation from the supply must be checked using a two-pole voltage detector.
Attention! Automatically restart after a power failure or mains disconnection!
2.7 Modications / interventions in the device
Attention!
For reasons of safety, no unauthorized interventions or modications may be made on the device. All planned modications must be authorized by the manufacturer in writing.
Only use the manufacturers original spare parts / wearing parts / accessories. These parts are specially designed for this device. If parts from other sources are used, there is no guarantee that they are designed and produced for the proper loads and with the required level of safety. Parts and special equipment not supplied by the manufacturer are not approved for use.
2.8 Operators obligation of diligence
The contractor or owner must also ensure that the electric systems and equipment are operated and maintained in accordance with electro-technical regulations.
The owner is obliged to ensure that the device are operated in perfect working order only.
The device may only be used as intended (
Application).
You must periodically examine the safety equipment for their properly functioning condition.
The assembly instructions and/or operating instructions are always readily available at the location where the device is being used, are complete and are in legible condition.
These persons are regularly instructed in all applicable questions regarding occupational safety and environmental protection and are knowledgeable regarding the assembly instructions and/or operating instructions and, especially, are familiar with the safety instructions contained therein.
All safety and warning notices attached to the device are never removed and remain legible.
2.9 Employment of external personnel
Maintenance and service work are frequently carried out by external employees who often do not recognize the specic situations and the thus resulting dangers.These persons must be comprehen­sively informed about the hazards in their area of activity. You must monitor their working methods in order to intervene in good time if necessary.
3 Product overview
3.1 Operational area
The controller described is used for continuous speed adjustment on variable voltage 1~ motors used to drive ventilators or pumps.
3.2 Maintenance
The device must be checked for soiling and, if necessary, cleaned in periodic intervals.
3.3 Transport
The device is packed ex factory to suit the transport method previously agreed.
Always use the original packaging materials when transporting the device.
Avoid shocks and impacts to the device during the transport.
During manual handling the human lifting and carrying restrictions must be observed and adhered to.
Operating Instructions RETP6 / RETP10 Product overview
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
6/31
3.4 Storage
The device must be stored in its original packaging in a dry and weather-proof room.
Avoid exposure to extreme heat and cold.
Avoid over-long storage periods (we recommend a maximum of one year).
3.5 Disposal / recycling
Disposal must be carried out professionally and environmentally friendly in accordance with the legal stipulations.
4 Mounting
4.1 General notes
Attention!
The following points must be complied with during the mechanical installation to avoid causing a defect in the device due to assembly errors or environmental inuences:
Before installation remove the device from the packing and check for any possible shipping damage!
Assemble the device on a clean and stable base. Do not distort during assembly! Use the appropriate mounting devices for proper installation of the unit!
Do not mount equipment on vibrating base!
When mounted onto lightweight walls, there must be no impermissibly high vibrations or shock loads. Any banging shut of doors that are integrated into these lightweight walls, can result in extremely high shock loads. Therefore, we advise you to decouple the devices from the wall.
Do not allow drilling chips, screws and other foreign bodies to reach the device interior!
The device should be installed in a location where it will not be disturbed, but at the same time can be easily accessed!
Depending on the housing model use supplied stoppers for cable inlets, cut off necessary cable inlets respectively to the cable diameter. Or alternative use cable inlet for cable glands. Any cable ducts openings not used must be sealed!
Care must be taken to avoid direct radiation from the sun!
The device is designed for vertical installation (cable inlet down). A horizontal or reclined installation is only permissible after technical release of the manufacturer!
Be sure to observe proper heat dissipation (
Technical data, heat dissipation).
4.2 Minimum space requirement
In order to ensure sufcient ventilation of the device, clearance on all sides of at least 50 mm has to be maintained to the housing walls, switch cabinet doors, wiring ducts, etc. The same clearance applies to the installation of several devices next to each other. When installing several devices on top of each other, the danger of reciprocal heating exists. This layout is only then permissible when the air suctioned from the upper unit does not become warmer than the permissible ambient temperature (
Technical data). I.e., a correspondingly larger clearance
or thermal shielding is required.
4.3 Outdoor installation
Outdoor installation is possible up to -20 °C when the controller supply is not switched off. Installation must be protected from the effects of weather as much as possible, including protection from direct sunlight!
Operating Instructions RETP6 / RETP10 Mounting
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
7/31
4.4 Installation location for agriculture
In order to avoid damage caused by ammoniac vapours, the controller shall not be installed in the stable, but rather in an outhouse wherever possible.
4.5 Temperature inuences during commissioning
Avoid condensation in the controller and functional faults attributable to condensation by storing the controller at room temperature!
5 Electrical installation
5.1 Safety precautions
Danger due to electric current
Work on electric components may only be carried out by trained electricians or by persons instructed in electricity under the supervision of an electrician in accordance with electrical engineering regulations.
It is forbidden to carry out work on electrically live parts.
A second person must always be present when working on energized parts or lines who disconnects in case of emergency.
Inspect electrical equipment periodically: retighten loose connections – immediately re­place damaged lines and cables.
Always keep switch cabinets and all electrical supply facilities locked. Access is only allowed for authorized persons using a key or special tool.
Operating the device with the housing cover removed is prohibited because energized, exposed parts are present inside the device. Disregarding this regulation can lead to severe personal injury.
The required protective earth connection is established using screws between the hous­ing parts in metal terminal space covers and housing casings. Commissioning is only permissible after these screws have been properly attached!
Metal screwed-connections are not permitted in plastic housing parts because there is no potential equalization.
Never clean electrical equipment with water or similar liquids.
Information
The respective connections are represented in the enclosure of this manual (
Connection diagram)!
5.2 EMC-compatible installation
5.2.1 Motor cable
The applicable standard for interference emissions is EN 61000-6-3. Compliance with this standard is achieved through the use of an unscreened motor feed cable.
5.2.2 Signal cable
Pay attention to sufcient distance from powerlines and motor wires to prevent interferences. The control cable may not be longer than 30 m. Screened control cables must be used when the cable length is longer than 20 m. When using a shielded cable connect the shielding to one side only, i.e. only to the control unit with the protective ground (keep cable short and with as little inductance as possible!).
5.2.3 Harmonics current for devices 16 A
According to EN 61000-3-2 the devices are to be classied as professional devices. The application is therefore limited to use by trade, certain vocations or industries. Connection to a low voltage supply (public networks) is allowed insofar as this has been claried with the respective energy supply company responsible. Note: up to a maximum current of approx. 4 A, the limits are adhered to with no restrictions. Exception for Germany: An energy provider follows the technical connection conditions of the TAB2007, in which case the use of phase angle controlled devices up to a rating of 3.4 kVA per phase is allowed.
Operating Instructions RETP6 / RETP10 Electrical installation
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
8/31
5.3 Mains connection
Power from the mains is connected to terminals: PE, L1 and N. Here, it must be strictly observed that the mains voltage lies within the allowable tolerance specications (
Technical data and nameplate
afxed to the side).
Danger due to electric current The mains voltage must comply with the DIN EN 50160 quality characteristics and the dened standard voltages in IEC 60038!
5.4 Motor connection
The motor is connected at terminals U1 and U2. Several motors can be connected to the device.
Attention The maximum total control current (specied for electronic voltage regulation) for all motors may not exceed the devices rated current. If the maximum control current for electronic voltage regulation is not known, a supplementary 20% of the rated motor current must be allowed for. When controlling motors from other manufacturers, the controllability and the maximum current for electronic voltage regulation should be requested from the manufacturer.
Information
It is recommended that a separate motor protection unit be foreseen for each fan.
5.4.1 Running noise
When controlling ventilators using electronic voltage regulators, motor noise can occur (due to the system), which can be troublesome. On fast running ventilators with a high level of air noise, this noise is relatively low. On slow running ventilators with a low level of air noise, this noise may be dominant in the lower speed range due to the occurrence of resonance.
5.5 Motor protection
The motor can be protected by connecting thermostats TB. When multiple motors are connected, it is essential to ensure that thermostats TB are always connected in series. If a connected thermostat is tripped (break between the two terminals “TB”), the device is switched off and is not switched back on. Relais K1 is de-energized, terminals 11 - 12 bridged. The signal lamp ashes in code
|2|
(
Diagnostics / faults).
Possibilities for re-starting after the drive has cooled down (terminals TB bridged) by:
By switching the mains voltage off and then on again.
Via a digital input for remote control (ON / OFF enable).
Attention!
An outside voltage may never be connected to the terminals TB”!
If a bypass circuit is installed, or in the “100 %” position on devices with a main switch, the motor protection inside the controller has no function. In this case, additional motor monitoring may be required.
5.6 Signal or sensor connection (E1 = Analog In 1)
The unit has one-analog input: terminals E1 / “GND” (Analog In 1). The connection is independent of the programmed operating mode and from the sensor signal employed. The internal jumpers must be placed in correct position depending on input signal. Factory setting 0 ­10 V.
When connecting passive temperature sensors TF.. (KTY81-210) must be paid attention to no polarity.
When connecting active sensors attention must be paid to correct polarity, a 24 V DC power supply is integrated.
Operating Instructions RETP6 / RETP10 Electrical installation
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
9/31
For sensors in two-wire-technology (4 - 20 mA signal), the connection is made on the +24 V and E1 (GND terminal is omitted).
Over DIP 4 an inverting of the input is possible for mode
1.01 speed controller.
DIP 4 =
|
OFF| (factory setting) for signals: 0 - 10 V, 2 - 10 V, 0 - 20 mA, 4 - 20 mA
DIP 4 =
|ON|
for signals: 10 - 0 V, 10 - 2 V, 20 - 0 mA, 20 - 4 mA
Attention! Never apply line voltage to analog inputs!
5.7 Output voltage 0 - 10 V (A1 = Analog Out 1)
Connection to terminals A1 - GND = “Analog Out 1” (I
max
10 mA).
It is not permissible to connect outputs of several devices to each other!
For mode speed controller
1.01 function of signal output A1 (Analog Out 1) can be determined
by DIP 8.
DIP 8 =
|
OFF|Constant voltage + 10 V for external potentiometer (factory setting)
DIP 8 =
|ON|
0 - 10 V modulation 0 - 100 %
Proportional the internal control of modulation with consideration “n-min” and “n-max” setting.
For enable “OFF” it goes not back to0 V.
For motor fault the output signal remains for a slave controller (“Master-Slave” combination).
For mode as P-Controller or PI-Controller
2.01 , 3.01, 4.01 the function is rmly adjusted.
0 - 10 V
modulation 0 - 100 %
Proportional the internal control of modulation with consideration “n-min” and “n-max” setting.
For enable “OFF” it goes back to 0 V.
For motor fault the output signal remains for a slave controller (“Master-Slave” combination).
Information
For operation as P-Controller or PI-Controller function constant voltage cannot be selected! For operation as P-Controller or PI-Controller function for
|D1|
can be selected with DIP 8!
5.8 Voltage supply for external devices (+24V, GND)
There is an integrated power supply for external devices, e.g. a sensor. Terminal +24 V, output voltage tolerance +/- 20%. max. load current
Technical data.
In case of overload or short circuit (24 V – GND), the external power supply is shut down (multi-fuse). The device performs a Reset and continues operation. It is not permissible to connect outputs of several devices to each other!
5.9 Digital input (Digital In 1 = D1)
Activation via oating contacts, a low voltage of approx. 24 V DC is connected.
Attention! No disconnection when turned off (no isolation in accordance with VBG4 §6)!
Never apply line voltage to the digital input! It is not permissible to connect inputs of several devices to each other!
Operating Instructions RETP6 / RETP10 Electrical installation
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
10/31
5.9.1 Enable, device ON / OFF Electronic disconnection and Reset after motor fault via floating contact at terminals “D1” - D1
Device ON for closed contact.
Device OFF with opened contact.
Relais K1 remains energized, terminals 11 - 14 bridged. The signal lamp ashes in code
|1|
( Diagnostics / faults)
5.9.2 Reverse action of control function (only for P-Controller / PI-Controller)
For operation as P-Controller or PI-Controller
2.01 , 3.01 , 4.01 . Digital input can used instead for
enable, alternative for reverse of control function (DIP 8 =
|ON|
).
For the effect of the regulation there are two functions:
Val > Set = n+”
increasing modulation for increasing actual value over setpoint.
Val < Set = n+”
increasing modulation for decreasing actual value below setpoint.
When terminals D1 - D1 bridged, the device works with the opposite function than the one set with DIP 4!
5.10 Relay output (K1)
An external fault indicator is available over the potential-free contacts of the built-in relay (max. contact rating
Technical data and connection diagram).
For operation the relay is energized, terminals 12 and 14 are bridged. For fault the relay is de­energized, terminals 11 and 12 are bridged (
Diagnostics / faults).
Fault indicated for: line fault, blown internal semiconductor fuse, broken controller-internal voltage supply, overheating by the motor (thermostats TB connected).
By sensor failure (only in P-Control or PI-Control operation
2.01 , 3.01 , 4.01 ) message only via
ash code of signal lamp (code
|3|
), the relay remains energized.
When switching off via enable (D1 = Digital In 1), the relay remains energized.
5.11 Potential at control voltage connections
The control voltage connections (< 50 V) relate to the joint GND potential (Exception: Relay contacts are potential free). There is a potential separation between the control voltage connections and the protective earth. It must be ensured that the maximum external voltage at the control voltage connections cannot exceed 50V (between GND terminals and PE protective earth). If necessary, a connection to the protective earth potential can be established, install bridge between GND terminal and the PE connection (terminal for screening).
Operating Instructions RETP6 / RETP10 Electrical installation
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
11/31
6 Operating and display elements
6.1 Main switch and potentiometer with integrated light signal
1
2
3
17.09.2012
v_retp_front_bed.VSD
1
Main switch
Position Function
100 %
Ventilators are operated directly from the mains with no control.
The fuse in the device is bypassed! Motor protection has no function
0 Controller off
Auto
Function dependently on selected mode of operation For Speed controller
1.01 adjusting via external signal (DIP 2 = |OFF| = factory setting) or internal
potentiometer set (DIP 2 =
|ON|
).
Setting range: Output voltage 0 - 100 %.
For P-Controller,
2.01 , 3.01 and PI-Controller, 4.01
Automatic speed control depending on actual value measured and congured set value.
Manual setting of output voltage by potentiometer 2
2
Potentiometer outside 0...100 %
For main switch position “Auto” function depending on internal switch “DIP 2” and selected mode
For Speed controller
1.01 always without function
For the P controller,
2.01 , 3.01 and PI controller, 4.01 the “DIP 2 switch can be used to select whether
the set value setting can be made easily using the outer potentiometer or using the internal potentiometer “set. The internal potentiometer is set to active ex-factory (DIP 2 =
|
OFF
|
) i.e. the set value setting is protected against unauthorized adjustments.
– For temperature control
2.01 with passive sensors TF.. (KTY).
setting range: 0 - 100 %
-26...76 °C (measuring range of controller).
– For control with active sensors
3.01 , 4.01 (0 - 10 V, 4 - 20 mA).
Setting range: 0 - 100 %
measuring range of sensor.
For main switch position “Hand”
Setting of output voltage 0 -100 %. Independently from input signal and selected mode.
3
Potentiometer with integrated light signal
Indicate the operating conditions over ashing code.
Operating Instructions RETP6 / RETP10 Operating and display elements
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
12/31
6.2 Internal Setting
Attention!
The controller housing cover may only be removed when the power line has been switched off! It is generally forbidden to carry out work on electrical live parts. Protection class of the device when open is IP 00! It is possible to touch hazardous voltages directly!
19.09.2008
v_pxet_q_intern_bed.VSD
%
n-max
0 100
R7
%
set
0 100
R4
R5
%
n-min
0 100
R6
V
°C
mA
E1
ON
OFF
10987654321
DIP S1
%
Pband
5
30
Potentiometer
set
For main switch position “Auto” function depending on internal switch DIP 2 and selected mode (for main switch position “Hand” without function).
For Speed controller
1.01 and DIP 2 = |OFF
|
(factory setting) without function
For Speed controller
1.01 and DIP 2 = |ON
|
setting of output voltage 0 - 100 %
For P-Controller,
2.01 , 3.01 and PI-Controller, 4.01 can be selected with DIP 2 whether setpoint
setting is made by these internal potentiometer or by the outside potentiometer, (factory setting internal potentiometer active (DIP 2 =
|
OFF
|
).
For temperature control
2.01 with passive sensors TF.. (KTY).
setting range: 0 - 100 %
-26...76 °C (measuring range of controller).
For control with active sensors
3.01 , 4.01 (0 - 10 V, 4 - 20 mA).
Setting range: 0 - 100 %
measuring range of sensor.
Potentiometer
Pband
Function dependently on selected mode of operation
For Speed controller
1.01 : without function
P-controller
2.01 , 3.01
– For temperature control with passive sensors TF.. (KTY).
Setting range: 5 - 30 %
5.1 - 30.6 K.
– For control with active sensors (0 - 10 V, 4 - 20 mA).
Setting range: 5 - 30 %
5 - 30 % measuring range of sensor.
PI-Controllerr
4.01
– For control with active sensors (0 - 10 V, 4 - 20 mA).
Setting range: 5 - 30 %
5 - 100 % measuring range of sensor.
Potentiometer
n-min
Minimal output voltage (basic speed)
Setting range: 0 - 100 % (n-min takes priority if over n-max)
Potentiometer
n-max
Maximal output voltage (speed limiter)
Setting range: 100 % - “n-min”
Jumper
E1
Basic setting for kind of signal at analog input E1 = Analog In 1
Dipswitch
S1
Basic setting for device function
Operating Instructions RETP6 / RETP10 Operating and display elements
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
13/31
7 Base setup
7.1 Programming of the desired function (Speed controller / P-Controller, PI-Controller)
It is possible to use the device as a Speed controller or as a P-controller, PI-Controller. Selection of the function must rst be made by setting the internal jumper E1 and dipswitch S1.
Factory setting of internal jumper E1 in position for 0 - 10 V input signal. When using other signals bring the jumper in correct position.
Factory setting of all dipswitches is
|
OFF| position for operation as Speed controller
1.01 with external setting signal. In the following the fundamental dipswitch positions for
further modes of operation are represented. Depending upon desired function further adjust­ments are necessary (
function dipswitches).
Attention! Setting of jumper and switches not under voltage! Observe the safety notices! Changed functions become active partly only after renewed switching on the mains voltage!
E1 Analog In (factory setting 0 - 10 V)
13.03.2012
v_jumper_e1_dip_s1_mode.vsd
1
GND
0 - 10 V
10 k
1
GND
TF..
TF.. (KTY)
31
BN GN
24V
1
MBG..
4 - 20 mA
(0 - 20 mA)
4 - 20 mA
24V
1
GND
YE
DSG..
WHBN
0 -10 V
24V
1
GND
MAL1/10
21
0 -10 V
E1
E1
0 - 10 V
E1
0 - 10 V
E1
.01 .01 .01 .01
ON
OFF
10987654321
S1
ON
OFF
10987654321
S1
ON
OFF
10987654321
S1
ON
OFF
10987654321
S1
7.2 Select operation mode
Simple installation is possible through the use of modes of operation.
Mode
Signal or Sensor
(input)
Function
1.01 Signal 0 - 10 V Speed controller, two step operation (factory setting)
2.01 Sensor TF.. (E1) Temperature control airconditioning and refrigeration
3.01 Sensor MBG.. (E1) Pressure control condensers (refrigeration)
4.01
Sensor DSG.. (E1) Pressure control for ventilation systems
Sensor MAL.. (E1) Air velocity control e.g. clean room
Operating Instructions RETP6 / RETP10 Base setup
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
14/31
7.3 Function of dipswitches for operation as Speed controller 1.01 (DIP 1 = |OFF|)
For operation as a speed controller (main switch = Auto), the output voltage is set manually by adjusting the built-in potentiometer, by an external potentiometer or external signal. The desired function is determined with dipswitch S1. Position factory setting for all dipswitches =
|
OFF
|
DIP Function OFF ON
1
Selection: Speed controller / P-Controller,
PI-Controller
Speed controller P-Controller, PI-controller
2 Signal source of control
Setting of output voltage by external signal to E1
(Potentiometer outside and potentiome­ter inside = “set” without function)
Setting of output voltage by “potentiometer inside = set
(Potentiometer outside without function)
3 Type of Signal 0 - 10 V, 0 - 20 mA 2 - 10 V, 4 - 20 mA
4 Inverting signal input 0 - 10 V, 2 - 10 V, 0 - 20 mA, 4 - 20 mA 10 - 0 V, 10 - 2 V, 20 - 0 mA, 20 - 4 mA
5 Minimum speed cut off OFF ON
6 Hardstart function OFF ON
7 no function - -
8
Function signal output Analog Out 1
Constant voltage + 10 V for external potentiometer
0 - 10 V
modulation 0 - 100 %
9 no function - -
10 no function - -
7.4 Function of dipswitches for operation as P-Controller, PI-Controller,
2.01 , 3.01 , 4.01
(DIP 1 = |ON|)
For operation as a P-controller, PI-Controller (main switch = Auto) the actual value measured by the sensor is compared with the nominal value that has been set. The output voltage and hence the rotational speed of the connected motor automatically change as a function of the parameter settings. The desired function is determined with dipswitch S1. Position factory setting for all dipswitches =
|
OFF
|
DIP Function OFF ON
1
Selection: Speed controller / P-Controller,
PI-Controller
Speed controller P-Controller, PI-controller
2
Function potentiometer out­side
Setpoint setting via potentiometer inside = set.
Potentiometer outside without function.
Setpoint setting via potentiometer out­side
Potentiometer inside = set without func­tion.
3 Type of Signal
0 - 10 V, 0 - 20 mA
TF.. (KTY)
2 - 10 V, 4 - 20 mA
4
Control function (e.g. Cooling / Heating
increasing modulation for increasing actual
value
increasing modulation for decreasing ac-
tual value
5 Minimum speed cut off OFF ON
6 Hardstart function OFF ON
7 Controller function
|P|
Applications: Temperature control airconditioning and
refrigeration sensor TF.. Pressure control condensers (refrigera-
tion) sensor MBG..
|PI|
Applications: Volume control (constant) for ventilation
systems Sensor DSG.. Air velocity control e.g. clean room Sensor
MAL..
8
Function digital input Digital In 1
Enable
Device ON / OFF
Switch over control function:
- Val > Set = n+ (Cooling)
- Val < Set = n+ (Heating) (reverse function DIP 4)
9 no function - -
10 no function - -
Operating Instructions RETP6 / RETP10 Base setup
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
15/31
7.5 Minimum speed cut off DIP 5
7.5.1 For mode Speed controller
1.01
If no n-min is adjusted,output voltage goes continuously with reduction of the regulating variable down to 0 (cutoff below approx. 2 % regulating variable).
Without minimum speed cut OFF (DIP 5 =
|
OFF| = factory setting)
If minimal speed n-min is adjusted (e.g. 20%), then no disconnection of the fan takes place. I.e. always a minimum ventilation is ensured (fan does not go under setting n-min).
With minimum speed cut off (DIP 5 =
|ON|
)
Cutoff below approx. 2 % regulating variable from sestting n-min to 0”.
Switch on again for a regulating variable above 5 % (to setting n-min).
Functional diagram
setting for operation as Speed controller
7.5.2 For operation as P-Controller, PI-Controller 2.01 , 3.01 , 4.01
This function is primarily signicant for installation of the device as a pure P-Controller ( 2.01 , 3.01 ).
Without minimum speed cut OFF (DIP 5 =
|
OFF
|
=
factory setting)
If no “n-min” is adjusted, the fan stops with reaching the desired value.
If “n-min” is adjusted (e.g. 20 %), then no disconnection of the fan takes place. I.e. always a minimum ventilation is ensured (fan does not go under setting “n-min”).
With minimum speed cut off (DIP 5 =
|ON|
)
When the setpoint is reached, the modulation is reduced to “0 %”, or to the set value if “n-min” is specied.
For actual value = setpoint disconnection takes place from “n-min” to “0”. Hysteresis (ON / OFF) approx. 2.5 % of 100 % set value.
nM
50 %
100 %
I
Min.
Min. 35 % Max. = 100 %
20 °C
S
7 K
R
27 °C
-2.0 K
10.05.2007
v_min_luft_abschalt.vsd
Minimum speed cut off (idealized principle diagram)
nM Motor speed S Setpoint R Pband I Actual value
7.6 Hardstart function DIP 6
Special function for motorstart with maximum output voltage.
DIP 6 =
|
OFF|“Hardstart function = OFF (factory setting).
After switching the mains voltage on the output voltage rises during the firmly programmed run-up time to the given value.
DIP 6 =
|ON|
Hardstart function = ON.
For a safe starting of the connected fans the function Hard start can be activated. After switching on (line voltage or enable via digital input D1) the controller generates for
approx. 10 seconds max. voltage 100 % ignoring any control or sensor signal. Afterwards the output voltage adjusts itself to the given or over the control amplier calculated
value. For operation as controller(from mode
2.01 ) the Hard start function works also by switching
over the control function (Heating / Cooling).
Operating Instructions RETP6 / RETP10 Base setup
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
16/31
8 Start-up
8.1 Prerequisites for commissioning
Attention!
1. You must mount and connect the device in accordance with the operating instructions.
2. Double check that all connections are correct.
3. The mains voltage must match the information on the rating plate.
4. The rated current on the rating plate will not be exceeded.
5. Make sure that no persons or objects are in the fan's hazardous area.
9 Setting for operation
9.1 Speed controller
1.01
9.1.1 Setting for operation as Speed controller
Signal to:
E1
E1
GND
14.02.2008
v_signal_e1.vsd
E1 Setting via external signal or external potentiometer (DIP 2 =
|
OFF|= factory
setting)
Setting range: Output voltage from approx. 0 - 100 % of connected line voltage or in range of settings n-min up to n-max.
(Potentiometer set without function)
%
set
0 100
18.07.2011 v_set_pxet.VSD
set For setting via internal potentiometer (DIP 2 =
|ON|
)
Setting range: Output voltage from approx. 0 - 100 % of connected line voltage or in range of settings n-min up to n-max.
18.07.2011 v_nmin_pxet.VSD
%
n-min
0 100
n-min Minimum output voltage (basic speed)
Setting range: 0 - 100 % (n-min takes priority if over n-max).
18.07.2011 v_nmax_pxet.VSD
%
n-max
0 100
n-max Maximal output voltage (speed limiter)
Setting range: 100 % - “n-min”.
Operating Instructions RETP6 / RETP10 Start-up
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
17/31
9.1.2 Diagram: setting signal and speed
nM
50 %
100 %
0 1 2 3 4 5 6 7 8 9 10
10 9 8 7 6 5 4 3 2 1 0
0 2 4 6 8 10 12 14 16 18 20
20 18 16 14 12 10 8 6 4 2 0
4 5,6 7,2 8,8 10,4 12 13,6 15,2 16,8 18,4 20
20 18,4 16,8 15,2 13,6 12 10,4 8,8 7,2 5,6 4
0 – 10 V
10 – 0 V 0 – 20 mA 20 – 0 mA 4 – 20 mA 20 – 4 mA
Min.
Min. 0 % Max. = 100 %
Min. 35 % Max. = 85 %
05.02.2008
v_nmotor_101_miluab.vsd
Si
Idealized principle diagram
nM Motor speed Si Signal
9.1.3 Operation with two variable output voltages (two steps)
DIP2 =
|
OFF| for setting via external signall.
Switchover between two steps via external potential-free contact possible.
Step 1 (low speed). When there is no input signal connected to the input terminal E1, then the unit supplies the output voltage set by n-min.
Step 2 (high speed). When the terminal A1 (+10 V) is connected with the input terminal E1 then the units supplies the output voltage set by n-max.
n-min
nM
100 %
1
t
n-max
12
05.02.2008
v_diagr_2stufen.VSD
"A1" (+10 V)
"E1"
nMotor
= "n-max"
nMotor
= "n-min"
1
2
05.02.2008
v_schalter_2stufen.VSD
Operating Instructions RETP6 / RETP10 Setting for operation
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
18/31
9.2 Temperaturre control (P-Controller) 2.01
9.2.1 Setting for operation as Temperature controller
%
set
0 100
R4
08.02.2008 v_set_pxet.VSD
potentiometer inside
(DIP 2 = OFF)
or
26.05.2008 v_pxet_q_aussen _pot.VSD
potentiometer outside
(DIP 2 = ON)
set
Setpoint setting alternatively by potentiometer inside (DIP 2 =
|
OFF|) or potenti-
ometer outside (DIP 2 =
|ON|
)
For control with active sensors (0 - 10 V, 4 - 20 mA) Setting range: 0 - 100 %
measuring range of sensor
For Temperature control with passive sensors TF.. (KTY) Setting range: 0 - 100 %
-26...76 °C (measuring range of controller)
The enclosed scale for type TF.. temperature sensors can be attached above the potentiometer.
28.05.2008
v_pxet_q_skala_temp.VSD
set [%] 0 10 20 30 40 50 60 70 80 90 100
[C°] -26.0 -15.8 -5.6 4.6 14.8 25.0 35.2 45.4 55.6 65.8 76.0
Scale 0 - 100 % -26...76 °C for Temperature control with passive sensors TF.. (KTY)
set
[%]
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100
[° C] -26.0 -20.9 -15.8 -10.7 -5.6 -0.5 4.6 9.7 14.8 19.9 25.0 30.1 35.2 40.3 45.4 50.5 55.6 60.7 65.8 70.9 76.0
20.03.2008 v_pand_pxet.VSD
R5
%
Pband
5
30
Pband Pband
Narrow control range = Short control times Wide control range = Longer control times and more stable control
For control with active sensors (0 - 10 V, 4 - 20 mA) Setting range: 5 - 30 %
5 - 30 % measuring range of sensor
For Temperature control with passive sensors TF.. (KTY) Setting range: 5 - 30 %
5.1 - 30.6 K
08.02.2008 v_nmin_pxet.VSD
%
n-min
0 100
R6
n-min Minimum output voltage (basic speed)
Setting range: 0 - 100 % (n-min takes priority if over n-max)
08.02.2008 v_nmax_pxet.VSD
%
n-max
0 100
R7
n-max Maximal output voltage (speed limiter)
Setting range: 100 % - “n-min”
Operating Instructions RETP6 / RETP10 Setting for operation
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
19/31
9.2.2 Example Temperature control “Cooling function” (factory setting)
Val > Set = n+” (DIP4 =
|
OFF|)
Temperature sensor type TF..
Measuring range controller -26...+76 °C
Settings:
set = 50 %
25 °C (102 K / 100 % x 50 % - 26 °C)
Pband = 10 %
10.2 K (102 K / 10 )
U
Motor
50 %
100 %
[°C]
n-min. 0 %, n-max. = 100 %
50 % ^ 25 °C
Set
Pband 10 % ^ 10.2 K
11.03.2008
v_temp_cool_umotor.vsd
35.2 °C
n-min. 35 %, n-max. = 85 %
Idealized principle diagram
9.2.3 Example Temperature control “Heating function”
Val < Set = n+” (DIP4 =
|ON|
)
Temperature sensor type TF..
Measuring range controller -26...+76 °C
Settings:
set = 50 %
25 °C (102 K / 100 % x 50 % - 26 °C)
Pband = 10 %
10.2 K (102 K / 10 )
U
Motor
50 %
100 %
[°C]
n-max. = 100 %, n-min. 0 %
50 % ^ 25 °C
Set
Pband 10 % ^ 10.2 K
11.03.2008
v_temp_heat_umotor.vsd
14.8 °C
n-max. = 85 %, n-min. 35 %
Idealized principle diagram
Operating Instructions RETP6 / RETP10 Setting for operation
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
20/31
9.3 Pressure control condensers (P-Controller) 3.01
9.3.1 Setting for operation as Pressure controller
%
set
0 100
R4
08.02.2008 v_set_pxet.VSD
potentiometer inside
(DIP 2 = OFF)
or
26.05.2008 v_pxet_q_aussen _pot.VSD
potentiometer outside
(DIP 2 = ON)
set
Setpoint setting alternatively by potentiometer inside (DIP 2 =
|
OFF|) or potenti-
ometer outside (DIP 2 =
|ON|
)
For control with active sensors (0 - 10 V, 4 - 20 mA) Setting range: 0 - 100 %
measuring range of sensor
The enclosed scale for the type MBG-30I pressure sensor can be attached above the potentiometer.
28.05.2008
v_pxet_q_skala_mbg30.VSD
set [%] 0 10 20 30 40 50 60 70 80 90 100
[bar] 0.0 3.0 6.0 9.0 12.0 15.0 18.0 21.0 24.0 27.0 30.0
20.03.2008 v_pand_pxet.VSD
R5
%
Pband
5
30
Pband Pband
Narrow control range = Short control times Wide control range = Longer control times and more stable control
For control with active sensors (0 - 10 V, 4 - 20 mA) Setting range: 5 - 30 %
5 - 30 % measuring range of sensor
08.02.2008 v_nmin_pxet.VSD
%
n-min
0 100
R6
n-min Minimum output voltage (basic speed)
Setting range: 0 - 100 % (n-min takes priority if over n-max)
08.02.2008 v_nmax_pxet.VSD
%
n-max
0 100
R7
n-max Maximal output voltage (speed limiter)
Setting range: 100 % - “n-min”
Operating Instructions RETP6 / RETP10 Setting for operation
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
21/31
9.3.2 Example Pressure control condensers Pressure sensor
Type MBG-30I
Measuring range 0 - 30 bar
Output signal 4...20 mA
Settings:
set = 50 %
15.0 bar, in use of refrigerant medium table for R507
Pband = 10 %
3.0 bar
U
Motor
50 %
100 %
[bar] / [°C]
50 %
15 bar ^ 34.28 °C @
507
Set
Pband 10 %
12.03.2008
v_diagramm_bar_c.vsd
18 bar ^ 41.53 °C @ 507
n-min. 0 %, n-max. = 100 %
n-min. 35 %, n-max. = 85 %
Idealized principle diagram
Operating Instructions RETP6 / RETP10 Setting for operation
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
22/31
9.3.3 Setting with refrigerant medium table
Information
Calculation for relative pressure (differential measurement of pressure relative to ambient pressure).
Set
0 %5 %10%15%20%25%30%35%40%45%50%55%60%65%70%75%80%85%90%95%100
%
MBG-30I
[bar]
0.00 1.50 3.00 4.50 6.00 7.50 9.00 10.50 12.00 13.50 15.00 16.50 18.00 19.50 21.00 22.50 24.00 25.50 27.00 28.50 30.00
I
[mA]
4.0 4.8 5.6 6.4 7.2 8.0 8.8 9.6 10.4 11.2 12.0 12.8 13.6 14.4 15.2 16.0 16.8 17.6 18.4 19.2 20.0
R12
[°C]
-30.09 -6.28 8.11 18.90 27.70 35.22 41.84 47.80 53.23 58.23 62.90 67.27 71.39 75.30 79.01 82.57 85.97 89.24 92.39 95.43 98.37
R13
[°C]
-81.99 -62.83 -51.33 -42.75 -35.77 -29.82 -24.60 -19.91 -15.65 -11.72 -8.07 -4.65 -1.43 1.61 4.51 7.27 9.91 12.45 14.89 17.25 19.52
R13b1
[°C]
-58.14 -36.81 -23.92 -14.26 -6.38 0.36 6.29 11.63 16.49 20.97 25.15 29.06 32.75 36.25 39.58 42.76 45.81 48.74 51.56 54.28 56.92
R22
[°C]
-41,11 -19.52 -6.57 3.09 10.95 17.65 23.53 28.80 33.60 38.02 42.13 45.97 49.59 53.02 56.27 59.38 62.35 65.20 67.95 70.59 73.15
R23
[°C]
-82.44 -64.82 -54.36 -46.61 -40.34 -35.02 -30.36 -26.20 -22.43 -18.96 -15.75 -12.75 -9.94 -7.27 -4.75 -2.35 -0.05 2.15 4.26 6.30 8.26
R32
[°C]
-52.53 -32.24 -20.30 -11.51 -4.44 1.54 6.76 11.41 15.62 19.47 23.03 26.35 29.47 32.40 35.18 37.83 40.35 42.76 45.07 47.30 49.44
R114
[°C]
3.45 30.02 46.05 58.04 67.82 76.17 83.53 90.13 96.15 101.70 106.87 111.71 116.27 120.59 124.71 128.63 132.40
136.0­11
139.49 142.85 146.10
R134a
[°C]
-26.43 -4.29 8.93 18.75 26.72 33.49 39.43 44.75 49.58 54.02 58.14 61.99 65.62 69.04 72.30 75.40 78.36 81.20 83.93 86.57 89.11
R142B
[°C]
-10.07 15.44 30.54 41.71 50.72 58.37 65.05 71.01 76.42 81.38 85.98 90.27 94.29 98.09 101.70 105.13 108.40 111.54 114.55 117.44 120.24
R227
[°C]
-17.58 5.82 20.05 30.76 39.52 47.03 53.66 59.63 65.09 70.13 74.83 79.24 83.41 87.37 91.13 94.74 98.20 101.52 104.73 107.83 110.83
R401
[°C]
-27.05 -4.65 8.71 18.63 26.68 33.52 39.52 44.89 49.77 54.25 58.41 62.30 65.96 69.41 72.70 75.82 78.81 81.68 84.44 87.09 89.66
R401A
[°C]
-29.21 -6.93 6.40 16.33 24.39 31.26 37.28 42.68 47.59 52.10 56.29 60.22 63.91 67.40 70.72 73.88 76.91 79.81 82.60 85.29 87.99
R401B
[°C]
-28.97 -6.74 6.52 16.37 24.35 31.14 37.08 42.41 47.24 51.69 55.81 59.67 63.29 66.72 69.97 73.07 76.03 78.87 81.60 84.23 86.77
R402
[°C]
-47.59 -26.34 -13.71 -4.36 3.21 9.64 15.26 20.29 24.85 29.04 32.92 36.55 39.95 43.17 46.23 49.13 51.91 54.57 57.13 59.59 61.97
R402A
[°C]
-47.59 -26.34 -13.71 -4.36 3.21 9.64 15.26 20.29 24.85 29.04 32.92 36.55 39.95 43.17 46.23 49.13 51.91 54.57 57.13 59.59 61.97
R402B
[°C]
-45.46 -24.06 -11.33 -1.89 5.75 12.23 17.92 22.99 27.61 31.84 35.77 39.44 42.89 46.14 49.23 52.18 54.99 57.69 60.28 62.77 65.18
R404A
[°C]
-46.36 -24.92 -12.18 -2.74 4.89 11.37 17.04 22.11 26.72 30.94 34.86 38.52 41.95 45.20 48.28 51.21 54.01 56.70 59.28 61.67 64.16
R407A
[°C]
-39.47 -18.64 -6.32 2.78 10.13 16.36 21.80 26.66 31.06 35.10 38.84 42.33 45.60 48.69 51.62 54.41 57.07 59.62 62.06 64.42 66.69
R407B
[°C]
-43.49 -22.74 -10.44 -1.34 6.01 12.24 17.69 22.55 26.97 31.02 34.77 38.27 41.56 44.66 47.61 50.41 53.09 55.65 58.11 60.48 62.76
R407C
[°C]
-37.31 -16.35 -3.95 5.22 12.62 18.89 24.37 29.27 33.70 37.77 41.54 45.06 48.36 51.47 54.43 57.24 59.92 62.49 64.96 67.34 69.63
R500
[°C]
-33.80 -10.77 3.02 13.28 21.62 28.72 34.96 40.54 45.62 50.29 54.63 58.69 65.51 66.13 66.56 72.83 75.97 78.97 81.86 84.65 87.34
R502
[°C]
-45.54 -23.63 -10.53 -0.77 7.15 13.89 19.81 25.10 29.92 34.35 38.47 42.32 45.94 49.37 52.62 55.72 58.69 61.54 64.28 66.91 69.46
R503
[°C]
-88.64 -70.55 -59.77 -51.77 -45.29 -39.79 -34.96 -30.65 -26.73 -23.12 -19.78 -16.66 -13.72 -10.95 -8.32 -5.81 -3.41 -1.11 1.10 3.22 5.28
R507
[°C]
-46.51 -25.59 -13.02 -3.64 3.98 10.49 16.20 21.32 25.99 30.28 34.28 38.01 41.53 44.86 48.03 51.05 53.94 56.72 59.39 61.97 64.46
R717
[°C]
-33.59 -13.65 -1.88 6.80 13.80 19.73 24.91 29.52 33.71 37.54 41.09 44.40 47.50 50.43 53.21 55.84 58.36 60.78 63.09 65.32 67.46
Operating Instructions RETP6 / RETP10 Setting for operation
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
23/31
9.4 Pressure control, Air velocity control (PI-Controller) 4.01
9.4.1 Setting for operation as Pressure and air velocity controller
%
set
0 100
R4
08.02.2008 v_set_pxet.VSD
potentiometer inside
(DIP 2 = OFF)
or
26.05.2008 v_pxet_q_aussen _pot.VSD
potentiometer outside
(DIP 2 = ON)
set
Setpoint setting alternatively by potentiometer inside (DIP 2 =
|
OFF|) or potenti-
ometer outside (DIP 2 =
|ON|
)
For control with active sensors (0 - 10 V, 4 - 20 mA) Setting range: 0 - 100 %
measuring range of sensor
The enclosed scale for type DSG.. pressure sensors can be attached above the potentiometer. Example for DSG 200:
28.05.2008
v_pxet_q_skala_dsg200.VSD
set [%] 0 10 20 30 40 50 60 70 80 90 100
[Pa] 0.0 20 40 60 80 100 120 140 160 180 200
The enclosed scale for a type MAL.. air speed sensor can be attached above the potentiometer. Example for MAL1:
28.05.2008
v_pxet_q_skala_mal1.VSD
set [%] 0 10 20 30 40 50 60 70 80 90 100
[m/s] 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
20.03.2008 v_pand_pxet.VSD
R5
%
Pband
5
30
Pband Pband
Narrow control range = Short control times Wide control range = Longer control times and more stable control
For control with active sensors (0 - 10 V, 4 - 20 mA) Setting range: 5 - 30 %
0 - 100 % measuring range of sensor
08.02.2008 v_nmin_pxet.VSD
%
n-min
0 100
R6
n-min Minimum output voltage (basic speed)
Setting range: 0 - 100 % (n-min takes priority if over n-max)
08.02.2008 v_nmax_pxet.VSD
%
n-max
0 100
R7
n-max Maximal output voltage (speed limiter)
Setting range: 100 % - “n-min”
9.4.2 Example: Pressure control for ventilation systems
Pressure sensor
Type DSG200
Measuring range 0 - 200 Pa
Output signal 0...10 V
Settings:
set = 50 %
100 Pa
9.4.3 Example: Air velocity control for clean rooms Air velocity sensor
Type MAL1
Measuring range 0 - 1 m/s
Output signal 0...10 V
Settings:
set = 50 %
0.5 m/s
Operating Instructions RETP6 / RETP10 Setting for operation
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
24/31
10 Diagnostics / Faults
Operating states are indicated by the rotary controls integrated light signal and, at the same time, using the internal status LED by a ashing code.
Code
Relay
K1
Explanation
Reaction of Controller
Adjustment
OFF
de-energized terminals 11 - 12 bridged
no line voltage
In the event of a mains interruption the unit switches OFF and automatically ON when the voltage has been re­stored.
Check line and internal controller fuse.
ON
energized Terminals 12 - 14 bridged
Normal operation without fault
1
energized Terminals 12 - 14 bridged
no enable
Terminals “D1” - “D1” (Digital In 1) not bridged.
For mode Speed controller
1.01 Digital
In 1 is mly pre-programmed for enable. For operation as P-Controller, PI-Control-
ler,
2.01 , 3.01 , 4.01 DIP 8 must be set
to
|
OFF|.
Switch OFF by external contact (
digi-
tal input).
2
de-energized terminals 11 - 12 bridged
Motor fault
Tripping of connected thermostat or break between terminals TB.
The unit cuts out and does not switch on again.
Check motor and connection then reset (
Motor protection).
3
energized Terminals 12 - 14 bridged
Signal fault
Function only for operation as P-Control­ler, PI-Controller (
2.01 )!
Interruption or short circuit in the sensor leads or sensor values measured are out­side measuring range:
- For temperature sensors TF.. (KTY) below approx. -26 °C and above approx. 76 °C
- For active sensors with reaching mini­mum or maximum signal values (depend­ing on selected signal type).
The device works with minimal or maxi­mum modulation depending on whether there is a short-circuit or an interruption, and on the programmed mode of opera­tion.
The controller functions automatically again with the value measured at the temperature sensor after the fault has been rectied.
Check sensor.
Code
28.05.2008
v_flash_code_pxet_q.VSD
3
2
1
ON
OFF
Operating Instructions RETP6 / RETP10 Diagnostics / Faults
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
25/31
10.1 If controller doesn´t work correctly
Information
Setting of dip switches in principle only when device is not under voltage. If the device is on mains supply modications will partly not be identied and realized.
Attention!
It is generally forbidden to carry out work on electrical live parts. Protection class of the device when open is IP 00! It is possible to touch hazardous voltages directly!
11 Enclosure
11.1 Technical data
Type Part.-No.
Rated current
{1}
Max. line fuse
{2}
Integrated semicon-
ductor fuse
{3}
Max. heat dissi-
pation approx.
{1}
Weight
[A] [A] [Part.-No.] [W] [kg]
RETP6
32293
(303612-42)
6 10 M 10 A 5x20 mm 20 1.3
RETP10
32294
(303613-42)
10 16 FF20 A 6x32 mm 40 2.3
{1} with supply voltage of 230 V / 50 Hz, values for other specications available on request {2} Max. supply side line fuse according to DIN EN 60204-1 classication VDE0113 chapter 1 {3} Integrated semiconductor fuse in device (no line safety switch)
Line voltage 1 ~ 230 V (-15...+10 %), 50/60 Hz
Input resistance for sensor or signal set for the rotational speed
for 0 - 10 V input: R
i
> 100 k
for 4 - 20 mA input: R
i
= 100
Output voltage approx. 0 - 100 % of applied mains voltage
Min. motor current approx. 0.2 A
Voltage supply e.g. for sensors +24 V ±20 %, I
max
250 mA
Output (0 - 10 V) I
max
10 mA (short-circuit-proof)
Max. permissible ambient temperature 40 °C (up to 55 °C with derating)
Min. permissible ambient temperature 0 °C (if mains voltage is not switched off up to -20 °C)
Max. permissible installation height 0...4000 m amsl
above 1000 m amsl the rated current is to be reduced by 5 % / 1000 m.
Permissible rel. humidity 85 % no condensation
Electromagnetic compatibility for the standard voltage 230 / 400 V accord­ing to DIN IEC 60038
Interference emission EN 61000-6-3 (domestic household applications)
Interference immunity EN 61000-6-2 (industrial applications)
Harmonics current According EN 61000-3-2 (for a professional device)
Electrical installation / harmonics current
Housing protection IP54
Operating Instructions RETP6 / RETP10 Enclosure
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
26/31
11.1.1 Performance reduction during elevated ambient temperatures
The maximum permissible ambient temperature for the devices is 40 °C. Up to this temperature, loading (maximum continuous current) with the specied rated current is possible. The removal of heat in the unit due to power dissipation is dependent on the ambient temperature, so the maximum load has to be reduced if the ambient temperature is higher than 40 °C! For each degree higher the load has to be reduced approx. 2.2 %. The average value measured during a 24 h period must be 5 K under the max. ambient temperature. For installation in a switch cabinet, the devices dissipation and its possible affect on the ambient temperature must be taken into consideration (
Technical data)!
Maximum load for ambient temperatures higher 40 °C
Type
Rated current for 40 °Cmax. current load for
45 °C
max. current load for
50 °C
max. current load for
55 °C
[A] [A] [A] [A]
RETP6 6 6.0 5.5 5.0
RETP10 10 9.5 9.0 8.0
Operating Instructions RETP6 / RETP10 Enclosure
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
27/31
11.2 Connection diagram
Didital In 1
K1
...6 F1=M10 A / ...10 F1=FF20 A
Analog In 1
Analog Out 1
RETP6/10
N L1PE
Netz
Line
1 ~ 230 V 50/60 Hz
L1
N
N L1PEPE
11 12 14
1
U1 U2
U1 U2
M
1 ~
U1
U2PETBqTB
1 ~ Motor
mit eingebauten Thermostatschaltern
with internal thermostats
2
A1 GND
Ausgang
Output
0...10 V
(I
max
= 10 mA)
+
3
E1 GND GND
Eingang
Input
0...10 V
0...20 mA
4...20 mA TF..(KTY)
+
4
E1
V
mA°C
PEUN17K2
15.07.2009
TB TB
D1 D1 24V
Hand/Auto
0
100 %
Kontaktbelastung
Contact rating
max. AC 250 V 5 A
5
1 Line 1 ~ 230 V, 50/60 Hz 2 1 ~ Motor with internal thermostats 3 Output 0...10 V (I
max
= 10 mA) 4 Input: 0...10 V, 0...20 mA, 4...20 mA, TF..(KTY) 5 Contact rating max. AC 250 V 5 A
A
E1
GND
0-10 V
10 k
0 - 10 V TF..
24V
E1
GND
DSG 0 - 10 V
YE
DSG..
(0 - 10 V)
WHBN
24V
E1
GND
MAL 0 - 10 V
3
MAL1/10
(0 - 10 V)
21
31
BN GN
MBG..-I
24V
E1
MBG..
(4 - 20 mA)
E1
GND
TF..
18.10.2011
v_sensoren_e1_anschlplan_q.vsd
GND
Operating Instructions RETP6 / RETP10 Enclosure
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
28/31
11.3 Dimensions [mm]
RETP6
RETP10
Operating Instructions RETP6 / RETP10 Enclosure
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
29/31
Operating Instructions RETP6 / RETP10 >
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
30/31
11.4 Index
B
basic speed 13 bypass circuit 9
C
control cable 8 control function 11
E
external potentiometer 17 external signal 17
H
heat dissipation 26
I
Input resistance 26 internal potentiometer 17
L
line fuse 26
M
mains is connected 9 mains voltage 9 maximum control current 9 MBG-30I 22 Minimum space requirement 7 Minimum speed cut off 16 Mode 14 motor feed cable 8 motor protection unit 9
O
Outdoor installation 7
P
P-Controller 19, 21 P-controller, PI-Controller 14 PI-Controller 24
R
refrigerant medium table 23 relative pressure 23 relay 11 Relay output 11 Reset 11
S
Speed controller 14 speed limiter 13 standard voltages 9
T
Technical data 3, 26 The motor can be protected 9 two steps 18 two-wire-technology 10
V
voltage regulation 9
11.5 Manufacturer reference
Our products are manufactured in accordance with the relevant international regulations. If you have any questions concerning the use of our products or plan special uses, please contact:
Systemair Industrievägen 3 73930 Skinnskatteberg Telefon:+46 (0) 222 440 00 Telefax:+46 (0) 222 440 99 mailbox@systemair.se www.systemair.se
Operating Instructions RETP6 / RETP10 Index
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
31/31
Loading...