1. SY120SA system brief introduction
SY120SA is a low price & multiple function accesscontrol system, which can expand to connect one card reader and control one door unit. It also equipted with four types of inputs, two types of outputs, and two “CALL” function keys which are programable I/O access points.
SY120SA can work with SYBASE program in order to form the network connection function. With this combination, it can process the data, e-map, manual control, remote control, and emergency control. It could be used as the controller for door access, parking lot access, elevator access and many other use which could be able to apply on SY120SA. The build-in functions also includes two section’s anti-theft and emergency control which can work with alarm system for arm and disarm.
In SY120SA’s System Setting Function Table shows all of the functions. For more detail please check the following instructions.
User can use all of the control setting form the reader’s kekpad. The follow is keypad’s diagram.
1.1 SY120SA system control function list
1.1.1 General use function
1. Proximity Card Open. 2. Proximity Card + Card Password.
3. Proximity Card + Anti-Anti-duress Password. 4. Card Password or Card Number+ Password.
5. Card Number + Anit-Anti-duress Password. 6. Set or modify Card Password.
7. Remove Alarm Status
CALL : Call LED
! : Error LED OK : OK LED : Power LED
FUN : Function Key
: Up Key
: Down Key
MENU : Menu Key EN : Enter Key
CLR : Clear Key
SY120SA Series Operating Manual
© 2004 by SYRIS Technology Corp.
2
1.1.2 System setting function
Code Function Code Function Code Function
0 Remove security 42 Setup Master card 58 Setup I/O data m ode 1 To deploy security 43 Setup Anti-duress password 59 Setup extern reader 2 Login / Logout 44 Remove Anti-duress alarm 45 Enabled or Disable Door Forced 61 Configure Input point setting 31 Add single card 46
Enabled or Disable Door Time-Out
32 Delete single card 48 Encryption Card setting 71 Configure Output point setting 33 Modify single card group data 49 Restore to Default setting 34 Modify single card group status 51 Access with password 81 Setup system time 35 Add multiple card 52 Change defa ul t password 82 Setup time period 36 Delete multiple card 53 Setup error password lockdown 83 Setup Group 37 Modify multiple cards grou p data 54 Setup alarm source 84 Setup Weekly Group schedule 38 Modify multiple cards grou p status 55 Setup alarm enabled 85 Setup Holiday access limit 56 Setup doorbell enabled 41 Modify Master card password 57 Setup extend module 91 Setup controller ID
* Please see the reader display list for more particular system light description.
1.2 Reader LED status list
Show light & sound Footnote
code Status description
OK LED (SY120SA)
Power LED (SY120SA)
Error LED (error)
BEEPER (voice)
0 Normal status off LED Red LED Orange no action
1 Correct status LED Green LED Red off short beep(0.5sec) Return to original status
2 Error status off LED Red LED Orange 2 short beep Return to original status
3 Armed status off LED Red twinkling long beep(2sec) Work until remove guard
4 Login status off twinkling off long beep(1sec) Work until login out
5 Alarm status off LED Red twinkling keep rapid beep Work until remove guard
6 Finishing setting status LED Green LED Red off long beep(1sec) Return to original status
7 Activate alarm delay status twinkling LED Red off keep short beep Work until finish guard
8 Waiting input status twinkling LED Red off short beep(0.5sec) Work until finish guard or delay
9 Lockdown status twinkling LED Red twinkling No action Return to original status
*Keep waiting 30secs to response card & password, if delay or push enter and system will login out. *After 2 mins the system will login out when login and no any keypad enter action.
SY120SA Series Operating Manual
© 2004 by SYRIS Technology Corp.
3
2 Operating manual
2.1 Access with Prox. card
2.1.1 Prox. card enter
1. Present Prox card to reader; waiting for confirmation from controller.
2. If the card is valid, system will open the door automaticaly.
3. If the card is invalid, system will show error message.
2.1.2 Access with Prox. card and password
1. Present card to reader and wait for confirmation from controller.
2. If card is valid, the controller will wait for password and stop reading function until the password has inserted and push [EN]. If the password is correct the controller will show correct message, and the door will be opened automaticaly.; Password range: 0000 – 9999
3. If the card is invalid or error password, the system will show error message.
2.1.3 Access with Prox. Card and Anti-duress (with anti-duress output)
1. Present card to reader and wait for confirmation from controller.
2. If card is valid then reader will wait for password entered and stop reading function until password had been confirmed. After varified password is correct anti-anti-duress, on the controller will show correct LED message and will open the door automatically. If anti-druess mode had been activated, the controller will has anti-duress action at same time.
3. If invalid card or wrong password and system will response error message.
2.2 Access without Prox. card.
2.2.1 Access with card’s password or card number and card password
1. Enter (pppp)[EN], system will confirm correct or error, if correct will response correct status
and control open automatic.
(pppp):card password; default value :0000
* Enter password to open Æ please see 2.9.1 detail
2. Enter(NNNN)(pppp)[EN], and wait for confirmation from controller,
if correct will response correct message and the door will open automatically.
(NNNN):valid card number: 0001~2000
(pppp): Card’s password; default: 0000
2.2.2 Access with card number and anti-duress password
1. Enter (NNNN)(pppp) [EN], and wait for confirmation from controller, if correct will back to normal ststus and anti-duress alarm will be initiated automatically.
(NNNN): valid card number are in the range between 0001~2000 (pppp): anti-duress password (The password is four digit)
* If anti-duress password & personal password are the same, the personal password will be the first priority to be checked and the alarm won’t be triggered.