Syrelec, Brand of Crouzet Control NRU SERIES Data Sheet

CONTROLS CONTROLS
Products and specifications subject to change without notice.
Order/Technical Support – Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com
2/74
NRU SERIES
LIQUID LEVEL CONTROL PUMP UP
UL listed CSA recognized
Three Styles
Pump Up Control
4.7 kto 100 kSensitivity
10 Amp SPDT Relay
SPECIFICATIONS:
Input Power . . . . . . . . . . . . . . .24, 48, 110, 220 VAC, ±15% (50/60 Hz)
Maximum voltage . . . . . . . . . . .24 VAC: 1.5 VA
48 VAC: 1.7 VA 110 VAC: 2 VA 220 VAC: 2 VA
Output . . . . . . . . . . . . . . . . . . .SPDT Relay
Contact material . . . . . . . . . . .AgCdO
Maximum loading . . . . . . . . . .10A AC resistive 8A DC resistive
Maximum switching voltage . .250 VAC 80 VDC
Maximum power rating . . . . . .2500 VA 80 W
Electrical life . . . . . . . . . . . . . .2 x 105at 2200 VA resistive load
Mechanical life . . . . . . . . . . . . .3 x 107operations
Probe isolation . . . . . . . . . . . . .Electrodes: 2000 VAC
Probe sensitivity . . . . . . . . . . .4.7 K to 100 K ohms
Probe voltage . . . . . . . . . . . . . .24 VAC, 60 Hz
Probe current . . . . . . . . . . . . . .2 mA max.
Operating temperature . . . . . .+14°F to +140°F -10°C to +60°C
Weight . . . . . . . . . . . . . . . . . . .7 oz. (200g)
Note: The cable for probes (max 300ft) should be run in separate conduit. A
shielded cable is recommended.
MOUNTING
D = DIN-rail mounting L = 11 pin plug-in P = 8 pin plug-in
SERIES
NRU
P
MOUNTING
NRU
SERIES
220D
INPUT POWER
INPUT POWER
24A = 24VAC 48A = 48VAC 110A = 110VAC 220A = 220VAC
WIRING DIAGRAM:
ORDERING INFORMATION:
Control of conductive liquids (tap water, sea water, sewage, chemical solutions, coffee, ice cream, etc.)
The relay is energized when the level falls below the low level probe. It de-energizes when the high level probe is reached. The NRU will also control a single level. In this case, a single probe is used and the relay operates when the probe is not immersed. The Max terminal is connected to common with a jumper.
In either case, a common electrode is needed if the container is non-conductive.
S
Max
min
LEVEL
R
S
LEVEL
R
t0
PNRU
SSS
min min
7
8
9
10
3
2
45
1
8
6
7
˜
˜
DNRU
A1
12 14
LNRU
Max C C Max
min Max
11
C
R
A2
6
5
4
3
RR
2
1
11
Loading...