![](/html/e3/e37f/e37ff89e893050de507b6006ddc8a01420866701d7931b167a11dc35324fdaca/bg1.png)
Plug-in Mount 39 mm L2N Part number 84870403
Relay for controlling level of conductive liquids
Output relay status display LED
Sensitivity adjustable from 5 kΩto 100 kΩ
LN
Relay for controlling level of conductive liquids
Regulation of two levels : minimum, maximum
Empty function
Plug in (8 or 11 pins)
Sensitivity adjustable from 5 kΩto 100 kΩ
LN2
Combined fill and empty functions
Combined regulation of pumping out a well and filling a tank
Plug in (11 pins)
Part numbers
Specifications
Operating principle
Control of maximum and/or minimum levels of conductive liquids (tap water, sea water, waste water, chemical solutions, coffee etc).
The principle is based on measurement of the apparent resistance of the liquid between two submerged probes. When this value is lower than the preset threshold on the unit front face, the output
230 V, 110 V, 48 V, 24 V AC, 50/60 Hz
Measurement accuracy (at maximum sensitivity)
Electrode current (maximum)
10 nF Response time high level
Output relay (according to AC1 resistive load)
1 AgCdO switch 8 A AC max.
Galvanic isolation via transformer (4 kV, 8 mm creepage
distance)
Isolation of contacts and electrodes from power supply
Temperature limits use (°C)
Temperature limits stored (°C)
20/10/2014 www.crouzet.com
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
![](/html/e3/e37f/e37ff89e893050de507b6006ddc8a01420866701d7931b167a11dc35324fdaca/bg2.png)
relay changes state. To avoid electrolytic phenomena, an AC current funs across the probes. Applications found in environmental, chemical industries and food technology etc.
Combined Fill / Empty function
The output relay changes state when the level of liquid in the tank reaches the "max" electrode, with the "min" electrode submerged. It returns to its initial state when the "min" sensor is no longer in
contact with the liquid.
When the level of liquid in the well reaches the "min" electrode, the pump stops.
If, on power-up or after a power break, the "max" electrode in the tank is above the surface, reset the device by pressing the PB pushbutton.
Note
The probe wire (max length 100 metres) does not have to be screened, but avoid mounting it in parallel with the power supply wires. A screened wire can be used, with the screening connected
to the common.
TRADOS Empty Field
LN2 : connector sockets
8-pin : 25 622 129
11-pin : 25 622 078
20/10/2014 www.crouzet.com
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected