DESCRIPTION
LAMPS CONTAIN MERCURY. DISPOSE ACCORDING
The SSF Series is a functional and multi-purpose standard strip family
that incorporates premium performance and construction durability.
Designed with our easy-to-use Flip-Up socket design, the SSF
significantly reduces installation time. The performance and application
versatility of this series can be increased by incorporating symmetrical
or asymmetrical reflectors. The SSF Series can be installed using various
mounting methods and numerous options and accessories are available.
SPECIFICATION FEATURES
Construction
Channel die cold rolled steel
with numerous KOs for ease of
installation. Groove for Tong
Hanger. End plate quickly converts
to snap-in channel connector for
Electrical*
Ballasts are CBM/ETL Class "P" and
are positively secured by mounting
bolts. Rotor Lock lampholders.
UL/CUL listed. Suitable for damp
locations.
continuous row alignment. Lamp
holder bracket flips in place.
Channel/wireway cover secured
with quarter-turn fasteners.
Finish
Multistage iron phosphate
pretreatment ensures maximum
bonding and rust inhibitor. Lighting
Channel/Wireway Cover
Die formed heavy gauge steel.
Tight fit for ease of maintenance.
upgrade, baked white enamel
finish. Prepainted material is
standard, PAF optional.
Easily removed without use of
tools. Optional reflector available
incorporating silver technology
enhancements (Silver Lining).
Consult Pre Sales Technical
Support.
Application
The SSF Series can be the
illumination solution in
commercial, industrial, retail and
residential applications. Fixtures
can be used in storage/utility areas,
coves, display cases, shops, task
and general area lighting.
3-5/8"
[93mm]
2', 3' OR 4' STRIP
1, 2 OR 3 T8 LAMPS
Standard Striplite
LAMP CONFIGURATIONS
1 LAMP
3-5/8"
[93mm]
4-1/4"
[108mm]
8'
Y=5"
[127mm]
[108mm]
X=3-1/4"
[83mm]
Y
4-1/4"
2 LAMP
3-5/8"
[93mm]
Ceiling Stand-Off
Embossments
11/16" x 1" KO (2 Places)
2-5/8"
[67mm]
4-1/4"
[108mm]
4-1/4"
[108mm]
MOUNTING DATA
Y=5"
[127mm]
4-1/4"
[108mm]
X=3-1/2"
[89mm]
2" [51mm] K.O.
96" [2438mm]
4'
Y
11 /16" x 1"
KO (2 Places)
X
24-1/2" [622mm]
Y=5"
[127mm]
4-1/4"
[108mm]
X=3-1/2"
[89mm]
Ceiling Stand-Off
Embossments
Ground Screw
[108mm]
3'
Y
11 /16" x 1"
KO (2 Places)
Y=5"
[127mm]
4-1/4"
X=3-1/2"
[89mm]
Ceiling Stand-Off
Embossments
Ground Screw
2"
[51mm]
KO
2'
Y
11 /16" x 1"
KO (2 Places)
Ground Screw
2"
[51mm]
10" [254mm]
KO
X
48" [1220mm]
11 /16" [17mm] K.O. (2)
Ceiling Stand-Off
Embossments
Hole for Toggle
Ground Screw
X
24" [609mm]
Hole for
Toggle
X
36" [914mm]
Hole for
Toggle
Hole for Toggle
7/8" [22mm]
K.O. (2)
3-1/4"
[83mm]
7/8" [22mm]
K.O. (4)
3-1/4"
[83mm]
7/8" [22mm]
K.O. (3)
3-1/4"
[83mm]
7/8" [22mm]
K.O. (3)
3-1/4"
[83mm]
4-5/8"
[118mm]
ENERGY DATA
Input Watts:
EB Ballasts Normal Ballast Factor
117 (20), 217 (34), 125 (23), 225 (53),
128T8 (25), 228T8 (49), 328T8 (71),
132 (28), 232 (58), 332 (80)
EB Ballasts Low Ballast Factor
125 (21), 225 (40), 128T8 (22),
228T8 (44), 328T8 (64), 132 (25),
232 (48), 332 (72)
Luminaire Efficacy Rating
LER = FS-88
Catalog Number: SSF-232
Yearly Cost of 1000 lumens,
3000 hrs at .08 KWH = $2.73
*Reference the lamp/ballast data in the
Technical Section for specific lamp/ballast
requirements.
TO LOCAL, STATE OR FEDERAL LAWS
Safe and convenient means of
disconnecting power.

PHOTOMETRICS
Electronic Ballast
F28T8-SP35-UMXECO Lamps
2750 Lumens
Spacing criterion:
(II) 1.3 x mounting
height, (⊥) 1. 5 x
mounting height
Efficiency 86.2%
Test Report:
SS232.IES
LER = FS95
Yearly Cost of 1000
lumens, 3000 hrs at
.08 KWH = $2.53
Angle Along II 45° Across ⊥
0
929 929 929
5
927 928 927
10
916 925 928
15
896 914 927
20
869 899 936
25
834 888 945
30
792 876 949
35
742 860 946
40
687 837 934
45
627 808 915
50
561 771 889
55
492 727 866
60
418 675 845
65
340 632 818
70
261 598 775
75
181 554 674
80
106 443 568
85
41 340 453
90
5 234 349
Coefficients of U tilization
Effective floor cavity reflectance 20%
rc 80%70% 50% 30% 10
rw 70 50 30 10 70 50 30 10 50 30 10 50 30 10 50 30 10 0
RCR
99 99 99 99 95 95 95 95 88 88 88 81 81 81 75 75 75 73
0
88 83 78 74 84 79 75 71 73 69 66 67 64 62 62 60 58 55
1
79 70 63 57 75 67 61 56 62 57 52 57 53 49 52 49 46 43
2
71 61 53 46 67 58 51 45 53 47 42 49 44 40 45 41 37 35
3
64 53 45 38 61 51 43 37 47 40 35 43 38 33 40 35 31 29
4
59 47 38 32 56 45 37 31 42 35 30 38 33 28 35 31 27 24
5
54 42 34 28 51 40 33 27 37 31 26 34 29 24 32 27 23 21
6
50 38 30 24 48 36 29 23 34 27 22 31 26 21 29 24 20 18
7
46 34 26 21 44 33 26 21 31 24 20 28 23 19 26 22 18 16
8
43 31 24 19 41 30 23 18 28 22 18 26 21 17 24 20 16 14
9
40 29 22 17 39 28 21 17 26 20 16 24 19 15 23 18 14 13
10
Zonal Lumen Summary
Zone Lumens %Lamp %Fixture
758 13.8 16.0
0-30
1291 23.5 27.2
0-40
2533 46.1 53.5
0-60
3988 72.5 84.2
0-90
751 13.6 15.8
90-180
4739 86.2 100.0
0-180
ORDERING INFORMATION
Electronic Ballast
FO32T8 Lamps
2900 Lumens
⊥
Spacing criterion:
(II) 1. 3 x mounting
height, (⊥) 1. 6 x
||
mounting height
Efficiency 91.6%
Test Report:
SS232.IES
LER = FS-88
Yearly Cost of 1000
lumens, 3000 hrs at
.08 KWH = $2.73
AngleAlong II 45°Across ⊥
0
1017101
5
1007 1010 1021
10
949 985 1030
15
857 951 1042
20
738 906 1029
25
588 830 978
30
422 727 920
35
252 632 834
40
104456 601
45
50
55
60
65
70
75
80
85
90
0253 393
0320 518
0246 430
0199 353
0131 263
06
01
01 7
00 0
00 0
017
67
6
Coefficients of Utilization
%
Effective floor cavity reflectance 20%
rc 80%70% 50%30% 10
rw 70 50 30 10 70 50 30 10 50 30 10 50 30 10 50 30 10 0
RCR
105105 105105 100100 100100 92 92 92 84 84 84 77 77 77 74
0
93 87 83 78 88 84 79 75 76 73 70 70 67 64 64 61 59 56
1
83 74 67 61 79 71 65 59 65 60 55 59 55 51 54 51 47 44
2
75 64 56 49 71 62 54 48 56 50 45 51 46 42 47 42 39 36
3
68 56 48 41 65 54 46 40 49 43 37 45 39 35 41 36 32 30
4
62 50 41 35 59 48 40 34 44 37 32 40 34 30 37 32 28 25
5
57 44 36 30 54 43 35 29 39 32 27 36 30 26 33 28 24 22
6
53 40 32 26 50 38 31 25 35 29 24 33 27 22 30 25 21 19
7
49 36 28 23 47 35 27 22 32 26 21 30 24 20 27 22 19 17
8
46 33 25 20 44 32 25 20 30 23 19 27 22 18 25 20 17 15
9
43 30 23 18 41 29 22 18 27 21 17 25 20 16 23 18 15 13
10
%
Zonal Lumen Summary
Zone Lumens %Lamp %Fixture
0-30
0-40
0-60
0-90
90-180
0-180
83014.315.6
1411 24.3 26.6
2753 47.5 51.8
4288 73.9 80.7
1023 17.6 19.3
5311 91.6 10 0.0
Tandem
Blank=2', 3' or
4' Length
8T=8' Length
Series
SSF=Commercial
Standard Striplite
Number of Lamps
(Not Included)
1=1 Lamp
2=2 Lamps
3=3 Lamps
Wattage
17=17W T8 (24")
25=25W T8 (36")
28T8=28W T8 (48")
32=32W T8 (48")
(1)
(2)
Options
GL=Single Element Fuse
GM=Double Element Fuse
EL4=Emergency Installed
(7)
(2)
Voltage
120V=120 Volt
277V=277 Volt
347V=347 Volt
UNV=Universal
Voltage 120-277
(Order Separately)
A1B/Spacer-U=Spacer 1-1/2" to 2-1/2" from ceiling (Use 2
Per Fixture)
GRP-SSF=Gripper Hanger (Use 2 Per Fixture)
AYC-Chain/Set=36" Chain Hanger (Use 1 Set Per Fixture)
SCF=Fixed Stem Set (Specify Length)
SCS=Swivel Stem Set (Specify Length)
SCA=Adjustable 48" Stem Set
CLC-SSF=Long Channel Connector SSF
SSF-ASY-4
SSF-REV-4
2', 3', or 4')
SSF-SYM-4
(3)
=3" Asymmetric Reflector (Specify 2', 3', or 4')
(3)
=3" Asymmetric Reverse Reflector SSF (Specify
(3)
=6" Symmetric Reflector Specify (2', 3' or 4')
ICF-4FT-REFL=12" Symmetric Reflector
WG/SSF-2FT=2' Wire Guard
WG/SSF-3FT=3' Wire Guard
WG/SSF-4FT=4' Wire Guard
TOGGLE=Single Toggle NO. 2 (Specify Length)
Y- TOGGLE=Y Toggle NO. 2 (Specify Length)
(Additional Accessories Available. See Options and Accessories
Section.)
Ballast Ty pe
EB8 =T8 Electronic Instant Start.
(4)(5)
Total Harmonic Distortion < 10%
No. of Ballast
1 or 2
/PLUS=T8 Electronic Instant Start.
EB8
No. of
Ballast
1 or 2
=T8 Electronic Program Rapid Start.
ER8
Total Harmonic Distortion < 10%
No. of Ballast
1 or 2
/PLUS=T8 Electronic Program Start.
ER8
No. of
Ballast
1 or 2
HPT8 Ballast
L=T8 Electronic Instant Start. Low Ballast Factor .77
HB8
=T8 Electronic Instant Start. Ballast Factor .88
HB8
N=T8 Electronic Instant Start. Normal Ballast Factor 1.0
HB8
H=T8 Electronic Instant Start. High Ballast Factor 1.15-1.2
HB8
DIM=T8 Electronic Program Start Step Dimming. Ballast Factor .88
HR8
L=T8 Electronic Program Start. Low Ballast Factor .77 max.
HR8
=T8 Electronic Program Start. Ballast Factor .88
HR8
H=T8 Electronic Program Start. High Ballast Factor 1. 15-1.2
HR8
(2)
High Ballast Factor >1.13.
Total Harmonic Distortion < 10%
High Ballast Factor >1.13.
Total Harmonic Distortion < 10%
Options
6-3/18 SJT-C&P-515P=
Cord & Plug (120V)
(6)
(15 AMP)
6-3/18 SJT-C&P-L715P=Cord
& Plug (277V) (15 AMP)
PI/CPI=Plug-In Option
TILW=Tandem In-Line Wiring
Option (Consult TILW Option
Catalog Page)
Packaging
U=Unit Pack
4B=4 Bulk Packing (48" and 96")
(6)
(6)
(6)