Symmons Temptrol 262BODY, Temptrol 261XBODY, Temptrol RTS-076, Temptrol 262XBODY Installation Instructions Manual

Page 1
Temptrol® Pressure Balancing Valve
Installation Instructions
262BODY (4 PORT)
262XBODY
261XBODY
(3 PORT, SERVICE STOPS)
RTS-076
(BRACKET)
COMPLIANCE
-ASME A112.18.1/CSA B125.1
-ASSE 1016
-Buy American Act Compliant
IMPORTANT / FOR INSTALLER
WARNING:
As the installer of this valve, you must first carefully read and understand the material covered in this manual before
installing and adjusting this valve per instructions. Failure to do so may compromise the installation, operation and/or
serviceability of this valve.
Do not install positive shut-o devices on the outlet of this valve, or devices that do not allow the valve to flow at
least 1.5 GPM at 45 psi inlet pressure. Exception: If a self-closing or slow-closing valve is installed on the outlet, the
supplies of the valve must be equipped with checks to eliminate hot to cold bypass in the event the valve’s handle is
not turned o after use.
When installing this valve, failure to adjust limit stop screw properly may result in serious scalding.
LIFETIME LIMITED WARRANTY
All warranty claims MUST be pre-approved by Symmons.
All parts and finishes of the Symmons products are warranted to the original consumer purchaser to be free from manufacturing defects in material and workmanship for 5 years Non-Residential or Commercial Applications. Symmons warrants to the original consumer purchaser/ end-user that any Symmons product will be free of defects in material and workmanship during normal domestic use for the life of your home.
Symmons recommends using a professional plumber for all installation and repair. During the warranty period, Symmons at its sole option, will provide replacement part(s) or product (or, if no longer available, a comparable product) to replace those which have proven defective in materials or workmanship under normal installation, use and service, FREE OF CHARGE for the time period of 5 years from the date of purchase. (BATTERIES NOT INCLUDED)
This warranty is extensive in that it covers replacement of all defective parts and even finish, but these are the only two things that are covered. Damage due to installation error, product abuse, product misuse, or use of cleaners containing abrasives, alcohols, or other organic solvents, whether performed by a contractor, Service Company or yourself are excluded from this warranty. Symmons will not be responsible for labor charges and/or damage incurred in installation or repair or replacement, nor for any indirect, incidental or consequential damages, losses, injury or costs of any nature relating to the bathing products. Except provided by law, this warranty is in
lieu of and excluded all other warranties, conditions and guarantees, whether expressed or otherwise, including without restriction those of merchantability or of fitness for use.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation of exclusion may not apply to you. This warranty gives you specific legal rights, and you also may have other rights which vary from state to state. This warranty is not transferable. This warranty does not cover damage or defects relating to misuse, abuse, negligence, normal wear and tear, accident, acts of God, repairs or alterations not authorized in writing by Symmons, or improper installation, storage or handling.
The above mentioned warranty information includes each product that falls under the following: Symmons Bathing Products Warranty- Non-Residential or Commercial Applications; Symmons Non-Electronic Lifetime Faucet and Finish Limited Warranty Non-Residential or Commercial Applications; Symmons Electronic Faucet Limited Warranty - Non-Residential, Commercial and Residential Applications; Symmons Bathing Products Warranty- Residential Application Symmons Non­Electronic Lifetime Faucet and Finish Limited Warranty Residential Application
If you have any questions regarding technical support, installation or concerns regarding our warranty plan, please email us at GetHelp@symmons.com or call us at: 1-800-796-6667.
ZV-3247 REV B
Page 2
1. RECOMMENDED TOOLS
FIGURE 1
Phillips Screwdriver Flathead Screwdriver
Adjustable Wrench
Safety Glasses Thread Seal Tape Measuring Tape
Torch
Solder
Pipe Cutter
Drywall Saw
(IPS Only)
Pipe Wrench
(CPVC Only)
CPVC Cement
(PEX Only)
PEX Crimping Tool
(PEX Only)
PEX Cold Expansion Tool
Level
Drill
(ProPress Only)
ProPress Tool
Copper, IPS, CPVC, PEX (Crimp) & PEX (Cold Expansion)
2. MOUNTING BRACKET INSTALLATION
2.1 Metal Straps
Mounting bracket is used to secure valve between wall studs up to 24 inches, center to center.
1. Place metal straps (x4) over screws. Screws will come preassembled to bracket.
2. Pull metal straps tight against bracket ears. Screws will protrude through small screw hole in metal straps.
3. Drive screws into bracket to secure straps.
Use caution not to strip screws.
FIGURE 2.1
2.2 Install Bracket
FIGURE 2.3
FIGURE 2.4
ZV-3247 REV B
NOTE: Valve will come preassembled to mounting bracket unless specified otherwise.
FIGURE 2.2
Mounting bracket will locate valve body in wall cavity at appropriate depth (valve body rough-in is not required).
1. Confirm valve body and mounting
2. Bend excess strap around wood studs.
3. Drive (4x) wood screws, at inward angle,
NOTE: If not using mounting bracket, see STEP 5.1 for stringer mounts installation.
2
bracket are level. Drive (x4) wood screws through metal straps into wood studs (see FIGURE 2.2)
(see FIGURE 2.3)
through metal straps into sides of wood studs (see FIGURE 2.4). Installing wood screws at inward angle will pull metal straps tight against wood studs.
Page 3
3.1 Tub/Shower Systems
FIGURE 3.1
77"
(1956mm)
12"
32"
(813mm)
(305mm)
INSTALL
BRACING
INSTALL BRACING
3. DIMENSIONS AND MEASUREMENTS
Valve should be positioned 32 inches above the tub basin floor. Shower arm should be 77 inches above the tub basin floor. Tub spout should be positioned approximately 12 inches below the valve.
IMPORTANT: The design of this valve requires a rigid copper tubing connection between the tub port and the tub spout with no more than one (1) 90 degree bend allowed. Failure to do so, or to substitute PEX, CPVC, or any other connection type or outlet accessory such as a hand or body-spray, other than the Symmons tub spout provided, may result in excessive backpressure through the system, and compromise operation.
When valve is used in shower only or tub spout only installation, apply plumber tape to outlet that will not be used and install the enclosed cap to that outlet (see FIGURE 3.2).
FIGURE 3.2
FLOOR
3.2 Shower Systems
FIGURE 3.3
77"
(1956mm)
42"
(1067mm)
FLOOR
INSTALL BRACING
CAP
1/2-14 NPT
Valve should be positioned 42 inches above the tub basin floor. Shower arm should be 77 inches above the tub basin floor.
NOTE: For ADA compliance (Americans with Disabilities Act) consult your local municipality for proper product choice and mounting locations.
3
ZV-3247 REV B
Page 4
4. DETERMINE WALL TYPE
4.1 T-176 Protective Shield 4.2 T-177 Valve Mounting Plate
FIGURE 4.1
-
F
I
N
T
I
N
S
A
H
T
E
R
D
O
P
M
I
E
C
A
F
R
U
S
S
I
H
T
W
A
L
L
M
U
S
T
B
E
F
L
U
F
S
O
H
M
W
O
I
T
T
H
T
O
B
FIGURE 4.2
Without service stops
With service stops
4.3 Drywall or Other Type Wall
FIGURE 4.3
1/2" (13 mm) or greater
protective shield
Wall Cutout Hole Size
3-1/2" (89 mm) min
4" (102 mm) max
finished wall
shower supply
Rough-in
± 1/2"
2-3/8" (60 mm ± 13 mm) pipe centerline to front of finished wall
hot & cold supply inlets
tub spout supply
Protective shield (T-176) is required for drywall, plaster or other type walls with:
• 1/2 inch (13 mm) or greater wall thickness
1. Attach protective shield by snap fitting over end of valve spindle to protect valve during wall construction.
2. Finished wall must be flush with back side of protective shield surface.
4.4 Thin Wall Installation
FIGURE 4.4
1/16" (2 mm) min
1/2" (13 mm) max
valve mounting plate
Wall Cutout Hole Size
3-1/2" (89 mm) min
4" (102 mm) max
finished wall
shower supply
Rough-in
± 1/2"
2-3/8" (60 mm ± 13 mm) pipe centerline to front of finished wall
hot & cold supply inlets
tub spout supply
Valve mounting plate (T-177) is required for fiberglass or acrylic walls, and optional for plaster or other type walls with:
• Minimum 1/16 inch (2 mm) wall thickness
• Maximum 1/2 inch (13 mm) wall thickness
1. Seat mounting plate against valve (see FIGURE 4.2 for orientation).
2. Valve mounting plate must be flush with inner wall.
4.5 Alternative Rough-ins
FIGURE 4.5
2" (51 mm)
Trim Series ± Tolerance
Oxford
Canterbury
Carrington
Temp Com
± 1/4" (± 6 mm) ± 1/2" (± 13 mm) ± 1/2" (± 13 mm) ± 1/2" (± 13 mm)
ZV-3247 REV B
Rough-in
± see table pipe centerline to finished wall
finished wall
When installing valve used with any of the shower or tub/shower trims shown below, reference rough-in dimensions as shown in FIGURE 4.5 instead of standard valve rough-in:
Oxford
Canterbury
Temptrol
Carrington
Commercial
4
Page 5
5. VALVE BODY INSTALLATION
5.1 Stringer Mounts
Stringer mounts are used to secure valve body to wood blocking for valve bodies without mounting bracket. (see FIGURE 5.1).
For valve body installation with mounting bracket see STEPS 2.1 & 2.2.
stringer mount
FIGURE 5.1
stringer mountwood blocking
wall stud
5.2 Install Piping/Fittings (Bracket Removed for Clarity)
FIGURE 5.2
HOT
INLET
SHOWERHEAD OUTLET
TUB SPOUT OUTLET
COLD INLET
1. Install valve as specified in FIGURES 4.3 - 4.5, per application.
2. Pipe from outlet port on the valve marked S to showerhead mounting arm location.
3. Connect hot water supply to valve inlet marked H and cold water supply to valve inlet marked C.
4. Pipe from outlet port on valve marked T to tub spout (262BODY & 262XBODY only).
5. Remove protective shield snap fitted over the end of valve flow control spindle once valve is securely installed and wall finish work has been completed.
5.3 Adjust Valve Packing Nut
FIGURE 5.3
temperature
limit stop screw
packing nut
1. Turn hot and cold supplies on. Valve will not operate unless both hot and cold water supply pressures are on.
2. Place handle over flow control spindle.
3. Tighten packing nut for positive frictional resistance as handle is rotated from shut-o position across adjustment range.
control spindle
finished wall
5.4 Flush System
1. Turn valve to the warm position and run for a few minutes.
2. If system is dirty, remove TA-10 flow control spindle in center of valve to ensure proper flushing (see STEP 8.1).
3. Check for leaks around valve assembly and all pipe fittings.
5.5 Set Temperature Limit Stop Screw
The temperature limit stop screw limits valve handle from being turned to maximum position resulting in excessive hot water discharge temperatures.
WARNING: Failure to adjust temperature limit stop screw properly may result in serious scalding.
1. Place handle on flow control spindle and open valve to maximum desired temperature.
2. Turn limit stop screw clockwise until it seats (see FIGURE 5.3).
5
ZV-3247 REV B
Page 6
6. BACK TO BACK INSTALLATION
6.1 Back to Back Wall Type
FIGURE 6.1
ROUGH-IN
± 1/2"
2-3/8"
(60 mm ± 13 mm)
STANDARD
VALVE
5-1/2"
(140 mm) MIN. WALL THICKNESS
REVERSE SEAT VALVE
COLD
6.2 Identify Reverse Seat Valve
FIGURE 6.2
1. To simplify piping on back to back installations use one standard valve (hot on left, cold on right) and one reverse seat valve (hot on right, cold on left) as shown in FIGURE 6.1.
NOTE: Back to back installations require 5-1/2" (140 mm) minimum wall thickness for proper installation, with or without bracket.
1. Locate the "R" stamp on bottom side of the valve casting to identify reverse seat valve as shown in FIGURE 6.2.
R
REVERSE SEAT VALVE,
R
T
BOTTOM SIDE
6.3 Install Piping/Fittings (Bracket Removed for Clarity)
FIGURE 6.3
HOT
HOT
STANDARD VALVE
REVERSE
SEAT
VALVE
C
H
H
C
COLD
COLD
1. Inlet marked H on standard valve should be plumbed to inlet marked C on reverse seat valve. Inlet marked C on standard valve should be plumbed to inlet marked H on reverse seat valve (see FIGURE 6.3).
2. Follow STEPS 5.3 - 5.5 to complete installation of valve bodies.
ZV-3247 REV B
6
Page 7
7. VALVE BODY TEST CAP (162BODY, 162XBODY, 161XBODY)
7.1 Install Valve Body with Test Cap
FIGURE 7
valve body test cap
Test cap will come installed to valve to allow pressurization of system. Do not remove test cap from valve during wall construction, installation of valve or pressurization of system.
WARNINGS:
1. Do not expose valve with test cap to heat for longer than 2 minutes when soldering copper tubing. Doing so may damage the internal components of the valve and will void the product warranty.
2. Ensure test cap is tightened securely after soldering valve body.
To install valve body with test cap, follow instructions outlined in STEP 5.2.
7.2 Preparing Valve Body with Test Cap for Trim
TA-10 flow control spindle will be included with shower and tub/shower trim. When ready to install trim to valve:
3. Check for leaks around the valve assembly and all pipe fittings.
4. Remove test cap from valve.
5. If system is dirty, flush valve.
6. Install flow control spindle and cap assembly to valve (see STEP 8.5).
7. Adjust packing nut and set temperature limit stop screw (see STEPS 5.3 & 5.5).
7
ZV-3247 REV B
Page 8
8. SERVICE INSTRUCTIONS
8.1 Removing Flow Control Spindle
Reference parts breakdown (see FIGURE 9.1). See trim manual for trim removal instructions.
1. Shut o water supply to valve. Turn valve’s TA-10 flow control spindle to open position using trim handle.
2. Remove trim handle and dome cover.
3. Remove escutcheon plate by first removing escutcheon screws.
4. Unscrew both T-12A cap assembly and flow control spindle together.
8.2 Hot/Cold Seat Repair Kit
Service requires TA-4 hot and cold seats and T-35C removal tools.
1. Remove flow control spindle (see STEP 8.1).
2. Remove both seats with removal tools, turning counterclockwise.
3. Replace both seats even if only one appears worn.
4. Install and tighten both seats to 15 foot pounds of torque, turning clockwise.
8.3 Flow Control Spindle Washer Repair Kit
Service requires TA-9 washer repair kit.
1. Remove flow control spindle (see STEP 8.1).
2. Remove cold washer by holding flow control spindle using trim handle and unscrew cold washer retainer using channel lock pliers, turning counterclockwise.
3. Remove hot washer by removing hot washer screw.
8.4 Checking Water Pressure Balancing Piston
The perforated end of the flow control spindle houses the water pressure-balancing piston.
1. Remove flow control spindle (see STEP 8.1).
2. Shake flow control spindle and listen for clicking noise. Piston should be free to slide back and forth the full length of its travel.
3. If piston appears restricted then do the following: a) tap the handle, or the stem end of flow control spindle, against a solid object to free the piston, or b) try soaking in household vinegar and repeat tapping handle or stem of flow control spindle.
4. If unable to free piston, replace flow control spindle.
8.5 Valve Reassembly
Reassemble valve, reversing the procedure in STEP 8.1. Be sure flow control spindle is drawn close to the cap before screwing cap assembly back into valve.
ZV-3247 REV B
8
Page 9
FIGURE 9.1
COMMON PLANE VALVE BODY
262XBODY (PICTURED) 262BODY 261XBODY
LARGE
WASHER
PACKING
PACKING NUT
FLOW CONTROL
SPINDLE
O-RING
WASHER KIT
TA- 9
LIMIT STOP
SCREW
SMALL
WASHER
COLD
WASHER
RETAINER
COLD
WASHER
REVERSE SEAT KIT
T-108
CAP
SPINDLE ASSEMBLY
TA-1 0
WASHER
SCREW
HOT
WASHER
CHECK STOP ASSEMBLY
T-57A-KIT
REPAIR TOOL ASSEMBLY
T35C
GASKET
HOT
STOP
SPINDLE
CAP
9. PARTS BREAKDOWN
CAP ASSEMBLY
T-12A
CAP
SEAT KIT
TA- 4
HOT
SEAT
COLD
STOP SPINDLE
SEAT
ASSEMBLY
T-5 2
STOP
SPINDLE
STOP
SPINDLE
CAP
CHECK
SPRING
STOP
SPINDLE
NOTE:
NEW CHECK STOP SPINDLE SHALL FEATURE CHAMFER AND SHALL BE PLATED TO DISTINGUISH FROM T-52.
NOTE:
USE CAP WHEN VALVE IS USED IN SHOWER ONLY OR TUB SPOUT ONLY APPLICATIONS.
CHECK
FOR
STOP SPINDLE
CAP
FOR
LEGACY
HOT SEAT
CAP ADAPTER KIT
T45KIT
FOR
LEGACY
COLD SEAT
REVERSE
SEAT
TOOL
FOR DIVERTER RETAINER
9
FOR
HOT SEAT
FOR
COLD SEAT
LOCKING
PIN
ZV-3247 REV B
Page 10
9. PARTS BREAKDOWN
FIGURE 9.2
VALVE BODY FITTING MODIFICATIONS
(2x) PEX CRIMP
RTSPEXCR
MOUNTING BRACKET COMPONENTS
(2X) PROPRESS
RTSPFIT
TEST CAP
RTSTC1
(2x) PEX COLD EXPANSION
RTSPEXCE
(4X) BRACKET STRAPS
RTS-077
(2X) CPVC
RTSCPVC
ZV-3247 REV B
(2X) VALVE TO BRACKET SCREWS
RTS-078
(8X) STRAP TO BRACKET SCREWS
RTS-079
BRACKET STRAPS & BRACKET
RTS-076
10
Page 11
10. TROUBLESHOOTING CHART
PROBLEM CAUSE SOLUTION
Valve will not pass water. Both hot and cold water supplies
are not turned on.
Valve leaks when shut o. Hot and cold washers are worn
or foreign matter (dirt, chips) is lodged between washers and seat surfaces.
Temperature control handle is turned from cold to hot (or hot back to cold) and volume from spout or head is not constant.
Valve delivers sucient quantity of cold, but little hot, or the reverse.
Temperature varies without moving handle.
Valve delivery temperature reduces gradually during use; handle must be turned to hotter positions to maintain constant temperature.
Valve delivers hot water when initially opened. Water turns colder as handle is rotated in a counterclockwise direction toward the hot position.
Pressure-balancing piston housed in spindle assembly is restricted from free movement by foreign matter.
Same as above. Same as above.
Same as above. Same as above.
Overdraw on hot water supply (i.e. running out of hot water).
Valve is piped incorrectly (i.e. the hot supply is piped to the valve’s cold inlet and the cold supply is piped to the hot inlet.)
Turn on both supplies. Valve will not operate unless both hot and cold water pressure is on.
Replace washers using TA-9 washer repair kit. Replace hot & cold seats using TA-4 hot/cold seat repair kit.
Open valve halfway, remove handle and tap spindle with plastic hammer. Check water pressure balancing piston in control spindle. See service instructions. Replace TA-10 flow control spindle.
Reduce maximum flow by using volume control adjustment on valve or showerhead. This will allow longer period of use before overdrawing hot water supply.
If piping is accessible, correct connections to the valve. If piping is not accessible, order T-108 reverse seat and tool kit. Older installations may also require replacing the TA-4 hot/cold seat repair kit.
11
ZV-3247 REV B
Page 12
WARNING: This product can expose you to chemicals including lead, which is known to the state of California to cause cancer, birth defects, or other reproductive harm. For more information, go to www.P65Warnings.ca.gov.
Symmons Industries, Inc. 31 Brooks Drive Braintree, MA 02184 Phone: (800) 796-6667 symmons.com Copyright © 2019 Symmons Industries, Inc.
ZV-3247 REV B
gethelp@symmons.com
Fax: (800) 961-9621
100719