Symmons HTA-100 Service Manual

Page 1
12V
6V
T
coil connections
Remote monitoring
system connections
Temperature probe and 1/4" NPT male tting
Water hammer
arrestor (optional)
Tee tting
(required, see
options)
Alarm control module
Water ow
Transformer 12 VAC/15 VA
Solenoid valve (optional)
12 VDC, 10 Watts max
120 VAC Power
25'probe cable (optional lengths)
ON
OFF
Fuses #229
1.5A / 250VP
12 VAC
power input
12 VDC valve
power output
(optional)
Temperature
input probe
DIP Switches
Rear view of Alarm Control Module
12 VDC relay
power output
(optional)
TempControl
®
High Temperature Audio Visual Alarm System, HTA-100
Installation and Service Instructions
General Information
Alarm System - TempControl High Temperature Audio Visual Alarm System will monitor, alert and alarm when water temperature exceeds preset limit. It best ts applications where there is a critical need to accurately monitor and control warm or hot water temperature.
Solenoid Valve (optional) - When alarmed, the valve is de-energized and closes to provide complete shutdown of the water ow.
Relay (customer supplied option) - Installed relay enables remote monitoring of alarm control module.
Caution Set Point - is the lower of the two set point temperatures that alerts when the output water is approaching an undesirable temperature limit.
Alarm Set Point - Once the output temperature reaches the
alarm set point, the system goes into full alarm mode.
Installation
Important: All piping should be thoroughly ushed prior to installation to prevent debris from
interfering with the solenoid operation. Do not run solenoid power and temperature probe through same conduit.
■ Connect 120 VAC line voltage to the primary side of the transformer as displayed in Figure 1.
Figure 1
■ Connect the 12 VAC secondary side of the transformer to the 12 VAC power input terminals on the back of the alarm control module as identied in Figure 2 below. Note that there is no polarity required for the input terminals.
Piping
Tee Fitting - Required; appropriate size tting for application purchased seperately (see options).
Temperature Probe - Locate probe as far downstream from mixing valve as is reasonably possible.
a. Slide connector nut and ferrule piece over the probe. b. Slide probe 1/2” to 2/3” into the tee tting. c. Slide the ferrule and connector nut down the probe sha
and tighten in place.
Solenoid Valve (optional, 12 VDC, 10 Watts, normally closed) - Install valve directly before the temperature probe in any orientation. Make note of the correct direction of the water ow as marked on the valve.
Electrical
■ Mount the 4" x 4" supplied mounting box in a dry location within wiring reach of the temperature probe and solenoid valve if used.
■ Mount supplied transformer. (120 VAC – 12 VAC/15 VA UL listed, CSA certified class 2)
For California Residents WARNING: is product contains chemicals known to the State of California to cause cancer, birth defects, or other reproductive harm.
Figure 2
Temperature Probe - Plug probe into the connector on the backside of the control module as identied in Figure2 above. Note that the connectors are keyed and will only mate in one direction. (optional cable lengths are available)
Solenoid Valve (optional) -
Connect coil wires between the solenoid valve and the valve power output terminals on the back of the control module as identied in Figure 2 above. Note that there is no polarity required between connections.
Page 2
Relay (customer supplied option) -
Connect relay coil wires between the relay and the valve power output terminals on the back of the control module as identied in Figure 2. Note that there is no polarity required between connections.
Fahrenheit / Celsius Temperature Display Setting
■ Select either Fahrenheit or Celsius display units by setting Dip Switch on control module circuit board.
Fahrenheit
DIP Switch 1 = OFF
Celsius
DIP Switch 1 = ON
Figure 3
Electrical Enclosure Box
■ Secure control module in electrical box using the two (2) screws provided with box. Screws should be inserted into the upper right and lower le corners of the control module.
■ Do not remove upper le and lower right screws securing the control module together.
It may be necessary to move the opposite set point to achieve the desired setting. Once the desired temperatures are selected, return the key to the RUN position.
Alarm Lockout
e alarm control module can be locked to prevent changes to the set points, even with the access key.
■ Once caution set point and alarm set point has been set, remove the screws from upper right and lower le corners of front plate. Remove the control module from the 4" x 4" box.
Enable set point lockout
Enable
- DIP Switch 2 = ON
Disable - DIP Switch 2 = OFF
■ Reinstall the control module into the 4" x 4" box.
■ When the key is placed in the SET position, the display will alternate between a set point temperature and the characters LOC.
■ Set point temperatures can be viewed but unable to change.
Figure 5
Temperature Set Point Adjustments
NOTE: The following settings were set at the factory:
Caution Alert Temperature = 114˚F (45.6˚C) High Limit Alarm Temperature = 120˚F (48.9˚C)
Reset temperature
settings
factory temperature settings as required by the application to prevent erratic temperature readings that can prematurely activate the alarm.
SET key position - Turn key from the RUN position to the SET position.
Identify caution set
point temperature (A)
Press SELECT keypad button until A appears in the rst eld of the LED display. e three (3) digits immediately following the A identies the current caution set point temperature.
Set caution set point temperature - Pressup down keypad arrow buttons located below the display to increase or decrease temperature setting.
Identify alarm set point temperature (H) - Press SELECT keypad button until H appears in the rst eld of the LED display. e three (3) digits immediately following the H identies the current alarm set point temperature.
Set alarm set point temperature - Press up down keypad arrow buttons located below the display to increase or decrease temperature setting.
NOTE: Caution set point temperature cannot be set higher
than alarm set point temperature and alarm set point cannot be set lower than caution set point temperature.
- Reset the above
Figure 4
Alarm Operation
Normal Mode:
Green Valve (normal) LED LED is lit to indicate
normal operation; that water temperature is below set
point temperature
is installed, it is in the open position.
Flashing Red Dot  A ashing red dot (Heart Beat) in the lower right corner of the display indicates that the systems processor is running.
Caution Mode:
Amber Caution LED LED will blink and the audible signal will sound briey every 60 seconds when the temperature reaches the caution set point indicating attention should be paid to the system.
Green Valve (normal) LED LED will remain lit indicating normal operation.
Alarm Mode:
Red Alarm LED
Caution LED
reaches the alarm set point. A continuous pulsing audible signal will also be heard.
Green Valve (normal) LED LED will go out indicating no water can ow. (If solenoid is installed, valve will close)
Signals mean immediate attention should be given to the system.
Alarm Hysteresis:
Amber Caution LED LED will light if the temperature decreases below the alarm set point indicating that the temperature is lower than the alarm set point but still greater than the caution set point.
Alarm condition/mode will still be in eect. e system
will only reset when the temperature decreases below the
caution set point.
and can ow. If optional solenoid valve
LED will blink and the Amber
will go out if the output temperature
Page 2
Page 3
BUILDING
T
PARALLEL
CONNECTION TO
SOLENOID VALVE
MONITORING
SYSTEM
CONNECTIONS
12V-DC RELAY
(relay coil current @ <80 mA)
(CUSTOMER SUPPLIED)
Alarm Control Module
HIGH TEMPERATURE ALARM - SYSTEM OPERATING CONDITIONS:
System OFF – no current to valve or relay – valve closed/relay open – no alarm
System ON/SET – current to valve and relay – valve open/relay closed – no alarm
System ON/TRIPPED – no current to valve or relay – valve closed/relay open – alarm
(total current @ <833 mA )
Page 3
(valve current @ <750 mA)
NOTES:
3-The above system design only provides for a “binary or on/off” signal to the building monitoring system
1-All current values are maximums not to exceed
2-The above system design does not transmit “analog or digital” data to the building monitoring system
4-Building monitoring system connections and/or signals are defined per the customer application
Page 4
Override Key
Alarm Set Point - once alarm set point temperature has been
reached, only personnel with the override key can initiate water flowing in the system.
Override Position - Insert the key into the control module front panel and turn the key switch to the override position. e solenoid valve is held open allowing water to ow.
All users should be clear of the water ow due to excessive temperature owing until the system is corrected.
SILENCE Keypad Button - e audible signal may be silenced by depressing the SILENCE keypad button located on the panel. e audible signal will only be silenced for 60 seconds and will resume at the completion of the cycle.
Key Removal - e key cannot be removed in the override
position
preventing the solenoid from being held open and
le unattended.
Alarm Hysteresis - As the system output temperature is corrected, the above Alarm Hysteresis conditions will occur.
Green Valve (normal) LED  LED will blink and an audible signal will be heard regardless of the current mode when the key switch is in the override position and the silence period has expired.
TROUBLE SHOOTING CHART
HTA-100 Alarm System Kit - includes the following:
■ Programmable alarm control module with two system operation keys and stainless steel front panel
■ Electrical mounting enclosure box; 4" x 4"
■ Transformer; 120 VAC, 12 VAC/15 VA, UL listed/
CSA certified class 2
■ Solid state temperature probe with 25' cable and 1/4" male compression fitting for attaching probe
Options
Solenoid Valves 12 VDC/10 Watts max (normally closed)
SV-102 .....................1/2" NPT
SV-200 .....................3/4" NPT
SV-400 .....................1" NPT
SV-500 .....................1-1/4" NPT
SV-700/900 .............1-1/2" NPT
SV-1000 ...................2" NPT
Water Hammer Arrestor
WHA-1 .....................1" NPT water hammer arrestor
Tee Fittings
TF-102 .....................1/2" x 1/2" x 1/4" NPT
TF-200 .....................3/4" x 3/4" x 1/4" NPT
TF-400 .....................1" x 1" x 1/4" NPT
TF-500 .....................1-1/4" x 1-1/4" x 1/4" NPT
TF-700/900..............1-1/2" x 1-1/2" x 1/4" NPT
TF-1000 ...................2" x 2" x 1/4" NPT
Temperature Probe Cables - additional lengths
TPC-50 ....................50' probe cable
TPC-100 ..................100' probe cable
Relay (customer supplied option)
Problem Cause
Front Panel Display: ERR1
Front Panel Display: ERR2
Front Panel Display: ERR3
Front Panel Display: ERR4
Front Panel Display: ERR5
Front Panel Display: CAL
Front Panel Display: PRB1
Front Panel Display ashes: LOC
Memory problem with circuit board
“Up arrow” button shorted or stuck on power up
“Down arrow” button shorted or stuck on power up
Key switch in “set” position on power up
Key switch in “override” position on power up
Calibration error
Power up without probe attached or with probe wire broken
Set point lockout enabled
Solution (Follow service instructions)
Contact factory technical service
Ensure button is not depressed; if this does not correct problem contact factory technical assistance
Ensure button is not depressed; if this does not correct problem contact factory technical assistance
Turn key to run position; if this does not correct problem contact factory technical assistance
Turn key to run position; if this does not correct problem contact factory technical assistance
Contact factory technical service
Reconnect probe; if this does not correct problem contact factory technical assistance
Set DIP switch 2 to the off position
Set point cannot be adjusted
No power, no display or
One or both fuses are blown
erratic behavior
Symmons Industries, Inc. ■ 31 Brooks Drive ■ Braintree, MA 02184 ■ Phone: (800) 796-6667
Co pyri ght © 2016 Symmons Industries, Inc. ■ www.symmons.com ■ gethelp@symmons.com ■ ZV-3004 REV A ■ 012116
Check and replace 1.5A fuses located on circuit board
Fax: (800) 961-9621
Loading...