SymCom PumpSaver Plus 111P, PumpSaver Plus 233P-1.5, PumpSaver Plus 233P Installation Instructions Manual

INSTALLATION INSTRUCTIONS
MODEL 233P/111P/233P-1.5
Revision B1
Rapid City, SD, USA, 07/2009
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION!
FOLLOW NATIONAL, STATE AND LOCAL CODES.
READ THESE INSTRUCTIONS ENTIREL Y BE FORE INSTALLATION.
SymCom’s PumpSaver
®
Plus is a pum p monitor designed to protect single-phase pumps from dry­well, dead-head, jammed impeller, rapid-cycling, overvoltage and undervoltage conditions. The PumpSaver
®
Plus Model 233P protects 230V, 2 or 3-wire, 1/3 to 3 hp pumps. The Pum pSaver®Plus
Model 233P-1.5 protects 230V, 2 or 3-wire, 1/ 3 to 1.5 hp pumps. The PumpSaver
®
Plus Model 111P protects 115V, 2 or 3-wire, 1/3 to 1 hp pumps. Typical applications include submersible pumps, centrifugal pumps, circulating pum ps, cooling pumps, environmental pumps , residential waterwells, commercial waterwells, irrigation wells, and golf course and other sprinkler systems.
CONNECTIONS
NOTE: Use with UL/CSA listed over load or impe danc e pr ote ct e d pumps or motors only.
1. Mount the PumpSaver
®
Plus in a convenient location in or near the pump control box. If the
location is wet or dusty a NEMA 3R, 4, or 12 enc losure s hould be u sed. The PumpSaver
®
Plus
must be protected by a fuse or circuit breaker (30A RK5 fuse or 30A inverse time breaker max).
2. Connect one line from the fused disconnec t to the L1 I N terminal of the PumpSaver
®
Plus. Run
a wire from the L1 OUT terminal to the other in-line controls such as pressure or float switches.
3. Connect the other line from the fused disconnect (ungrounded fused conductor) t o the L2 IN
terminal of the PumpSaver
®
Plus. Run a wire from the L2 OUT terminal to the other in-line
controls such as pressure or float switches (see Figure 1).
4. Refer to the appropriate wiring diagram for your specific application:
Typical wiring diagram – Figure 1
Standard 3-wire control box – Figure 2
Deluxe control box – Figure 3
2-Wire pump direct feed – Figure 4
*** WARNING ***
PROPER OPERATION REQUIRES FIELD CALIBRATION
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
FIGURE 1: Typical Wiring Diagram
FIGURE 2: Standard Control Box Wiring Diagram
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
FIGURE 3: Deluxe Control Box Wiring Diagram
FIGURE 4: 2-Wire P ump Direct-Feed Wiring Diagram
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
OPERATION
The PumpSaver®Plus monitors pump load i n amps and ki lowatts. When the c urrent (am ps) exceeds approximately 125% of calibrated current, or power (kW) drops below the adjustable underload t rip point, the PumpSaver
®
Plus—after the trip delay—will turn off the pump. The PumpSaver®Plus will time through the restart delay, and then restart the pump. The calibration is stored in permanent memory—it does not need to be recalibrated if power is lost.
CALIBRATION
NOTE: Th e PumpSaver®Plus should be cal ibrated during normal pumping conditions.
1. T urn the RESTART DELAY/ CALIBRATION knob
fully counter-clockwise to th e CAL. position.
2. A pply power—the pump will run for approximately
10 seconds then shut off.
3. Set the RESTART DELAY/ CALIBRATION knob
to the desired restart delay (dry-well recovery time)—the pump will turn on.
CALIBRATING WHILE PUMPING
The PumpSaver
®
Plus can also be calibrated while the pump is running. Turn the R ESTART DELAY/ CALIBRATION knob to CAL. while pumping. Wait for the pump to turn off (approximately 10 seconds), then adjust the RESTART DELAY/ CALIBRATION knob to the desired setting.
SENSITIVITY
The PumpSaver®Plus has an adjustment knob to set the underload trip sensitivity. Setting SENSITIVITY to the m iddle pos ition (straight up) is equivalent t o Sym Com’s st andard underload tri p level. Adjust the SENSITIVITY knob to increase/dec rease underload sensitivity up to appro ximately 10% of the standard trip. It may be necessary to increase the sensitivity if the PumpSaver
®
Plus does not trip on dry-run or dead-head or it is k nown that the water level i n the well is ver y low relative to the pump’s capabilities.
WARNING: Decreasing the SENSITIVITY may compromise the PumpSaver
®
Plus’ ability to
detect dry-run and/or dead-head conditions.
RESET MODE / RESTART DELAY
Any restart delay can be by-passed by rotat ing the RESTART DELAY/ CALIBRATION knob to the RESET position and back to the desired restart delay setting.
NOTE: The restart delay setting can be changed at any time. The current and subsequent trips will follow the new restart delay setting.
The RESTART DELAY/ CALIBRATION knob can be placed in the RESET position for manual reset. If the PumpSaver
®
Plus trips off in this m ode due to a voltage or load probl em, the RESTART
DELAY/ CALIBRATION knob must be rotated out of the RESET position to restart the pump.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
RUN HOURS / FAULT HISTORY
The PumpSaver®Plus records pump run hours. Run hours can be displayed by a PumpSaver® Informer (see USING AN INFORMER
at the bottom of this page). Run hours and fault history can be
cleared on the PumpSaver
®
Plus. Read the following instructions fully before performing the
procedure.
NOTE: Turn the S ENSITIVITY knob completely to the left (counter-clockwise) o r completely to the right (clockwise) when directed.
To Reset Run Hours and Clear Fault History:
1. Remove power to the PumpSaver
®
Plus.
2. Set the RESTART DELAY/ CALIBRATION knob to RESET and the SENSITIVITY knob to t he
middle (12:00) position.
3. Apply power to the PumpSaver
®
Plus—the CAL. LIGHT will turn on.
4. Turn the SENSITIVITY knob to the right—the CAL. LIGHT will turn off and the RUN LI GHT will
turn on.
5. Turn the SENSITIVITY knob to the left—both lights will turn on.
6. Turn the SENSITIVITY knob to the right.
7. After 10 seconds, t he CAL. and RUN LI GHTS will blink twice indicat ing the run hours and fault
history have successfully been cleared.
RAPID CYCLING
Rapid cycling is defined as more than 4 restarts in a 60-second period. The PumpSaver®Plus is capable of detecting a rapid-cycle c ondition whether a control device, s uch as a pressure switch, i s installed before* or after it . Upon detecting either f orm of rapid cyc ling, the PumpSaver
®
Plus will
lock-out, preventing damage to the pump. To reset the PumpSaver
®
Plus, remove and re-apply
power.
RAPID CYCLING (Line Side / Upstream)
Rapid cycling of the line side of the PumpSaver
®
Plus may be caused by several naturally occurring conditions which are indistinguishable from true rapid cycling. For this reason, once tripped, the PumpSaver
®
Plus will wait 30 minutes and restart. If the restart is successful (the pump runs for
more than one minute), the rapid cycle counter will res et t o zero. If the PumpS aver
®
Plus encounters rapid cycle 4 times without a successful restart, it will lock-out and require a manual reset. To res et the PumpSaver
®
Plus, remove and re-apply power.
*Protection against rapid cycling of a control device installed before the PumpSaver
®
Plus is disabled by default. Read the f ollowing instructions fully bef ore performing the procedure t o enable this feature.
NOTE: Turn the S ENSITIVITY knob completely to the left (counter-clockwise) o r completely to the right (clockwise) when directed.
To Enable Rapid-Cycle Protection when a Control Device is Installed BEFORE the PumpSaver®Plus: (to disabl e, f ollow the sam e procedure)
1. Remove power to the PumpSaver
®
Plus.
2. Set the RESTART DELAY/ CALIBRATION knob to RESET and the SENSITIVITY knob to the
middle (12:00) position.
3. Apply power to the PumpSaver
®
Plus —the CAL. LIGHT will turn on.
4. Turn the SENSITIVITY knob to the right—the CAL. LIGHT will turn off, RUN LIGHT will turn on.
5. Turn the SENSITIVITY knob to the left—both lights will turn on.
6. Turn the SENSITIVITY knob rightleftrightleftright.
7. After 2 seconds, the CAL. and RUN LIGHTS will blink once indicating line side rapid-cycle
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
protection has been enabled.
RAPID CYCLING (Load Side / Downstream)
Load side rapid cycling of the pump will immediately result in a manual lock-out. The pump will not restart automatically. To reset the PumpSaver
®
Plus, remove and re-apply power.
Note: P
rotection against rapid cycling of a control device installed after the PumpSaver
®
Plus is
always enabled. Disabling line side detection will not disable load side detecti on.
USING AN INFORMER
PumpSaver®Plus products are equipped with an infrared LE D that will communicate to a SymCom Informer—a handheld, battery-operated, diagnostic tool. The Informer—when directed at the PumpSaver
®
Plus—will display real-time voltage, current and power; dry-well and overcurrent trip points; calibration voltage; last 20 faults; voltage, current and power at the last fault; highest/lowest voltage and current since c alibrat ion; the m odel num ber; and the CT s ize if applic able. The Inf ormer can be used on any single-phase PumpSaver®Plus equipped with an infrared LED transmitter. Contact SymCom for more information at 800-894-0412 or visit our website.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
TROUBLESHOOTING
RUN LIGHT CAL. LIGHT PROBLEM or FUNCTION CORRECTIVE ACTION
On Steady Off
RUN:
Pump is running—or ready to run—no problems in operation
If pump is not running, check for loose wiring and ensure proper function of pressure or float
switches.
On Steady On Steady
CAL:
The PumpSaver®Plus is in the
calibration process.
None
Off On Steady
CAL COMPLETE: The PumpSaver®Plus has calibrated, the RESTART DELAY/ CALIBRATION knob was left in the CAL. position.
Pump is off.
Pump will restart as soon as the
RESTART DELAY/ CALIBRATION k nob i s rotated
out of the CAL. position.
Off Off
OFF / MANUAL RESTART:
The pump is not running. Either the PumpSaver
®
Plus has t ri pped on dry-run, dead-head, or overcurrent while the RESTART DELAY/ CALIBRATION knob was in the RESET position or source power is not present.
If knob is in the RESET position, rotate out of RESET—If the CAL. light blinks, check for an overcurrent condition. If the RUN light blinks, look for a dry-run or dead-head condition. If no lights come on, check incoming power for adequate voltage.
Blinking Off
DRY RUN / DEAD HEAD: The PumpSaver
®
Plus has shut the pump off due to a dry run or dead head condition. The unit is timing through the restart delay and will try to restart.
Check for restricted flow or inadequate supply of liquid.
Off Blinking
OVERCURRENT: The PumpSaver
®
Plus has shut the pump off due to an overcurrent condition. The unit is timing through the restart delay and will try to restart if line voltage is at an acceptable level.
Check for low or high voltage or jammed pump impellers. If these conditions do not exist, recalibrate the unit while it is drawing higher current (amps should not exceed SFA).
Blinking
alternately
with the
CAL. LIGHT
Blinking
alternately
with the
RUN LIGHT
VOLTAGE FAULT:
The PumpSaver®Plus is preventing the pump from starting due to voltage problems. The voltage is being interrogated and the unit will remain in this mode until the voltage is at an
acceptable level.
If the unit remains in this state for more than 5 seconds, check for high or low voltage.
Blinking in
unison with
the CAL.
LIGHT
Blinking in
unison with
the RUN
LIGHT
RAPID CYCLE:
The PumpSaver®Plus has shut down on rapid cycling. Power must be removed and reapplied
to reset the unit.
Check for a broken bladder in the pressure tank (if used), or check for a defective pressure or float switch.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
PHYSICAL DIMENSIONS
4.05" (102.87)
5.26" (133.60)
4.50" (114.30)
.375"
(9.53)
2.93"
(74.42)
2.17"
(55.12)
2.90"
(73.66)
FRONT VIEW
BOTTOM VIEW
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
SPECIFICATIONS
Functional Specifications
Adjustments/Settings
Overcurrent
125% of calibration point
Underload (dry-well)
Adjustable (70-90% of calibrated run power)
Overvoltage
233P, 233P-1.5
265VAC
111P
132.5VAC
Undervoltage
233P, 233P-1.5
190VAC
111P
95VAC
Number of restarts allowed in 60
second period (rapid-cycling)
4
Trip Delay Times
Overcurrent
5 seconds
Dry-well
4 seconds
Dry-well Optional*
8 seconds
Restart Delay Times
Over/undervoltage
2 seconds
All other faults
Manual, 2-225 minutes
Input Characteristics
Supply Voltage
233P, 233P-1.5
230VAC
111P
115VAC
Load Range
233P
1/3 – 3 hp
233P-1.5
1/3 – 1.5 hp
111P
1/3 – 1 hp
Frequency 50/60Hz
(NOTE: 50Hz will increase all delay timers by 20%)
Output Characteristics
Output Contact Rating-SPST
233P
3hp @ 240VAC (17 Amps max.)
233P-1.5
1.5hp @ 240VAC (10 Amps max.)
111P
1hp @ 120VAC (16 Amps max.)
General Characteristics
Operating Temperature
-40° to 55°C (-40° to 131°F)
Maximum Input Power
5 W
Wire Gauge
Solid or stranded 10 – 22 AWG
Terminal Torque
13 in.-lbs.
Standards Passed
Electrostatic Discharge (ESD) Surge Immunity
IEC 61000-4-2, Level 2, 4kV contact, 6kV air IEC 61000-4-5, Level 4, 4kV line-to-line and line-to-
ground
Safety Marks
cUL Listed
UL508 & C22.2 No. 14
Dimensions
2.90” H x 5.26” W x 2.93” D
Weight
14 oz.
Mounting Methods
#8 screws
*use part number 233P-UCTD8
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Loading...