Pump Controller – Five Channel
Dimensions in Inches
Model PC-105
SymCom’s PumpControl™ Model PC-105
is a five-channel pump controller designed
to handle multiple pump applications.
Alternatively, it can operate as a 5-channel
switch.
The PC-105s control functions support all
of the popular industry-standard multipump configurations.
Using the built-in DIP switches, individual
pumps can be disabled when taken out of
service for repair or maintenance.
orders@symcom.com / customerservice@symcom.com
(605) 348.5580 / (800) 843.8848 / Fax (605) 348.5685

Specifications
Functional Specifications:
Pumping modes available
Duplex pump-down
Triplex pump-down
Quadplex pump-down
Duplex pump-down SPS (separate pump stop)
Duplex pump-up
Triplex pump-up
Quadplex pump-up
Duplex pump-up SPS (separate pump stop)
Adjustments
Time delay/lag pump delay
Mode Selector
Option Selector
Silence Button
Reset Button
External alternation configuration
External alternation configuration
5-Channel relay mode
5-channel
Pump-to-pump start delay
Input Characteristics:
Supply Voltage
Frequency
Power
Output Characteristics:
Relay Output Rating
General Characteristics:
Operating Temperature
Terminals
Wire Size
Torque
Standards Passed:
Electrostatic Discharge (ESD)
Radio Frequency Immunity (RFI)
Fast Transients
Safety Marks
UL
cUL
Dimensions
Weight
Mounting Methods
How to order:
Part Number: PC-105
2 pumps with high and low alarms
3 pumps with high alarm (typical)
4 pumps
2 pumps with high alarm (typical) 2 stop floats
2 pumps with high and low alarms
3 pumps with low alarm (typical)
4 pumps
2 pumps with low alarm (typical) 2 stop floats
2-255 sec.
0 – 8 (9-F: force mode 0)
1 – 10, ON/OFF
Dry input only
Dry input only
ALS-1
ALS-2
1 relay latched / time delay output
2 seconds (min.)
120VAC nominal
50/60 Hz
4 Watts (max.)
7Amps @ 240VAC General Purpose
Pilot Duty 480VA @ 240VAC, B300
-20 to 55
12-20 AWG
6 in.-lbs. (max.)
IEC 61000-4-2, Level 3, 6 kV contact, 8 kV air
IEC 61000-4-2, Level 3, 10V/m
IEC 61000-4-4, Level 3, 4 kV power terminals, 2kV
input/output terminals
UL508 (File #E68520)
C22.2 No. 14
(LxWxD) 5.03” x 3.7” x 2.35”
1.2 lbs.
35 mm DIN rail or
Surface Mount (#6 or #8 screws)
°
C
Typical applications explained in PC-105
installation bulletin. See www.SymCom.com
orders@symcom.com / customerservice@symcom.com