Symcom PC-102CICI-DL Engineering Specification

ENGINEERING SPECIFICATION
SYMCOM MODEL PC-102CICI-DL Pump Control
PART 1 GENERAL
1.1 REFERENCES
A. UL 508 Industrial Control Equipment – Underwriters Laboratories B. IEC 60947 Low Voltage Switchgear and Controlgear – International Electrotechnical Commission C. ANSI/IEEE C62.41 – American National Standards Institute/Institute of Electrical & Electronics Engineers
Equipment shall be installed according to the latest version of the National Electrical code.
1.2 WARRANTY
A. Manufacturer Warranty: The manufacturer shall guarantee the pump control to be free from material and workmanship defects
for a period of five years from the date of manufacture when installed and operated according to the manufacturer’s requirements.
PART 2 PRODUCTS
2.1 MANUFACTURERS
The equipment specified shall be the Model PC-102CICI-DL, manufactured by SymCom, Inc.
2.2 DESCRIPTION
A. Regulatory Requirements:
2.3 PERFORMANCE/DESIGN CRITERIA
1. The equipment shall be UL Listed as type NKCR—Industrial Control Equipment-Motor Controllers-Auxiliary Devices.
A . General I/O Capability:
1. Outputs: a. The equipment shall include two SPDT output relays contact pilot duty rate d at 180VA @ 120VAC, 5 amps @ 120VAC
general purpose.
2. Inputs: a. The equipment shall provide two control inputs. b. The equipment shall accept single-phase input voltage rated 120 VAC.
B . Functions:
1. The equipment shall provide dual-channel switch logic. a. The equipment shall activate an output relay upon activation of its associated input channel. b. The equipment shall illuminate an LED upon activation of its associated output relay.
C. Human Interface Features:
1. The equipment shall provide the following functions controlled from a DIP switch: a. Input channel 1 logic selection: direct, inverted b. Input channel 1 debounce delay selection: ½, 2 seconds. c. Input channel 2 logic selection: direct, inverted d. Input channel 2 debounce delay selection: ½, 2 seconds.
2. The equipment shall include a dial adjustment to set the input sensitivity from 4.7k to 100k ohms.
3. The equipment shall have two indicator LEDs capable of indicating the status of the output relays.
D . Electromagnetic Compatibility:
1. The equipment shall be immune to electrostatic discharge per IEC 61000-4-2, Level 3, 6 kV contact discharge and 8 kV air discharge.
2. The equipment shall be immune to electrical fast transient bursts per IEC 61000-4-4, Level 4, 4 kV power supply port, 2 kV input/output ports.
3. The equipment’s power supply port shall be immune to electrical surges per IEC 61000-4-5, Level 4. Specified limits shall be 4kV line-to-line and line-to-ground.
4. The equipment shall be immune to radiated radio frequency emissions. Specified limits shall be 10V/m at 150 MHz.
ES_PC-102CICI-DL_A1 06/09/2008
E. Dielectric Isolation: The equipment shall provide 2000VAC dielectric withstand between the AC mains and the relay contacts and
between the AC mains and enclosure for one minute. F. Enclosure Class of Protection: The equipment shall provide IEC IP20 (finger safe) protection. G . Environmental Requirements:
1. The equipment shall operate continuously without derating in ambient temperatures of -20° to 55°C (-4° to 131°F).
2. The equipment shall operate continuously without derating in relative humidity of up to 95% non-condensing per IEC 68-2-3.
3. The equipment shall operate properly after storage in ambient temperatures of -40° to 80°C (-40° to 176°F). H. Dimensions: The equipment dimensions shall not exceed 2.1” in width x 3.5” in length x 2.5” in height. I . Mounting:
1. The equipment shall be mountable on standard 35 mm DIN rail.
2. The equipment shall be surface mountable on a backplane using two screws, bolts or similar mounting hardware.
End of Section