ENGINEERING SPECIFICATION
SYMCOM MODELS PC-100-LLC-CZ / PC-200-LLC-CZ
2-INPUT, LIQUID LEVEL CONTROL
PART 1 GENERAL
1.1 REFERENCES
A. UL 508 Industrial Control Equipment – Underwriters Laboratories
B. IEC 60947 Low Voltage Switchgear and Controlgear – International Electrotechnical Commission
C. ANSI/IEEE C62.41 – American National Standards Institute/Institute of Electrical & Electronics Engineers
D. CSA C22.2 No. 14 Industrial Control Equipment – Canadian Standards Association
1.2 WARRANTY
A. Manufacturer Warranty: The manufacturer shall guarantee the product to be free from material and workmanship defects for a
period of five years from the date of manufacture when installed and operated according to the manufacturer’s requirements.
PART 2 PRODUCTS
2.1 MANUFACTURERS
For Model PC-100-LLC-CZ
The equipment specified shall be the Model PC-100-LLC-CZ, manufactured by SymCom, Inc.
For Model PC-200-LLC-CZ
The equipment specified shall be the Model PC-200-LLC-CZ, manufactured by SymCom, Inc.
2.2 DESCRIPTION
A. Regulatory Requirements:
1. The equipment shall be UL Listed as type NKCR—Industrial Control Equipment-Motor Controllers-Auxiliary Devices.
2. The equipment shall be ULC Listed as type NKCR7—Industrial Control Equipment-Motor Controllers-Auxiliary Devices
Certified for Canada.
3. The equipment shall be CE marked for use in the European Union and evaluated against IEC 6094 7 Low Voltage Switchgear
2.3 PERFORMANCE/DESIGN CRITERIA: 2-INPUT, SINGLE PHASE LIQUID LEVEL CONTROL
For Model PC-100-LLC-CZ
and Controlgear.
A. Capabilities and Features
1. The equipment shall include:
a. A voltage range of 95-120VAC
For Model PC-200-LLC-CZ
a. A voltage range of 190-240VAC
2. The equipment shall have a probe input debounce time delay of 2 seconds.
3. The equipment shall include inputs for High and Low Probes with one common connection.
4. The equipment shall include an adjustment knob that allows the user to select Pump-Up operation or Pump-Down operation.
5. The equipment shall include an adjustment knob that allows the user to select the sensitivity of the probe inputs from 4.7k to
100k.
6. The equipment shall operate as follows when set for Pump-Up operation:
a. The relay shall energize when the resistance of the Low Probe is above the sensitivity threshold.
b. The relay shall de-energize when the resistances of the Low Probe and the High Probe are below the sensitivity threshold.
7. The equipment shall operate as follows when set for Pump-Down operation:
a. The relay shall energize when the resistances of the Low Probe and the High Probe are below the sensitivity threshold.
b. The relay shall de-energize when the resistance of the Low Probe is above the sensitivity threshold.
8. The equipment shall include one relay output pilot duty rated 480VA at 240VAC.
9. The equipment shall include one relay output general purpose rated 10A at 240VAC.
10. The equipment shall have one g reen indicator light. The light shall turn on when the relay is energized, and turn off when the
relay is de-energized.
11. The equipment shall allow single probe operation by shorting the High Probe input to the common connection, and using the
Low Probe input and common connection.
B. Electromagnetic Compatibility
1. The equipment shall be immune to electrostatic discharge per IEC 61000-4-2, Level 3, 6 kV contact discharge and 8 kV air
discharge.
2. The equipment shall be immune to electrical fast transient bursts exceeding IEC 61000-4-4, Level 3. Specified limits shall
2kV
3. The equipment shall be immune to electrical surges per IEC 61000-4-5, Level 2 and Level 4. Specified limits shall be Level 4,
be
ES-PC-XXX-LLC-CZ_A1 10/9/2009

4kV line-to-line; Level 4, 4kV line-to-ground, and Level 2, 1kV probe inputs-to-ground.
4. The equipment shall be immune to electrical surges per ANSI/IEEE C62.41 Surge and Ring Wave. Specified limits shall be
6kV line-to-line.
5. The equipment shall be immune to radiated radio frequency emissions. Specified limits shall be 10V/m at 150 MHz.
B. Dielectric Isolation: Equipment withstands an alternating current potential of 1000V plus twice the rated voltage of the equipment
for 1 minute without breakdown between uninsulated live parts and the enclosure with the contacts open and closed; between
terminals of opposite polarity with the contacts closed; and between uninsulated live parts of different circuits.
C. Environmental Requirements
1. The equipment shall operate continuously without derating in surrounding air temperatures of -40° to 70°C (-40° to 158°F).
2. The equipment shall operate continuously without derating in relative humidity of 10% up to 95% non-condensing per IEC 682-3.
3. The equipment shall operate properly after storage in ambient temperatures of -40° to 80°C (-40° to 176°F).
D. Dimensions: The equipment dimensions shall not exceed 1.750” H x 2.375” W x 4.125 D” (with socket).
E. Mounting:
1. The equipment shall be mounted using the SymCom OT08-PC 8-pin Socket.
a. The socket shall be 600V rated.
b. The socket shall be 10A rated.
c. The socket shall provide a means for mounting on the surface or on a DIN rail.
End of Section