Symcom MP8000 series Quick Start Guide

MP8000 SERIES Bluetooth® Overload Relay
Rev: 1-B-021518
Document number: 090-04553-02
QUICK-START GUIDE
®
Overload Relays. For further technical information, refer to the product manual found at Littelfuse.com
/mp8000manual.
Ensure that the work area is de-energized prior to product installation. Follow your company’s safety policy and lockout procedures.
INSTALLATION
1. Write down the pairing code and password located on the adhesive
label on the side of the MP8000 and store in a secure location.
2. The MP8000 can be surface, DIN-rail or panel mounted in a sheltered
enclosure environment that does not exceed the temperature and humidity ratings for the relay. (See Figure 9 for dimensions)
3. Provide control power to power the MP8000 with 85-264 VAC and
connect to terminals A1 and A2 per the diagrams on page 2. (See Figures 10 and 11)
CONFIGURATION
The MP8000 can be used via Bluetooth Android™ smartphone or tablet.
Pair Apple iPhone® or iPad® (iOS version 9.0 and higher) or Google
1.
Android™ (version 4.3 and higher) smartphone or tablet to MP8000:
a. Obtain pairing code from label on MP8000. b. Download the free Littelfuse MP8000 app from Apple® App Store
or Google Play™ Store.
c. Ensure Bluetooth® is turned on and the device is discoverable. d. Select desired MP8000 from available devices in the Littelfuse
app. (See Figure 1)
e. Enter pairing code for the MP8000. (See Figure 2) f. Pairing is a one-time process per smartphone per MP8000. g. If the MP8000 has never been configured, a popup box will appear
prompting the user to configure the MP8000. (See Figure 3)
Entering settings on the MP8000:
2.
a. Press the “Configuration” button. b. Settings are divided into “Basic” for the most commonly used
parameters and “Advanced” for less commonly used parameters.
c. Tap the desired parameter to enter the setting. (See Figure 4) d. A popup box will appear. Enter the password for the unit. The
password is located on product label. (See Figure 5)
NOTE: A password is only required for modifying settings and is only required once per session. If the user disconnects from the MP8000, or the user moves out of range, the password will be required when re-connecting to the MP8000.
e. A popup box will appear in which the numerical setting can be
entered. Enter the setting and press “Save.” (See Figure 6)
f. Continue through the other settings, entering values
where desired.
®
using an Apple® or
Figure 1
Figure 3
Patent Pending
Figure 2
Figure 4
Figure 6Figure 5
MP8000 SERIES Bluetooth® Overload Relay
Rev: 1-B-021518
Document number: 090-04553-02
2.93 (74.42)
2.50 (63.50)
2.50 (63.50)
PHASE A
PHASE A
3. Viewing real-time information on the MP8000 (See Figure 7):
a. Press the “Real Time” button. b. Scroll down to view the real-time measurements for
each parameter.
Troubleshooting using the MP8000 (See Figure 8):
4.
a. Press the “Fault” button at the bottom of the screen. b. Fault information will appear on the screen in date order with the
most recent fault appearing first.
c. The fault displays the parameter that had the fault, with a time and
date stamp when the fault occurred.
d. Press the desired fault to display the conditions that were present
at the time of the fault.
If the MP8000 needs to be reset, this can be accomplished via the
5.
app by pressing the reset button.
Dimensions in inches (millimeters)
3.10 (78.74)
4.79 (121.67)
Figure 8Figure 7
4.08 (103.63)
Figure 9
3-phase wiring diagram Single-phase wiring diagram
C
90 - 690 VAC
0.5 - 100A
AUX VOLTAGE
SUPPLY
85 – 264 VAC
A1
MP8000
Z1
START
C
(95)
Z2 T1
FROM A1
STOP
(OPTIONAL)
PHASE B
PHASE C
AUX VOLTAGE
85 – 264 VAC
C
ZERO-SEQUENCE
CURRENT
TRANSFORMER
(OPTIONAL)
A1/N
Z1
L1 L3L2 A2/L
A
B
90 - 690 VAC
0.5 - 100A (100A+ using external CTs)
FROM A1
C
C
START
SUPPLY
MP8000
Z2 T1
STOP
C
(95)
HAND
PTC
(OPTIONAL)
PILOT
OFF
AUTO
NO (96)NC(14)
T2
NO (15)
I.2 I.1
.
C
(13)
FROM A2
PE
RESET
PHASE B
L1 L3L2 A2
A
B
M
C
HAND
PTC
M
C
OFF
NO (96)NC(14)
T2
PILOT
AUTO
NO (15)
I.2 I.1
.
C
(13)
FROM A2
PE
RESET
Figure 10 Figure 11