
in a convenient location in or near the motor
control panel. If the location is wet or dusty, the MotorSaver
be mounted in a NEMA 4 or 12 enclosure. The MotorSaver
mounted to a back panel using two #6 or #8 x 5/8 screws or can be
of the motor starter. (See Figure No. 1).
connect the normally open contact in series with the magnetic coil of the
motor starter as shown in Figure No. 1. For alarm operation, connect the
normally closed contact in series with the control circuit as shown in Figure

3-Phase Voltage
CONTROL VOLTAGE
24-240 VAC
LIGHT
3-Phase Voltage
CONTROL VOLTAGE
24-240 VAC
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

three-phase line voltage feeding the motor
desired position. The restart delay is the
acceptable voltage and the MotorSaver
closing its output contacts. For
compressor applications, the restart delay
should be set for the approximate time it
takes for the head pressure to bleed
off of the compressor. For other
applications, the restart delay is typically
set between 2 and 10 seconds.
adjustment to the desired
setting. This adjustment does not affect the
trip delay on phasing faults. Typically, the
trip delay adjustment is set between 1 and 5
seconds. In areas where voltage uctuations are frequent, the trip delay
adjustment may be set greater than 10 seconds.
4. Voltage unbalance adjustment: Rotate the
does not recommend operating a motor above 1% voltage unbalance without
the motor. The NEMA MG1 standard also recommends against
operating a motor above a 5% voltage unbalance under any circumstances.
SymCom recommends consulting the motor manufacturer for speci c
MODEL 460
190
200
416 440
230
240
380 480
400 460
208 220
Percent Unbalance =
Maximum Deviation from the Average
Average
x 100
Example: The measured line-to-line voltages are 203, 210, and 212.
Average =
203 + 210 + 212
3
= 208.3
The maximum deviation from the average is the largest difference
between the average voltage (208.3) and any one voltage reading.
208.3 - 203 = 5.3 210 - 208.3 = 1.7 212 - 208.3 = 3.7
The maximum deviation from the average is 5.3.
5.3
208.3
x 100 = 2.5% Unbalance
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

YOU HAVE JUST INSTALLED THE FINEST
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

does not have enough power
to operate its internal electronics. This
the voltages are correct, call SymCom at
two leads powering the MotorSaver
time. Re-apply the three-phase power.
the motor from running backwards. Correct
voltages and calculate the % unbalance. If
the voltage unbalance does not exceed the
the three line-to-line voltages. Calculate
the average of the three voltages. If the
voltage as selected by the LINE VOLTAGE
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Low, High, and Unbalanced Voltage
Single-phasing faults (>25% UB)
After a fault or complete power loss
Electrostatic Discharge (ESD)
Radio Frequency Immunity, Radiated
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

for a period of ve (5) years* from the date of manufacture. All other products manufactured by
years from the date of manufacture. For complete information on warranty, liability, terms, and
to a level of 6kv line-to-line
Ambient Operating: -20° - 70° C (-4° - 158°F)
Ambient Storage: -40° - 80° C (-40° - 176°F)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com