SymCom MotorSaver 201-SP, MotorSaver 201-SP-T01, MotorSaver 201-SP-T User Manual

2880 North Plaza Drive • Rapid City, SD 57702 (800) 843-8848 • (605) 348-5580 • FAX (605) 348-5685 www.symcominc.com • email: sales@symcominc.com
Features
Bicolor LED indicator light is green in normal conditions and red dur­ing trip conditions.
Microcontroller-based provides better accuracy and higher reliability than analog designs.
Transient protected to meet IEEE 587 and IEC 1000-4-5 standards and stand up under tougher conditions.
10A @ 240 VAC General Purpose Relay can switch most loads.
Model 201-SP
Model 201-SP-T
Model 201-SP-T01
Single Phase
Voltage Monitor
Engineered
Protection
Microcontroller
Based
Protects single phase
systems from:
Low Voltage
High Voltage (Option 9)
Additional Features:
UL and cUL listed
5 year Warranty
Made in USA
Din Rail or
Surface Mount
Model 201-SP is a plug-in voltage monitor designed to protect single phase motors regardless of size. It can be used on 95-120 VAC (201-100-SP), 190-240 VAC (201-200-SP), or 380-480 VAC (201-400-SP) motors to pre­vent damage caused by low voltage or high voltage (optional).
The unique microcontroller-based voltage and phase sensing circuit constantly monitors the voltage to detect harmful power line conditions. When a harmful condition is detected, the MotorSaver's output relay is deactivated after a specified trip delay. The output relay reactivates after power line conditions return to an acceptable level for a specified amount of time (RESTART DELAY). The trip delay prevents nuisance tripping due to rapidly fluctuating power line conditions.
9/02
2880 North Plaza Drive Rapid City, SD 57702 (800) 843-8848 (605) 348-5580 FAX (605) 348-5685 www.symcominc.com email: sales@symcominc.com
Specifications
Line Voltage Ranges ................................95 to 120 (100V Model)
....................................................................190 to 240 (200V Model)
....................................................................380 to 480 (400V Model)
Frequency ................................................50 or 60 Hz
Low Voltage (% of set point)
Trip ............................................................90%
Reset ........................................................93%
Trip Delay Time
Low Voltage or Optional High Voltage ......4 seconds
Restart Delay Time
After a Fault ..............................................2 seconds
After a Complete Power Loss ..................2 seconds
Output Contact Rating (Pilot Duty)
SPDT ........................................................480 VA @ 240 VAC
or 10A @240 VAC Gen. Purpose
Transient Protection (Internal) ................IEC 1000-4-5; 1995 to ±4kV
Power Consumption ................................5 Watts (Max.)
Weight ......................................................9 oz.
Socket Available ......................................The same 600V socket can be
Model Number OT08 surface mounted or installed on (UL Rating 600V) Din Rail
Specifications
Operating Points
Special Options
9/02
SymCom warrants its microcontroller-based products against defects in material or workmanship for a period of five (5) years from the date of manufacture. All other products manufactured by SymCom shall be warranted against defects in material and workmanship for a period of two (2) years from the date of manufacture. For complete information on warranty, liability, terms, returns, and cancellations, please refer to the SymCom Terms and Conditions of Sale document.
Model 201-SP
Model 201-SP-T
Model 201-SP-T01
Single Phase
Voltage Monitor
2880 North Plaza Drive, Rapid City, SD 57702 • (800) 843-8848
INSTALLATION INSTRUCTIONS FOR SYMCOM’S
MOTORSAVER
®
MODELS 201-SP, 201-SP-T, 201-SP-T01
BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION!!
FOLLOW NATIONAL, STATE AND LOCAL CODES!
SETTINGS
1. LINE VOLTAGE ADJUSTMENT: Rotate the LINE VOLTAGE ADJUSTMENT to the nominal line voltage feeding the motor to be protected.
POWER-UP
Turn on the power to the motor. The MotorSaver then goes through it's restart delay and the LED will flash green. After the RESTART DELAY, the MotorSaver®will energize its output contacts and the RUN LIGHT will turn solid green. If the contacts do not energize and the RUN LIGHT does not turn solid green, then see the TROUBLESHOOTING section.
Congratulations!!! You have just installed the finest motor protection available!
TROUBLESHOOTING
If the output relay does not energize and the RUN LIGHT does not turn solid green after waiting for the RESTART DELAY time, then:
1. Measure the line-to-line voltage. If the voltage is 10% above (for units with optional high voltage protection) or 10% below the voltage adjust set point,
the MotorSaver is functioning properly, saving your motor from abnormal power conditions.
2. If the unit seems to be malfunctioning, then contact SymCom at 1-800-843-8848 OR 1-605-348-5580 and we will be happy to help you.
To control a motor: Connect the normally open contact in series with the magnetic coil of the motor starter as shown for each model.
Figure No. 1:Typical Wiring Diagram
CONNECTIONS
1. Mount the MotorSaver in a convenient location in or near the motor control panel. If the location is wet or dusty, then the MotorSaver
should be mounted in a NEMA 4 or 12 enclosure.
2. Connect the lines of the power supply to L1 and L2 on the MotorSaver’s octal socket (see Figure No. 1).
3. Connect the output relay to the circuitry to be controlled (see Figure No. 1).
For motor control, use the ‘C’ and the ‘NO’ terminals.
For alarm circuits, use the ‘C’ and the ‘NC’ terminals.
RUN
RESTART DELAY
HIGH / LOW VOLTAGE
GREEN
GREEN
RED
INDICATOR LIGHT DIAGNOSTICS
WARRANTY
Seller warrants to the buyer that products furnished will be free from defects in material and workmanship, exclusive of corrosion, for a period of five years from the date of shipment from its factory, provided said products have been installed, maintained and operated in conformance with any applicable specifications and recommendations of the Seller. The sellers liability under this warranty shall be limited to the replacement within the aforesaid time of any defective work or material limited at the Seller’s factory and shall not be liable for any labor or other repair costs made outside the Seller’s factory without the written consent of the Seller. The Seller shall be liable for no other damages or losses. The warranty described in this paragraph shall be IN LIEU OF ANY OTHER WARRANTY EXPRESSED OR IMPLIED INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
BOTTOM
2.375"
(60.331)
1.75"
(44.545)
TOP
SIDE
3.15"
(80.010)
.5"
(12.700)
P/N-201-SP
190/240 VAC
www.symcominc.com
LINE VOLTAGE ADJUST
190
200
208 220
230
240
RUN LIGHT
(VAC)
SPECIFICATIONS MODELS 201-SP, 201-SP-T, 201-SP-T01
Line Voltage Ranges 95 - 120 (100V Model)
190 - 240 (200V Model)
380 - 480 (400V Model) Frequency 50 - 60 Hz Operating Points Low Voltage Trip (% of set point) 90% Reset (% of set point) 93% High Voltage Trip (% of set point)
N/A (Standard)
(110%, Option No. 9)
Reset (% of set point)
N/A (Standard)
(107%, Option No. 9)
Trip Delay Time (Nominal) Low Voltage 4 Seconds High Voltage
N/A (Standard)
(4 Seconds, Option No. 9)
Restart Delay Time After a Fault 2 Seconds From complete power loss 2 Seconds Output Contact Rating (SPDT)
Pilot Duty 480 VA @ 240 VAC
General Purpose 10 A @ 240 VAC
Internal Transient Protection Using IEC 1000-4-5:1995 4kv Power Consumption 5 Watts (Max.) Weight 9 oz.
DIMENSIONS FOR MODEL 201-SP, 201-SP-T, 201-SP-T01