Symcom LSRU-AL Installation Guide

INSTALLATION INSTRUCTIONS
FOR SYMCOM’S LOAD SENSOR
MODEL LSRU-AL
BE SURE POWER IS DISCONNECTED PRIOR TO INSALLATION!
FOLLOW NATIONAL, STATE, AND LOCAL CODES!
READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION!
The Model LSRU-AL is a dual trip point load monitor. It can be used to determine feed rates, tool wear, loss of prime on pumps, mixer viscosity, and all types of over and under load conditions. When the current draw is within the limits dened by the two user adjustments, the relay is energized. When the current falls outside of this range for one second, the relay will de-energize.
INSTALLATION
1. Mount the Model LSRU-AL near one of the conductors of the load being monitored. If the unit will be used in a dusty or wet environment, an appropriate NEMA rated enclosure should be used.
2. Insert one of the conductors of the load through the sensor hole in the LSRU-AL. a) For currents greater than 1 amp, proceed to step #3. b) For currents less than 1 amp, the conductor must be looped. Refer to the table below to determine the number of conductors needed through the sensor window.
NOTE: The OC and/or UC trip points must be set based on ‘I
eff
’ for
current range 1 units.
ACTUAL CURRENT NUMBER OF CONDUCTORS EFFECTIVE CURRENT (I
0.5 - 1.0 3 1.5 - 3.0
0.25 - 0.5 5 1.25 - 2.5
For values less than 0.25 consult the factory.
)
eff
3. Turn the user adjustments to the desired settings.
4. Wire the appropriate control voltage to L1 and L2.
5. Connect the output relay to the control circuitry. The proper wiring scheme may vary depending on the required action when a fault occurs. (A wiring diagram is shown in Figure 1 that utilizes the NO contact.)
2880 North Plaza Drive, Rapid City, SD 57702 • (800) 843-8848
LSRU
Unit Description
Model # Voltage Range Options Current Range
024 - 18 to 30 VAC 115 - 90 to 135 VAC
1 - 0 to 5 Amps 2 - 5 to 25 Amps 3 - 25 to 100 Amps
A L
OL
OL
OL
OL
MAGNETIC
CONTACTOR
L1
L2
L3
MOTOR
LOGIC INPUT
PLC OR OTHER
AUTOMATED
CONTROL SYSTEM
LOGIC OUTPUT
CONTROL
VOLTAGE
3 PHASE
POWER
LSRU-AL
RL1
M
RL1
6. Energize the load to be monitored. Verify normal running amps have been achieved. The LED will be lit under normal operating conditions (the current sensed is at an acceptable level) indicating the output contacts are energized (NO is closed and NC is open).
NOTE: The LSRU-AL is a fail-safe design, meaning the NO (normally open contact) will be open if the LSRU fails or control power is interrupted.
7. The installation is now complete.
FIGURE 1: TYPICAL WIRING DIAGRAM
Any questions or comments call SymCom at 1-800-843-8848 or
SymCom warrants its microcontroller based products against defects in material or workmanship for a period of ve (5) years from the date of manufacture. All other products manufactured by SymCom shall be warranted against defects in material and workmanship for a period of two (2) years from the date of manufacture. For complete information on warranty, liability, terms, and conditions, please refer to the SymCom Terms and Conditions of Sale document.
08/09/03 -2-
1-605-348-5580
Loading...
+ 2 hidden pages