Symcom LSRU Catalog Page

Load Sensor
Model LSRU
The Model LSRU load sensors use current levels to mon­itor all types of over and underload conditions such as feed rates, tool wear, pump loads, mixer viscosity and others. They may be used to stage pumps, chillers and other machinery. Two user adjustments are provided with your choice of overcurrent, undercurrent, trip de­lay, restart delay and extended restart delay options. Three current ranges, 0-10A, 5-25A and 25-100A, are available.
The output relay de-energizes when the current exceeds the over or under current setpoints. After the restart de­lay times out, the relay will close its output relay, letting the motor start back up. If the current level is unaccept­able, the relay will trip after the trip delay expires. If the current drops to zero, the LSRU will recognize a normal stop and will not de-energize it’s relay.
(605) 348.5580 / (800) 843.8848 / Fax (605) 348.5685
customerservice@symcom.com / technicalsupport@symcom.com
Specications
Functional Specications
Current Ranges
-1.5
-2
-3 Adjustment options Overcurrent Undercurrent Trip Delay Restart Delay Extended Restart Delay Motor Acceleration Time Accuracy Current Timing Isolation
Input Characteristics
Supply Voltage 24V Range 115V Range Frequency
Output Characteristics
Output Contact Rating-SPDT Form C 480VA@240VAC Pilot Duty
General Characteristics
Operating Temperature Terminals Wire AWG Torque Power Consumption Standards Passed CSA and CSA-NRTL/C Dimensions Weight Mounting Method
0 to 10 Amps 5 to 25 Amps 25 to 100 Amps
Adj. through entire Amp range* Adj. through entire Amp range*
0.5 to 60 seconds** Manual and 0.5 to 300 seconds** Manual and 0.5 to 300 minutes** 2 seconds***
+2% +10% 600VAC
18 to 30VAC 90 to 135VAC 50 to 60Hz
10A@240VAC General Purpose
-40o to 70o C (-40o to 158o F)
#12 - 24 7 in.-lbs. 2 Watts (max.)
LR 46510-35
2.30” L x 1.72” H x 3.55” D
5.5 oz. Surface Mount
* Note: Overcurrent adjustment cannot be set below the undercurrent adjustment nor can the undercurrent adjustment be set above the overcurrent adjustment for proper operation.
** Note: Delays are xed at 0.5 seconds, if not selected as an adjustement. Unit cannot have both trip and restart delay adjustment.
*** Note: Over and undercurrent levels are ignored for 2 seconds from the instant the device sees motor current.
How to order: Available Models:
LSRU-24-AL-2 LSRU-115-OU-1.5 O - Overcurrent
LSRU-24-AL-3 LSRU-115-OU-2 U - Undercurrent LSRU-115-AL-1.5 LSRU-115-OU-3 R - Restart Delay LSRU-115-AL-2 LSRU-115-UE-2 T - Trip Delay LSRU-115-AL-3 LSRU-115-UR-2 E - Extended Restart Delay LSRU-115-FC-1.5 LSRU-115-UR-3 (in minutes) LSRU-115-OR-1.5 LSRU-115-UT-2 AL - Alarm Logic LSRU-115-OR-2 LSRU-115-UT-3 FC - Feed Control LSRU-115-OT-1.5 LSRU-115-OT-2
LSRU-115-OT-3
(605) 348.5580 / (800) 843.8848 / Fax (605) 348.5685
customerservice@symcom.com / technicalsupport@symcom.com