Symcom ISS-105-ISO-F Installation Guide

PumpSaver
®
Model ISS-105-ISO-F
Installation Guide
RELAY#1RELAY
#2
MODEL ISS-105-ISO-F
RELAY#3RELAY#4RELAY
I1 I2 I3 I4 I5 IC
#5
www.pumpsaver.com
Visit our website www.symcom.com
complete product listing!
120 VAC
for our
2880 North Plaza Drive, Rapid City, South Dakota 57702
(800) 843-8848 · (605) 348-5580 · fax (605) 348-5685
www.symcom.com
WARNING: TO PREVENT IGNITION OF FLAMMABLE OR
CAUT ION:
COMBUSTIBLE ATMOSPHERES, DISCONNECT POWER FROM SYSTEM PRIOR TO INSTALLATION OR SERVICE.
Installation must comply with all national, state, and local codes. Personnel trained in intrinsically safe systems should only perform installation of this equipment. Improper installation may result in serious injury or damage. Before proceeding with installation, read and understand these instructions completely. The ISS-105-ISO-F Isolated Switch is UL913 listed as an associated apparatus for interfacing between hazardous and non-hazardous areas. The ISS-105-ISO-F must be installed in a non-hazardous area. Follow SymCom's Control Drawing 105 on the last page of this bulletin for proper installation. All wiring connected to a hazardous location must be separated from all non-intrinsically safe wiring. Description of special wiring methods can be found in the National Electrical Code ANSI/NFPA 70, Article 504 Intrinsically Safe Systems. Check your state and local codes for additional requirements.
INSTALLATION:
1. Mount the ISS-105-ISO-F in a non-hazardous location on a DIN-rail, or by installing two #6-#8 screws into mounting holes provided.
2. Connect wiring per SymCom's Control Drawing 105. Follow all hazardous code requirements while installing wiring to switch input terminals.
OPERATION:
The ISS-105-ISO-F relay, powered by 120VAC, is an isolated switch suitable for applications with switch inputs in a hazardous location. In a powered state, the ISS-105-ISO-F will actuate each output relay within .75 second of the corresponding input switch closing/opening (dependent on positive/negative logic mode). Each red LED illuminates when the corresponding output relay is energized. Each green LED illuminates when the corresponding input is closed.
CHANNEL INVERT:
The inversion adjustment on the side of the product allows all channels to be positive or negative logic. Channels cannot be inverted independently.
Positive Logic:
Invert adjustme nt is fully counte r cloc kwise; the relay will close when the corresponding input closes.
Negative Logic:
Invert adjustment is fully clockwise; the relay will close when the corresponding input opens.
2
08/06
ISS-105-ISO-F SPECIFICATIONS
Control Voltage 108-132VAC Frequency 50/60 Hz Power 4 Watts max. Operating Temperature -20 to 55°C Terminals
Wire AWG 12-20 AWG Torque 6 in.-lbs.
Relay Contacts
B 300 or 480VA @ 240VAC, Pilot Duty
240VAC, 7A max., General Purpose
Entity Parameters
Voc = 16.8 V
Isc= 1.2 mA La= 100mH Ca= 0.39uF
Po = Voc * Isc
4
Provides Intrinsically Safe Circuits in the Following Locations:
Class I, Divisions I & II, Groups A, B, C & D
Class II, Divisions I & II, Groups E, F & G
Class III
Standards Passed
Electrostatic Discharge (ESD) IEC 61000-4-2, Level 3, 6 kV contact, 8 kV air Radio Frequency Immunity (RFI) IEC 61000-4-2, Level 3, 10V/m Fast Transients IEC 61000-4-4, Level 3, 4 kV input power
2 kV inputs/outputs
SymCom warrants its microcontroller-based products against defects in material or workmanship for a period of five (5) years from the date of manufacture. All other products manufactured by SymCom shall be warranted against defects in material and workmanship for a period of two (2) years from the date of manufacture. For complete information on warranty, liability, terms, returns, and cancellations, please refer to the SymCom Terms and Conditions of Sale document.
3
08/06
CONTROL DRAWING 105
Non-Hazardous Location
Supply Voltage
DEVICE MUST BE INSTALLED IN A SUITABLE
BEFORE SERVICING
.
DEVICE MAY ONLY BE REPAIRED BY THE
COMPROMETTRE LA SÉCURITÉ INTRINSÈQUE.
CONTROL DRAWING 105
120VAC
120VAC
Non-Hazar dous Location
Supply Volt ag e
120 VAC
Relay Output Rating
7 Amps @240 VAC Gene ral Purpose Pilot Duty 480VA @240 VAC, B300
Maxi m um Amb ient Temperature Rating
ENCLOSURE
55°C
WARNING!
TO PREVENT IGNITION OF FLAMMABLE OR
COMBUSTABLE ATMOSPHERES, DISCONNECT POWER
MUST BE INSTALLED
IN A SUITABLE ENCLOSURE.
WARNING!
To pr event ignition of flammable or
com busti ble atmospheres , disconnect
MANUFACTURER
WARNING!
power before ser vicing.
SAFETY.
Load
Load
2
1
RELAY#1RELAY#2RELAY#3RELAY#4RELAY
MODEL ISS-105
INTRINSICALLY
SAFE INPUTS
I1 I2 I3 I4 I5 IC
Load
Load4Load
3
IS Supe r Cell
Relay Output Rating
5
7 Amps @ 240VAC Ge neral Purpose Pilot Duty 480VA @ 240VAC, B300
Maximum Ambient Temperature Rating
115 VAC
55°C
#5
INPUT
120 VAC
SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC
AVERTISSEMENT!
LA SUBSTITUTION DE COMPOSANTS PEUT
Hazardous Location
See Notes 1 & 2
See Note 3
Capacitance and inductance of the field wiring from the intrinsically safe equipment to the associated apparatus shall be calculated and must be included in the system calculations as shown i n the table above. Cable capacitance, Ccable, plus intrinsically safe equipment capacitance, Ci, must be less than the marked capacitance, Ca (or Co), shown on any associated apparatus used. The sam e applies for inductance (Lcable, Li and La or Lo, respecti vely). Where the cable capacitance and inductance per foot are not known, the following values shall be used: Ccable = 60pF/ft., Lcable = 0.2µH/ft.
Class I, Divisions I & II, Groups A, B, C & D; Class II, Divisions I & II, Groups E, F & G; and Class III locations
NOTES:
1. Maximum distance between unit and switch contact is 10,000
2. All non-intrinsically safe wiring shall be separated from
3. All s witch contacts shall be non-energy storing, containing no
4. Entity Parameters:
Hazardous Location
Class I, Group A,B,C,D; Class II, Group s E,F,G; and Class III locations
NOTES:
feet.
intrinsically safe wiring. Description of special wiring methods can be found in the National Electrical Code ANSI/NFPA 70, Article 504 Intrinsically Safe Systems. Check your state and local codes for additional requirements.
inductance or capacitance.
1. Maximum distance bet ween unit and switch contact contact is 10,000 feet.
2.All non-intrinsically safe wiring shall be separated from intr insicall y safe wiring per NEC artic le 500 and ANSI/NFPA 70.
3.All switch contacts shall be non-energy storing, containing no inductance or capacitance.
4.Entity Parameters
Voc= 16.8 V
Isc= 1.7 mA
La=0
Voc = 16.8V Ca = 0.39µF
Ca=0
Isc = 1.2mA Po = Voc * Isc La = 100mH 4
5. Entity Parameter Relationships: IS Equipment Associated Apparatus Vmax (or Ui) Voc or Vt (or Uo) Imax (or Ii) Isc or It (or Io) Pmax, Pi Po Ci + Ccable ≤ Ca (or Co) Li + Lcable La (or Lo)
4
08/06