Symcom ISS-105 Catalog Page

2880 North Plaza Drive • Rapid City, SD 57702 (800) 843-8848 • (605) 348-5580 • FAX (605) 348-5685 www.symcominc.com • email:sales@symcominc.com
Features
Model ISS-105
Intrinsically Safe Switch
Protection
Made in USA
UL 913 listed.* Compact Design Finger safe terminals. DIN rail or surface
mountable. LED state indicator. Isolated output relay for
PLC or control voltage.
The Model ISS-105 IS Super Cell is a “smart” five-channel intrinsically safe relay and pump controller. It can operate in a wide variety of pumping configurations including alternating or non-alternating duplex, duplex separate pump stop (SPS), triplex and quadplex for either pump up or pump down applications. It can also be set up as a simple five channel intrinsically safe relay.
The IS Super Cell has a long list of “smart”features that are needed for multiple pump applications. The IS Super Cell can indicate low, high and out-of-sequence alarms. If an out-of-sequence alarm occurs, the skipped pump(s) will be star ted as intended. The Model ISS-105 can be set up to do non-alternating control, alternating control and alternating control with one non-alternating pump.The non-alternating pump is intended for use as an emergency pump or jockey pump. The IS Super Cell can start the non-alternating pump once every 50 cycles to keep it working freely. Using the built-in DIP switches, individual pumps can be disabled when taken out of service for repair or maintenance. ISS-105 must be installed in a non-hazardous area.Follow SymCom’s Control Drawing 105 for proper installation (See ISS-105 installation guide).
12/04
*Meets all new
requirements for
UL 913 sixth edition,
August 8, 2002!
Additional Features
•Five intrinsically safe input channels meeting UL 913 Sixth Edition,August 8,2002
•Four normally open output relays & one SPDT output relay
•Field selectable pump control options
•Duplex pump control
•Duplex SPS (Separate Pump Stop) pump control
•Triplex pump control
•Quadplex pump control
•Out-of-sequence alarm
•High and/or low alarm options depending on number of pumps and settings
•Audible alarm output
•Meets IEC EMC standards for Electrical Fast Transients (EFT),Electrostatic Discharge (ESD) and Radio Frequency Immunity (RFI)
•DIN rail or surface mount in one package
•User selectable alternator/non-alternator option
•Non-alternating pump option for emergency or jockey applications
•Pump disable switches
•Delay on make timer for all lag pumps in all pump control modes
•Delay on make/break timer in five channel ISS mode
•Pump up or pump down control
2880 North Plaza Drive • Rapid City, SD 57702 (800) 843-8848 • (605) 348-5580 • FAX (605) 348-5685 www.symcominc.com • email:sales@symcominc.com
SymCom warrants its products against defects in material or workmanship for a period of two (2) years from the date of manufacture. For complete information on warranty, liability, terms, returns, and cancellations, please refer to the SymCom Terms and Conditions of Sale document.
Specifications
Operating Points
Special Options
SPECIFICATIONS
Supply V oltage ••••••••••••••••••••••120 V AC ±10% Relay Output Rating
General Purpose•••••••••••••••••••••••7 Amps @ 240 VAC Pilot Duty•••••••••••••••••••••••••••••••480 VA @ 240 VAC,B300 Relay Contact Life (Electrical) ••••••••100,000 cycles min. @ rated load Relay Contact Life (Mechanical)••••••10,000,000 cycles
Operating T emperature•••••••••••-20 to 55° C Weight•••••••••••••••••••••••••••••••••1.2 lb Power Consumption•••••••••••••••5 Watts max. Wire range •••••••••••••••••••••••••••12 to 20 AWG Recommended T erminal T orque•••3.5 to 4.5 in. lbs. (max. 6 in. lbs.) Provides intrinsically safe circuits in the following locations:
••••••••••••••••••••••••••••••••••••••••Class I,Groups A,B,C,D;
••••••••••••••••••••••••••••••••••••••••Class II,Groups E,F,G;
••••••••••••••••••••••••••••••••••••••••and Class III
Entity Parameters••••••••••••••••••Voc= 16.8 V
••••••••••••••••••••••••••••••••••••••••Isc= 1.7 mA
••••••••••••••••••••••••••••••••••••••••La= 0
••••••••••••••••••••••••••••••••••••••••Ca= 0
Standards Passed
Electrostatic Discharge (ESD) ••••••••IEC 61000-4-2,Level 3,6kv contact,8kv air. Radio Frequency Immunity (RFI) •••••••IEC 61000-4-2,Level 3,10V/m Fast T ransients••••••••••••••••••••••••••IEC 61000-4-4,Level 3,4kv input power
••••••••••••••••••••••••••••••••••••••••••••2kv Inputs/Outputs
12/04
Model ISS-105
INTRINSICALLY
SAFE SWITCH
.192
3.511
3.750.621
5.025
2.350
FRONT VIEW
TOP VIEW
SIDE VIEW
#1 #2 #3 #4 #5 C
MODEL ISS-105
I
N
T
R
I
N
S
I
C
A
L
L
Y
S
A
F
E
I
N
P
U
T
S
#1
PUMP#1PUMP#2LOW
ALARM
HIGH
ALARM
LOW
ALARM
HIGH
ALARM
OFF LEAD LAG1 COMMON
AUDIBLE
ALARM
MODE 1
DUPLEXER
PUMP DOWN
#2 #3 #4 #5 INPUT
120 VAC
IS Super Cell
Low Alarm Float
Stop Float
Lead Float
Lag 1 Float
High Alarm Float
120 VAC
Pump1Pump
2
Audible Alarm
High
Alarm
Low
Alarm
PUMP
Typical Application:
Duplex Pump Down with High and Low Alarms.
Many other configurations are possible. See users manual for more details.