Symcom ISS-102AA-DCS Catalog Page

Intrinsically-Safe Dual-Channel Switch
ISS-102
SymCom’s ISS-102AA-DCS is a dual-channel switch with two form-A output relays. The input resistance threshold is fixed at 100kΩ. Each output contact closes upon closure of its associated input switch (input resistance <100kΩ). Resistance probes or switches can be used on the inputs.
The ISS-102AA-DCS has a 0.5-second debounce time delay—the output contact will not change states until a condition exists for 0.5 second—to prevent nuisance actuation and rapid cycling.
Green LEDs illuminate on the ISS-102AA-DCS when the associated output relay is energized.
Model ISS-102AA-DCS
orders@symcom.com / customerservice@symcom.com
(605) 348.5580 / (800) 843.8848 / Fax (605) 348.5685
Specifications
Functional Specifications:
Entity Parameters:
Hazardous Locations
Adjustments/Settings Sensitivity (for resistive probes) Mode Debounce Time Delay
Input Characteristics:
Supply Voltage: Frequency:
Output Characteristics:
Relay Output Rating: 2 - Form A
LEDs (green)
General Characteristics:
Operating Temperature: Terminals: Wire Size Torque Standards Passed: Electrostatic Discharge (ESD) Radio Frequency Immunity (RFI) Fast Transients
Safety Marks: UL Dimensions: Weight: Mounting Methods:
Voc = 16.8V Ca = 0.39μF Isc = 1.2mA Po = La = 100mH 4
Class I, Division I & II, Group A, B, C & D; Class II, Division I & II, Group E, F& G; Class III locations
100kΩ fixed 2-channel switch
0.5 second
120VAC nominal 50/60 Hz
5Amps @ 120VAC General Purpose Pilot Duty 180VA @ 120VAC, C150 Output Relay Status Indicators
-20 to 55
12-20 AWG 6 in.-lbs. (max.)
IEC 61000-4-2, Level 3, 6 kV contact, 8 kV air IEC 61000-4-2, Level 3, 10V/m IEC 61000-4-4, Level 3, 4 kV power terminals, 2kV input/output terminals
UL913 (File #E233355) (LxWxD) 3.5” x 2.1” x 2.5” 9 oz. 35 mm DIN rail or Surface Mount (#6 or #8 screws)
°
C
Voc * Isc
How to order:
Part Number: ISS-102AA-DCS
orders@symcom.com / customerservice@symcom.com
(605) 348.5580 / (800) 843.8848 / Fax (605) 348.5685