Symcom ISS-101 Installation Guide

Installation Instructions for
ISS-101 Isolated Switch
WARNING:TO PREVENT IGNITION OF FLAMMABLE OR COMBUSTIBLE
ATMOSPHERES, DISCONNECT POWER FROM SYSTEM PRIOR TO INSTALLATION OR SERVICE.
CAUTION: Installation must comply with all national, state, and local codes.
Installation of this equipment should only be performed by personnel trained in intrinsically safe systems. Improper installation may result in serious injury or damage. Before proceeding with installation, read and understand these instructions completely.
The ISS-101 Isolated Switch is UL913 listed as an associated apparatus for interfacing between hazardous and non-hazardous areas. The ISS-101 must be installed in a non-hazardous area. Follow SymCom's Control Drawing 101 on the back of this sheet for proper installation.
All wiring connected to a hazardous location must be separated from all non-intrinsically safe wiring. Description of special wiring methods can be found in the National Electrical Code ANSI/NFPA 70, Article 504 Intrinsically Safe Systems. Check your state and local codes for additional requirements.
WARNING: REMOVE POWER FROM SYSTEM PRIOR TO INSTALLING OR SERVICING
THE ISS-101 RELAY.
Installation:
1.Mount the ISS-101 in a non-hazardous location on a DIN-rail, or by installing two #6-#8 screws into the octal base mounting holes provided.
2.Connect wiring per SymCom's Control Drawing 101. Follow all hazardous code requirements while installing wiring to switch input terminals 1 and 8.
Operation:
The ISS-101 relay is powered with 115VAC and is designed as an isolated switch suitable for applications with switch inputs in a hazardous location.In a powered state, the ISS-101 will close its output relay when the input switch is closed.The green LED on the cover will illuminate when the relay is energized and extinguish when the relay is de-energized.
2880 North Plaza Drive • Rapid City, SD 57702 (800) 843-8848 • (605) 348-5580 • FAX (605) 348-5685 www.symcominc.com • email:sales@symcominc.com
CONTROL DRAWING 101
Non-Hazardous Location
Supply V oltage
90 - 120 VAC
Relay Output Rating
8 Amps @120 VAC General Purpose Pilot Duty 180 VA @115 VAC, C300
Maximum Ambient Temperature Rating
55° C
UL listed when used with Part No. OTO8, manufactured by Custom Connector Corp. or Part No.PF083A-E, manufactured by OMRON
MUST BE INSTALLED
IN A SUITABLE ENCLOSURE.
WARNING!
To prevent ignition of flammable or
combustible atmospheres, disconnect
power before servicing.
Hazardous Location
Class I, Group A,B,C,D; Class II, Groups E,F,G; and Class III locations
NOTES:
1. Maximum distance between unit and switch contact is 10,000 feet.
2. All non-intrinsically safe wiring shall be separated from intrinsically safe wiring per NEC article 500 and ANSI/NFPA 70.
3. All switch contacts shall be non-energy storing, containing no inductance or capacitance.
4. Entity Parameters
Voc= 16.8
Isc= 1.7 mA
La= 0
Ca= 0
2880 Nor (800) 843-8848 • (605) 348-5580 • F www
th Plaza Dr
.symcominc.com • email:
iv
V
e • Rapid City, SD 57702
sales@symcominc.com
AX (605) 348-5685
Rev.A
7/03
Loading...