![](/html/2f/2f99/2f99a0d13597c1c6ad5f11e4505028e9e451797ee6991ac72584e94e675d51db/bg1.png)
Alternating Relay
Model ALT-XXX-1-SW
Features:
• Single oat input and two isolated Form C
relay outputs (DPDT)
• Debounce time delay (1 second)
• LED load indicators
• Built-in switch to manually force a specic
load (pump) to operate
• UL508 listed
• CE marked
• 11-pin plug in; DIN rail or surface mount
• 5-year warranty
• Made in the USA
Alternating relays are used to alternate between two loads and are
commonly used in duplex pump-up and pump-down applications
to balance the runtime of both pumps.
The ALT-xxx-1-SW alternating relays are 11-pin octal base plug-ins,
available in two different single-phase voltage ranges. The ALT100-1-SW is used for 95-120VAC applications and the ALT-200-1SW is used for 190-240VAC applications. Both models are designed
for a single oat input and feature two isolated Form C relays
(DPDT) outputs with two LEDs to indicate the energized load.
The ALT relays have a built-in debounce time delay that prevents
the relay from changing state if the oat momentarily bounces, and
they have a built-in switch to manually force a specic load (pump)
to operate each time the input oat closes. This is helpful when
performing periodic maintenance or pump repair.
(605) 348.5580 / (800) 843.8848 / Fax (605) 348.5685
customerservice@symcom.com / technicalsupport@symcom.com
Rev. 0210
![](/html/2f/2f99/2f99a0d13597c1c6ad5f11e4505028e9e451797ee6991ac72584e94e675d51db/bg2.png)
Specications
Functional Characteristics
Debounce Time Delay 1 second
Input Characteristics
Supply Voltage
ALT-100-1-SW
ALT-200-1-SW
Frequency
Output Characteristics
Output Contact Rating - DPDT
Pilot Duty
General Purpose
General Characteristics
Ambient Operating Temperature
Maximum Input Power
Relative Humidity
Terminal Torque
Wire Gauge
Standards Passed
Electrostatic Discharge (ESD)
Radio Frequency Immunity (RFI), Radiated
Fast Transient Burst
Surge Immunity
IEC
ANSI/IEEE
Hi-potential Test
Safety Marks
UL listed (OT11 octal socket required)
CE
Dimensions
Weight
Mounting Method
95-120VAC
190-240VAC
50/60 Hz
480VA @ 240VAC
10A @ 240VAC
-40o to 70o C (-40o to 158o F)
5 W
10-95%, non-condensing per IEC 68-2-3
12 in.-lbs.
12-22 AWG Solid or stranded
IEC 61000-4-2, Level 3, 6kV contact, 8kV air
150MHz, 10V/m
IEC 61000-4-4, Level 3, 3.5kV input power and controls
IEC 61000-4-5, Level 3, 4kV line-to-line; Level 4, 4kV line-toground
C62.41 Surge and Ring Wave Compliance to a level of 6kV
line-to-line
Meets UL508 (2 x rated V + 1000V for 1 minute)
UL508 (File #E68520)
IEC 60947-6-2
2.330” H x 2.375” W x 4.125” D (with socket)
9 oz.
Plugs into 11-Pin OT11 Socket; DIN Rail or surface mount
Enclosure Dimensions
3
4
2
5
6
7
(60.331)
8
9
2.375”
1
11
10
BOTTOM
1.75”
(44.55)
4.125”
(104.65)
How to order:
Part Number: ALT-100-1-SW
ALT-200-1-SW
SIDE
WITH OT11* SOCKET
Auxiliary Products:
OT11-PC (11-pin octal socket)
(605) 348.5580 / (800) 843.8848 / Fax (605) 348.5685
customerservice@symcom.com / technicalsupport@symcom.com