Symcom 77C-KW/HP, 77C-LR-KW/HP Catalog Page

2880 North Plaza Drive • Rapid City, SD 57702 (800) 843-8848 • (605) 348-5580 • FAX (605) 348-5685 www.symcominc.com • email:sales@symcominc.com
9/04
Features
UL listed as an overload relay.
15 parameters can be programmed for maximum protection.
Digitally programmable for precise customization.
Last fault memory provides instant troubleshooting diagnostics.
Recordable voltage, current, last four faults, KWh usage, and power factor with communications package.
Compact design saves precious panel space.
Protects Single-Phase motors from:
• Overload
• Underload
• Jams
• Low voltage
• High voltage
• Rapid cycling
Additional Features:
• Fully programmable
• CSA approved
• CE compliant
• UL and cUL listed
• Automatic or manual reset
• Tamper guard
• RS485 communication port (with pn RS485MS-2W)
• Remote reset
• Surface and DIN rail mount
• Alphanumeric LED diagnostic display
• Last fault memory
• 5-year warranty
• Made in USA
The Model 77C-KW/HP has important advantages over current monitors in many protection applications. Any motor load that has a small or very non-linear change in current vs.load requires the use of a power monitor for underload, dry run and dead-head protection. The change in power vs. load is more linear for most motor loads and is greater in magnitude than the change in current in all motor loads. This is because power measurements take into account both power factor (pf) and current.
Small motors, those under 3 hp and especially fractional horsepower, exhibit small changes in current vs. load, but the change in power is large. When larger motors are derated (run below their rated horsepower) the change in current is small vs. load, but again, the change in power is large and linear. Other typical applications include slower speed mixer or agitator motors up to 50 hp and beyond. These motors and others that run slower than around 3400 rpm usually have small current changes vs.load.
Magdrive and can pumps tend to be small horsepower, positive displacement­type pumps. These pumps need the high sensitivity of a power monitor to protect them from dry run using the underpower feature and dead-head conditions using the underpower feature if the motor decouples from the pump, and the overpower feature if the motor does not decouple.
The built-in UL Listed/CSA approved overload, current unbalance, reverse phase, single-phase and other protection features are significant benefits over similar products. The Modbus communications capability allows this device to be directly integrated with the SymCom RM-1000 and RM-2000 remote displays or other remote monitoring and control equipment.
77C-KW/HP
77C-LR-KW/HP
Overload Relay
Engineered
Protection
2880 North Plaza Drive • Rapid City, SD 57702 (800) 843-8848 • (605) 348-5580 • FAX (605) 348-5685 www.symcominc.com • email:sales@symcominc.com
9/04
SymCom warrants its microprocessor-based products against defects in material or workmanship for a period of five (5) years from the date of manufacture.All other products manufactured by SymCom shall be warranted against defects in material and workmanship for a period of two (2) years from the date of manufacture.For complete information on warranty, liability, terms, returns, and cancellations, please refer to the SymCom Terms and Conditions of Sale document.
Specifications
Operating Points
Special Options
77C-KW/HP & 77C-LR-KW/HP
Overload Relay
* If J Prefix is displayed in trip class setting, jam protection is
enabled. If programmed to Lin position, overcurrent trip delays are fixed linear-type delays set in OPT1 position.
**RD2 & RD3 can be changed from minutes to seconds
under program position OPT2.
0 Minutes Minutes 1 Minutes Seconds 2 Minutes Minutes 3 Seconds Seconds
SETTING RD2 RD3
SPECIFICATIONS OVERLOAD RELAY
Electrical
Input Voltage 100-240 VAC, 1Ø Frequency 50-60 Hz Motor Full Load Amp Range - 77C-KW/HP 2-25 Amps, 3Ø(Loops Required)
26-90 Amps, 3Ø(Direct) 91-800 Amps, 3Ø(External CT's)
Motor Full Load Amp Range - 77C-LR-KW/HP 1.0 Amps - 2.5 Amps (1 Loop)
2.0 Amps - 9.0 Amps (Direct) Short Circuit Withstand Rating 100kA per UL and CSA Power Consumption 5W (Maximum) Output Contact Rating SPDT (Form C) Pilot duty rating: 480 VA @ 240 VAC
General purpose: 10A @ 240 VAC
Expected Life
Mechanical
1 x 106 operations
Electrical
1 x 105 operations at rated load
Accuracy at 25° C (77° F)
Voltage ±1% Current ±3% (Direct, No External CT's) Timing 5% ± 1 second
Repeatability
Voltage ± 0.5% of nominal voltage Current ± 1% (Direct, No External CT's)
Safety Marks
UL UL508, UL1053 CE IEC 60947-1, IEC 60947-5-1
Standards Passed
Electrostatic Discharge (ESD) IEC 1000-4-2, Level 3, 6kv contact, 8kv air Radio Frequency Immunity (RFI), Conducted IEC 1000-4-6, Level 3 10V/m Radio Frequency Immunity (RFI), Radiated IEC 1000-4-3, Level 3 10V/m Fast Transient Burst IEC 1000-4-4, Level 3, 3.5 kv input power Surge
IEC 1000-4-5
Level 3, 2kv line-to-line; Level 4, 4kv line-to-ground
ANSI/IEEE C62.41 Surge and Ring Wave Compliance to a level of 6kv line-to-line Hi-potential Test Meets UL508 (2 x rated V +1000V for 1 minute) Vibration IEC 68-2-6, 10-55Hz, 1mm peak-to-peak, 2 hours, 3 axis
Shock IEC 68-2-27, 30g, 3 axis, 11ms duration, half-sine pulse
Mechanical
Dimensions 3.1"H x 5.1 " D x 3.9"W Terminal Torque 7 inch•lb Enclosure Material polycarbonate Weight 1.2 lbs
Maximum Conductor Size Through 777 0.65" with insulation
Environmental
Temperature Range Ambient Operating: -20° - 70° C (-40° - 158°F)
Ambient Storage: -40° - 80° C (-40° - 176°F) Pollution Degree 3 Class of Protection IP20, NEMA 1
Relative Humidity 10-95%, non-condensing per IEC 68-2-3
Programmable Operating Points Range
LV- Low Voltage Threshold 85V - HV Setting HV- High Voltage Threshold LV Setting - 264V MULT- # of Conductors or CT Ratio (XXX:5) 77C: 1-10 Conductors or 100-800 Ratio 77C-LR: 1 or 2 OC- Overcurrent Threshold (20-100A) ÷ MULT or 80-120% of CT Primary CUB- Current Unbalance Threshold 2 - 25% or 999 TC- Overcurrent Trip Class * 5, J5, 10, J10, 15, J15, 20, J20, 30, J30, or LIn (linear) RD1- Rapid Cycle Timer 0, 2 - 500 Seconds RD2- Restart Delay After All Faults Except Undercurrent 2 - 500 Minutes/Seconds
(motor cool down timer)**
RD3- Restart Delay After Undercurrent 2 - 500 Minutes/Seconds
(dry well recovery timer) #RU- Number of Restarts After Undercurrent 0, 1, 2, 3, 4, A(Automatic) ADDR- RS485 Address A01- A99 #RO-Number of Restarts After Overcurrent 0, 1, 2, 3, 4, A(Automatic) LP/PWS (PWS = LP Range) 1 = 0.01 - 0.99 KW 5 = 0.01 - 0.99 HP
2 = 1.00 - 9.95 KW 6 = 1.00 - 9.95 HP 3 = 10.0 - 99.5 KW 8 = 10.0 - 99.5 HP 4 = 100 - 650 KW 9 = 100 - 650 HP
3.050" (77.47)
2.650" (67.31)
2.280" (57.91)
3.850" (97.79)
3.600" (91.44)
3.100" (78.74)
0.002" (5.08)
5.050"
(128.27)
4.700"
(119.38)
1.200" (30.48)
D. 0.650" (16.51)
3.600" (91.44)
3.850" (97.79)
ABC
SYMCOM RECOMMENDS USING CTs WITH TERMINALS TO SIMPLIFY INSTALLATION.
NOTE: PHASES A & C ARE INACTIVE. USE PHASE B FOR ALL ACTIVE CURRENT MEASUREMENTS. CT SECONDARY MUST MAKE FIVE PASSES THROUGH THE PHASE B CONDUCTOR WINDOW. NOTE: OTHER NECESSARY CONNECTIONS ARE NOT SHOWN
L1
CONTACTOR
COIL
CONTROL POWER
START
STOP HAND
AUTOPILOT
M
A
TO MOTOR
BC
OFF
240 VAC OR LESS
NOTE: PHASES A&C ARE INACTIVE
L2