BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION!
FOLLOW NATIONAL, STATE AND LOCAL CODES.
READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION.TION.
WARNING!
Hazardous Voltage. Failure to follow these instructions can result in death,
Power must be disconnected prior to attaching and/or using the battery cable.
Damage to the device or serious injury may occur if the battery programming feature is used
while power is applied. Always follow proper safety procedures for removing and securing the
power source before connecting the battery cable.
The battery cable cannot be used when power is applied to the device. To program the device
when it is powered, the user must utilize a network programming option.
The 777-MV-P2 is an electronic overload relay that is fully programmable for customized protection.
The 777-MV-P2 is designed to protect 3-phase systems operating at medium voltage ranges. The
output relay is a Form C contact, which can control a contactor or other device within the output
relay contact rating. Typical applications can include pumps, grinders, and other 3-phase medium
voltage applications.
The 777-MV-P2 can be safely programmed prior to installation by supplying power with a 9V battery.
See Figure 5 in the PROGRAMMING section. DO NOT connect the battery to the unit when line
voltage is present. The 777-MV-P2 cannot
a 9V battery. For testing purposes, 3-phase power must be used with a minimum voltage of
100VAC. Follow all safety warnings when dealing with hazardous voltages.
CONNECTIONS
1. Disconnect power and verify line and control power are off.
2. Using the four corner tabs or the DIN rail mount, install the 777-MV-P2 directly above or below
the contactor. To mount on a DIN rail, hook the top clips first then apply downward pressure until
the lower clips snap onto the rail.
3. External CTs (current transformers) are required. SymCom recommends using CTs with terminal
connections for easier installation. All CT secondaries must make one or two passes through the
round holes on the MotorSaver®Plus according to Table 1. See Figure 2 for a typical wiring
diagram.
4. a) 3-phase voltage input: 100-240VAC, 3-phase voltage can be made available by using three
potential transformers in a wye-wye configuration. Reverse-phase protection, single-phase
and unbalance protection are available when using the wye-wye configuration shown in
Figure 4A. The motor will not start under these voltage fault conditions. Connect the 3-phase
be tested for proper operation or communications using
power from the secondary of the potential transformers to L1, L2 and L3 on the Model 777MV-P2 using #12-18 AWG wire.
b) 3-phase voltage input: Alternatively, 100-240VAC, 3-phase voltage can be made available
by connecting two potential transformers in an open delta configuration (Figure 4B).
c) Single-phase voltage input: If only single-phase, 120V control power is available, insert
control power into L1 and L2 inputs (Figure 4C). L3 must not be connected.
phase voltage input is used, single-phase faults are detected only after the motor starts and
reverse-phase protection is not available.
NOTE: Pay close attention to the wiring diagrams to eliminate any errors when communicating
power factor information over a network. The L2 phase conductor must pass through the B
current measurement hole for proper operation. VUB must be set to 999 for proper operation
with a single-phase voltage input.
5. Connect the 3-phase (or single-phase) power from the secondary side of the potential
transformer terminals using 12-18 AWG copper wire according to Figure 1 These should be
tightened to 7 in.-lbs., max.
6. Connect the control circuit wires to the appropriate terminals. The relay is designed for fail-safe
operation; the NO (normally open) contact should be in series with the coil on the contactor for
motor control (see Figure 1). For alarm circuits, the NC (normally closed) contact is in series with
the alarm circuitry.
(rectangle). Every CT secondary must make one or two passes through the corresponding main conductor
window. SymCom recommends using CTs with terminals to simplify installation.
3
All potential transformers typically have 120VAC secondaries. The 777-MV-P2 may be installed with 3phase voltage input (Figures 4A & 4B) for full voltage monitoring and protection. If the single-phase voltage
input is used (Figure 4C), the 777-MV-P2 is a current monitor only.
To program prior to installation, connect the 9V battery cable to the pins on the left side of the unit
(when looking at the display), and then attach a standard 9V battery to the cable. See Figure 5. The
9V battery cable is keyed for proper installation. If the cable is connected improperly, the 777-MV-P2
will not power the display. DO NOT connect the battery when line voltage is present. The 777-MVP2 cannot
purposes, power must be used with a minimum voltage of 100VAC. Follow all safety warnings when
dealing with hazardous voltages.
1. Rotate MODE SELECT to the parameter to be programmed. It is recommended that LV be
2. Press and hold the RESET/PROGRAM button.
3. While holding the RESET/PROGRAM button, rotate the DISPLAY/PROGRAM knob until the
4. Release the RESET/PROGRAM button. This stores the new parameter in the nonvolatile
5. Move clockwise through the positions to complete the process. Continue steps 1-4 until all
be tested for proper operation or communications using a 9V battery. For testing
programmed first.
proper setting for the parameter that is being programmed is displayed.
memory. If the number changes back to what it was before programming, then the tamper guard
is on and will need to be unlocked before programming can be completed (see Tamper Guard).
The following settings MUST be programmed by the user in order to provide proper protection for
the application. Settings vary by situation and application and should be selected and tested for
each unique installation. All parameters are actual values except for the VUB and CUB settings;
these are programmed as percentages. The range each parameter can be programmed is found in
the electrical specifications table. See Programming Examples for sample setup instructions.
Failure to program all setpoints could result in nuisance tripping or prevent the device from
protecting the motor. Always use the proper CTs for the motor full load amperage (FLA).
LV/HV - Low Voltage/High Voltage. The recommended settings for LV (low voltage) and HV (high
voltage) according to the NEMA MG1 standard are ±10% of the motor’s nameplate voltage.
Generally, the motor manufacturer should be contacted to verify these limits. High and low
voltage trips are based on average voltage measured. Never set LV higher than HV.
VUB - Voltage Unbalance. The NEMA MG1 standard does not recommend operating a motor
above a 1% voltage unbalance without derating the motor. Voltage unbalance is determined
from the following formula: % Voltage Unbalance = [(Maximum Deviation from the Average)
/ Average] x 100% The NEMA MG1 standard also recommends against operating a motor
above a 5% voltage unbalance under any circumstances. Therefore, a setting below 5 is a
good place to start but SymCom recommends consulting the motor manufacturer for
specific tolerances.
NOTE: A setting of 999 will disable reverse-phase, single-phase and voltage unbalance
protection. This setting should be used when single-phase voltage control power is used.
Single-phase faults will only be detected from current measurements after the motor starts.
The unit will only read and display voltage on one phase (L1-L2) even if 3-phase power is
applied.
Example: Measured line-line voltages from the face of the 777-MV-P2, which read the
secondary side of a wye-wye potential transformer configuration, = 118, 121 and 117.
The average voltage is (118+121+117)/3 = 118.7. The maximum deviation from the
average is the greatest difference between the average voltage (118.7) and any one
voltage reading: 118-118.7 = 0.7, 121-118.7=2.3 and 117-118.7=1.7. The maximum
MULT - MULT (multiplier) setting is found in Table 1. The MULT setting is determined by the number
OC - Overcurrent. Is typically set to the service factor amperage (SFA) of the motor or 100-135%
NOTE: When using external CTs, do not set OC greater than the thermal rating of the CTs
UC - Undercurrent. Is most commonly set to 80% of the full-load amperage (FLA) of the motor.
CUB - Current Unbalance. SymCom recommends contacting the motor manufacturer for a
deviation from the average is 2.3, thus voltage unbalance = 2.3/118.7 x 100= 2.0%.
of passes of the leads from the secondary side of the external CTs and the full load amps of
the motor the unit will be monitoring. MULT sets the trip point range for undercurrent,
overcurrent and ground fault current faults. Set MULT first, then set UC, OC and GF.
of motor full-load amps (FLA), which are determined by the motor manufacturer. The value
must be higher than UC. If any one leg exceeds the OC setting, the 777-MV-P2 will trip
according to the Trip Class (TC) settings.
This is usually adequate for protection of loss of load for many pumps and motors, including
submersibles. If the motor is drawing less than full load amperage, then the UC may be set
lower than 80% of FLA for adequate protection. Centrifugal/booster pumps may have to be
set to something higher than 80% of FLA for adequate protection. UC can be set to 0 if UC
protection is not desired. The 777-MV-P2 examines average current to determine if an
undercurrent trip condition exists. The value must be lower than OC
specific setting. Current unbalance is calculated the same way voltage unbalance is
calculated (see formula above). Setting CUB to 999 will disable current unbalance and
current single-phase protection.
TC - Trip Class. Determines how quickly the 777-MV-P2 will trip when an overcurrent (overload)
condition is detected. TC is a dual-function setting—both a thermal trip class (NEMA
standard) and a linear trip delay (in seconds) can be set.
While the standard trip classes are 5, 10, 15, 20, and 30, TC can be set from 2–60, with or
without jam protection. The trip class setpoint is the time in seconds that the device will take
to trip when any phase current is greater than or equal to 600% of the OC setpoint. These
additional “non-standard” trip classes allow the unit to follow a trip curve in-between the
“standard” trip class curves shown in Figure 6.
Trip classes 2–60 can be set from approximately the 7 o’clock to 10 o’clock position with the
DISPLAY/PROGRAM knob. Trip classes J02–J60, which include jam protection, can be set
from approximately the 10 o’clock to 1 o’clock position. This additional jam protection
feature, when enabled, is initiated 1 minute after the motor starts and provides a 2-second
trip delay for motors exceeding 400% of the OC setting.
The linear overcurrent trip delay can be set from approximately the 1 o’clock to 5 o’clock
position from 0–60 seconds (L00–L60) or to “oFF.” If TC is set to L00, the 777-MV-P2 will
trip off within 1 second after motor current reaches the OC setpoint. If both trip class and
linear trip delay settings are programmed, the 777-MV-P2 will follow the faster trip time. For
example, TC is set to J15 and L20, and the amperage is 200% of the OC setting. Following
the trip class 15 curve, the 777-MV-P2 will trip off in approximately 100 seconds. Thus the
777-MV-P2 will follow the linear trip delay setting, because it is faster, and will trip off in 20
seconds.
The motor manufacturer should be contacted for an exact TC setting. Table 3 describes the
trip classes, and Figure 6 shows the trip class curves.
RD1 - Restart Delay One. Rapid-cycle timer, in seconds (default). The purpose of this timer is to
provide protection against short cycling and to allow adequate cool down time between
motor starts. This timer is initiated when power is first applied to the unit. If no voltage fault
conditions exists, the output relay will energize (the NO will close and the NC will open) as
soon as RD1 timer expires. In most cases, this is set to 20-30 seconds. This should provide
adequate protection for successive power outages or short cycling caused by other motor
controls. This timer is also initiated when motor current goes to zero. Setting RD1 to zero
will turn off this feature and ensure that when an alarm circuit is used, an alarm will sound
only when there is a fault or power to the unit is lost.
RD2 - Restart Delay Two. Referred to as a motor cool-down timer, in minutes (default). RD2 is
used to restart the motor after a trip due to a current unbalance, current single-phasing, or
an overcurrent condition. A setting of 5-10 minutes will give most motors adequate time to
cool down after an overcurrent condition. The motor manufacturer should be contacted for
an exact value.
RD3 - Restart Delay Three. This timer, in minutes (default), only initiates after an undercurrent trip
and is referred to as a dry-well recovery timer in pumping applications. This is set according
to the time it takes for the well to recharge after pumping dry. This setting varies widely by
application and there is no typical setting. RD3 can be set from 2-500 minutes or to A to
enable the automatic Dry-Well Recovery Calculator.
The Automatic Dry-Well Recovery Calculator allows the 777-MV-P2 to automatically select
a restart delay based on the run time of the last run cycle before tripping on an undercurrent
fault. Table 2 shows the next restart delay vs. run time. In general, a longer run time
produces a shorter restart delay. This feature allows the 777-MV-P2 to optimize running and
rest times automatically.
Run Time
> 1Hr 6 10
30 min.- 59.99 min. 15 4
15 min.- 29.99 min. 30 2
#RU/ADDR - Restart Attempts (undercurrent)/Address. The #RU/ADDR is a dual-function setting.
#RU settings are displayed and selected by turning the DISPLAY/PROGRAM knob from
approximately the 7 o’clock to 12 o’clock position. ADDR settings are displayed and
selected by turning the DISPLAY/PROGRAM knob from approximately the 12 o’clock to 5
o’clock position.
#RU is the number of restarts the 777-MV-P2 will attempt after an undercurrent fault before
the unit locks out and requires a manual reset. #RU can be set to 0, 1, 2, 3, 4, or A. This
counter is cleared one minute after restarting if the 777-MV-P2 does not trip again on
undercurrent.
If #RU is set to “0”, the 777-MV-P2 will require manual resetting after all undercurrent faults.
If #RU is set to “A”, the 777-MV-P2 will always automatically restart after undercurrent
faults, once the RD3 timer expires.
ADDR is the RS-485 address of the 777-MV-P2 and is only used when communicating with
any external communication device. The address can be set from A01–A99.
#RF/COM - Restart Attempts (other faults)/Communications Settings. The #RF settings are
displayed and selected by turning the DISPLAY/PROGRAM knob from approximately the 7
o’clock to 12 o’clock position. COM settings are displayed and selected by turning the
DISPLAY/PROGRAM knob from approximately the 12 o’clock to 5 o’clock position.
#RF is the number of restarts the 777-MV-P2 will attempt after current unbalance or current
single-phase faults before the unit locks out and requires a manual reset. This counter will
be cleared one minute after start-up if the unit does not trip again for the same fault
condition. Available settings are 0, 1, 2, 3, 4 and A, or to include overcurrent faults, #RF can
be set to oc1, oc2, oc3, oc4 or ocA.
If #RF is set to “0”, the 777-MV-P2 will require manual resetting after all current unbalance,
current single-phase and overcurrent faults.
If #RF is set to “A”, the 777-MV-P2 will always restart automatically after current unbalance
and current single-phase faults, once the RD2 timer expires. Overcurrent faults will require
a manual reset.
If #RF is set to “ocA”, the 777-MV-P2 will always restart automatically after current
unbalance, current single-phase and overcurrent faults, once the RD2 timer expires.
COM determines the baud rate, even/odd parity, and stop bit. COM can be set to C00-
C07. C00 and C04 are duplicates provided for backward compatibility.
• C00 = 9600 baud, No parity, and 1 stop bit
• C01 = 9600 baud, Odd parity, and 1 stop bit
• C02 = 9600 baud, No parity, and 1 stop bit
• C03 = 9600 baud, Even parity, and 1 stop bit
• C04 = 19200 baud, No parity, and 1 stop bit
• C05 = 19200 baud, Odd parity, and 1 stop bit
• C06 = 19200 baud, No parity, and 1 stop bit
• C07 = 19200 baud, Even parity, and 1 stop bit
UCTD - Undercurrent Trip Delay. The length of time, in seconds (default), the unit will allow the
motor to run in an undercurrent situation before de-energizing its relay. Typically, UCTD is
set to 2-4 seconds to allow for motor to reach full load.
GF - Ground Fault. The maximum allowable current that can flow to ground before the 777-MV-
P2 de-energizes its relay. This is a residual, class II ground fault system and should not be
used for personnel safety. A typical setting for GF is 10-20% of motor FLA (in amps). GF
may be set to oFF if this feature is not desired. The GF test procedure in this installation
instruction manual must be conducted before the device is brought online.
The relay operation of the Model 777-MV-P2 is designed to be fail-safe. This means when the
voltage is within the programmed limits, the relay will energize—the NO contact will close and the
NC contact will open. When the unit loses power or senses a fault condition, the relay will deenergize and contacts will return to their original state. Once the unit has been installed and
programmed, the unit is ready to operate. Turn MODE SELECT to the RUN position. The display will
show “run” alternating with a number (the number displayed will be the number corresponding to
where the DISPLAY/PROGRAM knob is pointed). It will do this for the restart delay time
programmed into RD1. Once the timer expires, the relay will energize—the NO contact will close
and the NC contact will open. If something other than this is displayed, see the troubleshooting
section for more information. If MODE SELECT is taken out of RUN, the 777-MV-P2’s relay will deenergize.
Trip Class Application Description
5
10
15 Specialized applications
Small fractional horsepower motors where acceleration times are almost
instantaneous or where extremely quick trip times are required
(Fast Trip) Hermetic refrigerant motors, compressors, submersible pumps
and general-purpose motors that reach rated speed in less than 4 seconds
20
30
(Standard Trip) Most NEMA-rated general-purpose motors will be protected
by this setting
(Slow Trip) Motors with long acceleration times (>10 seconds) or high inertia
loads
Programming any of the trip classes with the J prefix will enable jam
J Prefix
(Jam Protection)
protection. This additional protection is enabled 1 minute after the motor
starts and provides a 2 second trip time for motors exceeding 400% of the
OC setting
Non-Standard
Trip Classes
Trip time in seconds when any phase current is 600% of OC. Time is
approximately 90% of the TC setting
NOTE: Since no network communications are connected in these examples there are no setting
changes needed for ADDR or COM.
Example #1
3-phase, 4160 Volt, 400 hp vertical hollow shaft pump with a full load amperage of 56.2A and
maximum service factor amps of 61.6A. Three potential transformers (4160/120) have been installed
in a wye-wye configuration to allow 3-phase voltage protection. This voltage monitoring will prevent
the motor from starting on a reverse-phase, single-phase or unbalance condition.
LV- 120 x 0.90 = 108
HV- 120 x 1.10 = 132
VUB- Manufacturer suggests 3
MULT- From Table No. 1, MULT=75 (with 75:5 CTs)
OC- Service Factor Amperage = 61.6
UC- FLA x 0.80 = 56.2 x 0.80 = 45.0
CUB- Manufacturer suggests 5
TC- From Table 3, general purpose motor, TC = 20
Linear Trip = Off
RD1- To protect the pump from rapid cycling, setting RD1 = 300 seconds will reduce the
number of starts per hour.
RD2- Because the pump is large, a cool-down time of 30 minutes should be appropriate,
RD2 = 30.
RD3/#RU- The well history shows that it will fully recover in two hours. RD3 = 120 minutes.
#RF- This well is known for sand to jam the impeller, therefore "oc" should be included so
the pump will automatically restart after an overloaded condition. History shows that 1
start attempt usually clears the sand out of the impeller. #RF = oc1
UCTD- Setting UCTD = 10 will allow normal operation and not allow the motor to run too long
in an undercurrent fault condition.
GF- Because it may take several days to get a new pump motor and schedule for
maintenance personnel to remove and replace the pump motor, GF setting of 10% of
full load amperage will give the well owner enough time to prepare for pump
Motor To Be Protected: 3-phase , 4160 Volt, 200 hp air compressor with a full load amperage rating
of 27A and maximum service factor amps of 30A. Use the following calculations and reasoning to
determine the appropriate settings for this application. One 4160/120 potential transformer is used
for control power. Voltage monitoring and reverse-phase protection is not implemented.
LV- 120 x 0.90 = 108
HV- 120 x 1.10 = 132
VUB- Since L3 is not connected, VUB = 999
MULT- From Table No. 1, MULT = 50 (with 50:5 CTs)
OC- Service Factor Amperage = 30
UC- FLA x 0.80 = 27A x 0.80 = 21
CUB- Manufacturer suggests 5
TC- General purpose motor, TC = 20
RD1- Since this compressor takes about 60 seconds to bleed off excess pressure after a
shutdown, setting RD1 = 120 seconds will allow the compressor to unload before being
restarted.
RD2- Because the motor may be hot from running in an unbalance or single-phase condition,
a motor cool down time of 20 minutes, RD2 = 20, should be appropriate.
RD3- Because an undercurrent would signal a serious problem in this application (a broken shaft
or belt), #RU should be set = 0 for manual reset. Therefore, RD3 has no function.
#RU- #RU = 0 (see RD3 setting)
#RF- Because an overload (overcurrent) fault signals a serious problem in this application (e.g.,
worn bearings), "oc" should not be included in the #RF setting so that a manual reset after
an overload fault is required. #RF = 1 will give the system 1 chance to recover from an
unbalance or single-phasing problem before a manual reset is required.
UCTD- Setting UCTD = 5 will allow normal operation and not allow the motor to run too long in an
undercurrent fault condition.
GF- A ground fault setting of 15% of full load amps will be a significant indicator that the motor
should be evaluated for repair or replacement. Thus, GF = 27A x 0.15 = 4.0.
On power up, the 777-MV-P2 will show the current software revision. For example if the software
revision is 33.04, the 777-MV-P2 will show 033 followed by 004.
The output display can show one of the following parameters when MODE SELECT is in RUN: L1L2, L2-L3, and L3-L1 line voltage; %VUB; A, B, and C phase current; %CUB; measured GF current.
The display is used for programming the operating parameters of the device and also identifies what
caused the unit to de-energize its relay or what is keeping the unit from energizing its relay, and
under normal operating conditions, what the last fault was. The last fault can be displayed by
pressing and holding the RESET/PROGRAM button while MODE SELECT is in RUN. When the unit
trips off or is holding the motor off, the current fault condition will be shown in the display without
pressing the button (CAUTION: pressing the reset button at this time will reset the unit). Table 4 lists
the fault codes the unit could display.
Displayed
Message
oc Tripped on overcurrent
SP
ub
uc Tripped on undercurrent
CF
GrF Tripped on ground fault
HI A high voltage condition exists (won’t allow motor to start)
Lo A low voltage condition exists (won’t allow motor to start)
rP Incoming phases have been reversed, the motor may run backwards if started
oFF A stop command was issued from a remote source
HPr Tripped on high power
LPr Tripped on low power
CLo Tripped on low control voltage
clr No previous faults
Pro Shown when programming using the battery in the RUN position
FFF Displayed value is greater than 999 (can be due to incorrect MULT setting)
Meaning
Tripped on current single-phasing or unit won’t start because the voltage is
single-phased
Tripped on current unbalance or unit won’t start because the voltage is
unbalanced
Tripped on contactor failure (due to faulty contacts or connections on the load
side)
The 777-MV-P2 will display a fault code alternating with a number or with “run” when it has tripped.
If the unit is showing a fault code alternating with “run,” it is timing down the restart delay. If the fault
code is alternating with a number (voltage reading or zero), the unit will not allow the motor to start
because there is a problem with the incoming voltage. If the display is showing just a fault code, the
unit is in a manual reset mode. This could be because the number of restarts (#RF, #RU) has
expired or is not allowed. If the display reads “oFF,” a stop command was issued through the
communications network or a remote monitor.
PROBLEM SOLUTION
The unit will not start.
Display alternates “rP”
with the
DISPLAY/PROGRAM
parameter value.
The unit will not start.
Display alternates “SP”,
“ub”, “HI”, or “Lo” with the
DISPLAY/ PROGRAM
parameter value.
Display alternates “SP”,
“ub”, or “oc” with “run.”
Display alternates “uc”
with “run.”
Display is showing a solid
“SP”, “ub”, or “oc.”
Display is showing a solid
“uc.”
Display is showing a solid
“CF.”
Display is showing a solid
“GrF.”
Display alternates “LPr” 4
with “RUN”
The voltage inputs are reverse-phased. If this is the initial start-up,
swap any two of the leads connected to L1, L2, or L3 on the 777MV-P2 to correct the problem. If the overload relay has been
previously running, the power system has been reverse-phased.
heck the phase sequence of the incoming power lines. C
Note: L1 must be tapped from conductor Phase A, L2 from B, and
L3 from C for correct power factor measurements on remote
communications.
The incoming voltage is not within the limits programmed in the
VUB, HV, and LV settings. Turn the DISPLAY / PROGRAM knob to
read each incoming line voltage value. Correct the incoming power
problem and check programmed limits by turning MODE SELECT.
Compare incoming values for HV, LV, and VUB to setpoints to
verify they are correct.
The overload relay has tripped on the fault shown on the display
and is timing down RD2 before restarting. No further action is
required.
The overload relay has tripped on undercurrent and is counting
down RD3 before restarting. If undercurrent is not a normal
condition for this installation, check for broken shafts, broken belts,
etc.
The unit has tripped on the fault shown and a manual reset is
required because of the programmed setting in #RF. Check the
system for problems that would produce the single-phase,
overcurrent or current unbalance fault, such as a jam.
The unit has tripped on undercurrent and a manual reset is required
because of the setting in #RU. Check the system for problems that
would produce a loss of load such as a broken belt or a lack of
liquid to pump.
The unit has tripped on current single-phasing, but was not singlephased by the incoming voltage. Check for damaged contacts or
loose or corroded wiring connections.
A ground fault current greater than the programmed GF value has
been detected. Check the motor for insulation breakdown. A
manual reset is required to clear this message. Press the
RESET/PROGRAM button to perform a manual reset.
The overload relay has tripped on low power (LPr) and is timing
down RD3 before restarting. If LPr is not a normal condition for this
installation, check for loss of liquid, closed valves, broken belts, etc.
The last fault stored can be cleared on the 777-MV-P2 by following these steps:
1. Rotate MODE SELECT to GF.
2. Press and hold the RESET/PROGRAM button. Adjust the DISPLAY/PROGRAM knob until “cLr”
appears on the display. Release the RESET/PROGRAM button.
To verify the last fault was cleared, place MODE SELECT in the RUN position. Then press and hold
the RESET/PROGRAM button; “cLr” should be on the display.
TAMPER GUARD
The 777-MV-P2 setpoints can be locked to protect against unauthorized program changes.
1. Rotate MODE SELECT to GF.
2. Press and hold the RESET/PROGRAM button. Adjust the DISPLAY/PROGRAM knob until “Loc”
appears on the display.
3. Release the RESET/PROGRAM button.
4. Turn MODE SELECT to RUN.
The program is now locked, but all settings can be viewed. The unit can be unlocked by following
the same steps except adjust the DISPLAY/PROGRAM knob to “unL” in step 2.
The unit has tripped on low power and a manual reset is required
because of the setting in #RU. Check the system for problems that
would produce a loss of load like a broken belt or a pump is out of
liquid. Press the RESET/PROGRAM button to perform a manual
reset.
The unit has tripped on high power and is timing down RD2. Check
for a high power condition.
The unit has tripped on high power and requires a manual reset
because of the setting in #RF. Press the RESET/PROGRAM button
to perform a manual reset.
The overload relay has tripped on low control voltage (CLo) and is
timing down RD2 before restarting.
The unit has tripped on low control voltage and a manual reset is
required because of the setting in #RF. Verify system voltage is
correct. Press the RESET/PROGRAM button to perform a manual
reset.
4
LPr, HPr, and CLo are enabled only from a network master via a communications module.
A ground fault test must be performed before installing the 777-MV-P2 as required by UL1053
nd NEC, ANSI/NFPA 70. a
1. Disconnect power.
2. Hook up the three line voltages to L1, L2, and L3 as required by the installation instructions.
3. Program the desired parameters into the unit. For test purposes, set MULT to 1 and GF to the
minimum allowed setting.
4. Construct the circuit, using an AC power supply. This circuit simulates a ground fault condition by
generating a current in one of the phases. Alternate test circuits may be used. The only
requirement is the current through the current transformer must be between 115% and 150% of
the GF setting and pass through only one CT window.
5. The values of V and R will be determined by the current required to generate a GF trip condition:
I = Vrms/R, where I = 115% of GF setting.
6. Place the unit in the RUN position, apply 3-phase power and allow the NO contact to close.
7. Energize the test circuit by pushing and holding the test pushbutton until the unit trips (within 8.5
seconds). The display should show “GrF” and the NO contacts should be open. Release the NO
pushbutton.
8. The results of the test are to be recorded on the test form provided below. The form should be
kept by those in charge of the building’s electrical installation in order to be available to the
authority having jurisdiction.
9. Confirm programmed parameters and proceed with installation instructions.
Programmable Operating Points
LV- Low Voltage Threshold 85-262V
HV- High Voltage Threshold 86–264V
VUB- Voltage Unbalance Threshold 2-25% or 999 (disable)
MULT- CT Ratio (XXX:5) 25, 50, 75, 100, 150, 200, 300, 400, 500, 600, 700, 800
OC- Overcurrent Threshold * See Table 1
UC- Undercurrent Threshold * See Table 1
CUB- Current Unbalance Threshold 2–50% or 999 (disable)
TC- Overcurrent Trip Class
5
RD1- Rapid Cycle Timer 0-999 seconds
RD2- Restart Delay After All Faults Except
Undercurrent (motor cool-down timer)
RD3- Restart Delay After Undercurrent (dry-
well recovery timer)
#RU- Number of Restarts After Undercurrent 0, 1, 2, 3, 4, A (Automatic)
ADDR- RS485 Address A01–A99
#RF-Number of Restarts After All Faults
Except Undercurrent
6
COM- Communication setting C00-C07
UCTD- Undercurrent Trip Delay 2–999 seconds
GF- Ground Fault Current Threshold* 6-40% of CT Primary or oFF
Trip Times
Ground Fault Trip Time Trip time
101%-200% of Setpoint 8 seconds ±1 second
201%-300% of Setpoint 4 seconds ±1 second
301%-400% of Setpoint 3 seconds ±1 second
401% or Greater 2 seconds ±1 second
Current Unbalance Trip Times
% Over Setpoint
0%
1%
2%
3%
4%
5%
6%
11%
15%
Input Characteristics
Input Voltage (3-phase) 100-240 VAC
Frequency 50/60 Hz
Motor Full Load Amp Range 10–800A (with the use of external CTs)
Output Characteristics
Output Contact Rating SPDT (Form C) Pilot duty rating: 480VA @ 240VAC, B300
5
If a “J” is included in the trip class (TC) setting, jam protection is enabled.
6
If "oc" is displayed in the #RF setting, overcurrent will be included as an automatic restart after RD2 expires.
Otherwise, a manual reset is required after an OC fault.
Shock IEC 68-2-27, 30g, 3 axis, 11ms duration, half-sine pulse
Mechanical
Dimensions 3.0" H x 3.6" W x 5.1" D
Terminal Torque 7 in.-lbs.
Enclosure Material Polycarbonate
Weight 1.2 lbs
Maximum Conductor Size Through 777-MV-P2 0.65" with insulation
NOTE: The 777-MV-P2 can be programmed prior to installation by connecting a 9V battery. Disconnect power
prior to using the battery cable and follow all safety warnings.
* Do not program the unit above the thermal rating for the CTs.