Symcom 777-TS, 777-LR-TS, 777-575-TS Catalog Page

Page 1
2880 North Plaza Drive • Rapid City, SD 57702 (800) 843-8848 • (605) 348-5580 • FAX (605) 348-5685 www.symcominc.com • email:sales@symcominc.com
01/05
Description
The Model 777-TS is a fully-programmable electronic overload relay. An alphanumeric LED display provides programming and diagnostic information. 17 parameters can be programmed in the Model 777-TS:
2) High voltage 11) Overload restart delay (RD2)
3) Voltage unbalance 12) Underload restart delay (RD3 - dry-well recovery timer)
4) Temp. sensor on/off 13) No. of restarts after an overload (manual or automatic)
5) CT size/loop setting 14) RS-485 address
6) Overcurrent 15) No. of restarts after an underload fault
7) Undercurrent 16) Underload trip delay
8) Current unbalance 17) Ground fault
9) Trip class (5, 10, 15, 20, 30)
Programming the Model 777-TS is an easy four step process: 1) Rotate the MODE SELECT switch to the parameter to be programmed; 2) Press and hold the RESET/PROGRAM button;
3) Rotate the DISPLAY/PROGRAM dial to the desired setting as shown in the LED display; and 4) Release the RESET/PROGRAM button.
An RS-485 port allows the Model 777-TS to be connected to an RM-1000 or RM-2000 remote monitor or directly to a computer or PLC. The RM-2000/777-TS motor management system combines unsurpassed electronic motor protection and critical, user-friendly motor monitoring. SymCom's Solutions software (sold separately) can be used to monitor and control up to 99 Model 777-TSs from a central computer. Using Solutions software, an operator can control motors, view the operating parameters, and record the following operating parameters:
• Line - Line Voltages (Recordable) • Restart Delay Timers
• Line Currents (Recordable) • kWh Usage (Recordable)
• Last 4 Faults (Recordable) • Power Factor (Recordable)
Model 777-TS Model 777-LR-TS Model 777-575-TS
Overload Relays
Engineered
Protection
Recordable voltage, current, last 4 faults, high temperature detection with Subtrol®-equipped pumps, kWh usage, and power factor are available when using communications package.
Digital programming provides precise customization.
Seventeen setpoints can be programmed for maximum protection.
Last fault memory provides instant troubleshooting diagnostics.
The 777-TS is UL and cUL listed as an overload relay.
RS-485 port can be used to communicate with systems using DeviceNet or Modbus protocol.
Features
Applications
The Model 777-TS can be used on any 3-phase motor drawing from 2-800 Amps. Applications include conveyor systems, HVAC equipment, pumps, saws, grinders and other 3-phase electric motors. In addition, the 777-TS, when used with a *Subtrol®-equipped submersible motor can detect high motor temperatures.
Protects 3-Phase Motors from:
High temperature
• Overload
• Underload
• Jams
• Undervoltage
• Overvoltage
• Single phasing
• Unbalance (voltage & current)
• Ground fault (Class II)
• Rapid cycling
• Phase reversal
Additional Features
• Fully programmable
• UL and cUL listed
• CE compliant
• CSA approved
• Automatic or manual reset
• Tamper guard
• RS-485 communications port
• Surface or DIN rail mountable
• Diagnostic display
• Last fault memory
• 5-year warranty
• Made in USA
New Features
• Network programmable
• Ability to clear last fault
NEW!
*Subtrol is a registered trademark of Franklin Electric Co., Inc.
Page 2
2880 North Plaza Drive • Rapid City, SD 57702 (800) 843-8848 • (605) 348-5580 • FAX (605) 348-5685 www.symcominc.com • email:sales@symcominc.com
01/05
777-TS 777-LR-TS 777-575-TS
Overload Relays
ABC
CONTACTOR
H1
X1
H1
X1
H1
X1
12 - 16 AWG
Stranded Wire
3 0
MOTOR
CURRENT TRANSFORMER WIRING DIAGRAM FOR MODEL 777-TS (80-800 AMPS)
SYMCOM RECOMMENDS USING CTs WITH TERMINALS TO SIMPLIFY INSTALLATION.
Note: All CTs must face the same direction and all CT secondaries must be wired identically, i.e. all X1 terminals enter the main (round) window and return to H1 terminals after exiting the loop conductor window (rectangle).
Every CT secondary must make five passes through the correspondin
g
main conductor window.
DISPLAY / PROGRAM
L 3
­L
1
L3-L1
L
B
E
+
O
V
AVG
A VG
T
L
1
-L
2
L1-L2
L 2
­L 3
L2-L3
C
N
T
C
E
A
A
G
A V
G
A VG
R
R
U
MODE SELECT
L1 L2
L3
NO C NC
OVERLOAD RELAY
DISPLAY MESSAGE
RESET/
PROGRAM
800-843-8848SYMCOM, INC. RAPID CITY, SD
Wiring configuration based on motor amps. Overload Trip Classes
777-TS
External CTs required. See wiring diagram for external CTs
777-LR-TS
Model
1 - 2 2 - 9
Full Load
Amps
# of
Loops
1 0
# of Conductors
through A, B and C
2 1
MULT to Program
(CT Ratio)
2 1
8 - 12 12 - 25 25 - 90
80 - 110 110 - 160 160 - 220 220 - 320 320 - 420 400 - 520 480 - 600 560 - 800
2 1 0
4 4 4 4 4 4 4 4
3 2 1
5 5 5 5 5 5 5 5
3 2 1
100 (100:5) 150 (150:5) 200 (200:5) 300 (300:5) 400 (400:5) 500 (500:5) 600 (600:5) 800 (800:5)
10000
1000
100
10
0 300 400 500
% of OC Setting
Trip Time (Seconds)
600 700 800 900 1000
Class 10
Class 30 Class 20
Class 15
Class 5
200100
1
Wiring Diagrams
Charts
Note: High temp. signal may be attenuated when external CTs are used.
Page 3
777-TS Manual Remote Reset Kit
The manual remote reset allows the 777-TS line of MotorSaver®and PumpSaver®products to be manually reset without opening the panel door. Simply connect the 9-pin adapter to the 777-TS communication port and mount the reset switch in a convenient location.
RM-1000
The RM-1000 is a local display/controller with RS-485 Modbus network capabilities. Its modular design allows for flexible, inexpensive installation yet provides robust motor management. Plant personnel safety is also enhanced by allowing system troubleshooting and control without opening the starter box.
2880 North Plaza Drive • Rapid City, SD 57702 (800) 843-8848 • (605) 348-5580 • FAX (605) 348-5685 www.symcominc.com • email:sales@symcominc.com
01/05
Dimensions for All 777-TS Units
777-TS 777-LR-TS 777-575-TS
Overload Relays
RS485MS-2W
The optional RS485MS-2W communications module is
required if Model 777-TS-type products are used on a
Modbus network or with RM-1000 or RM-2000
remote displays. The communications module
provides RS-485 bus drive capabilities and optical
isolation from the overload electronics and powerline.
Accessories
Dimensions
RM-2000
The RM-2000 motor monitoring device,used in conjunction
with SymCom’s Model 777-TS, provides a complete
motor management system. This system provides full
electronic motor protection, historical data and critical,
user-friendly, motor-monitoring information. The RM-2000
also features a real-time clock, 2x20 backlit LCD, one
upstream RS-485 Modbus communication port and is rated
NEMA-3R when mounted on a panel door.
COM-DN
The optional COM-DN DeviceNet Communications Module allows the Model 777-TS-type products to be easily used on a DeviceNet fieldbus.The COM-DN meets ODVA requirements for a slave only overload-type device. The COM-DN supports explicit and polled messaging as well as automatic node recovery. The EDS file allows easy setup with third party configuration tools.
Page 4
NOTES: SymCom's 777-TS & 777-LR-TS can be preprogrammed prior to installation by applying 120 VAC between the L1 and L2 terminals. * 575 volt Model (MS 777-575-TS) ** If J prefix is displayed in trip class setting, jam protection is enabled. *** If "oc" is disabled in the #RF setting, the overcurrent will be included as a normal fault and the relay will automatically
restart after RD2 expires,otherwise, manual reset is required after an overcurrent fault.
Specifications Model 777-TS Model 777-LR-TS Model 777-575-TS
01/05
EElleecctt rr iiccaa ll
Input Voltage 200-480VAC, 3Ø(Standard)
500-600VAC (Model 777-575-TS) Frequency 50 or 60Hz Motor Full Load Amp Range
777-TS, 777-575-TS 777-LR-TS, 777-575-LR-TS
2-25 Amps, 3Ø (Loops Required) 1-4.5 Amps, 3Ø(Loops Required) 25-90 Amps, 3Ø(Direct) 2-9 Amps, 3Ø(Direct)
80-800 Amps, 3Ø(External CTs) Short Circuit Rating 100kA Power Consumption 10W (Maximum) Output Contact Rating SPDT (Form C) Pilot duty rating: 480VA @ 240VAC
General purpose: 10A @ 240VAC
Expected Life
Mechanical
1 x 106 operations
Electrical
1 x 105 operations at rated load
Accuracy at 25° C (77° F)
Voltage ±1% Current ±3%(<100 Amps Direct) GF Current ±15% Timing 5% ± 1 second
Repeatability
Voltage ±0.5% of nominal voltage Current ±1% (<100 amps direct)
Trip Times (Those not shown have user selectable trip times.)
Ground Fault Trip Time Trip time
101%-200% of Setpoint 8 seconds ±1 second
201%-300% of Setpoint 4 seconds ±1 second
301%-400% of Setpoint 3 seconds ±1 second
401% or Greater 2 seconds ±1 second
Current Unbalance Trip Times
% Over Setpoint Trip time % Over Setpoint Trip time
1% 30 seconds 5% 6 seconds 2% 15 seconds 6% 5 seconds 3% 10 seconds 10% 3 seconds 4% 7.5 seconds 15% 2 seconds
Safety Marks
UL UL508, UL1053 CE IEC 60947-1, IEC 60947-5-1 CSA
Standards Passed
Electrostatic Discharge (ESD) IEC 1000-4-2, Level 3, 6kv contact, 8kv air Radio Frequency Immunity (RFI), Conducted IEC 1000-4-6, Level 3 10V/m Radio Frequency Immunity (RFI), Radiated IEC 1000-4-3, Level 3 10V/m Fast Transient Burst IEC 1000-4-4, Level 3, 3.5kv input power Surge
IEC 1000-4-5
Level 3, 2kv line-to-line; Level 4, 4kv line-to-ground
ANSI/IEEE C62.41 Surge and Ring Wave Compliance to a level of 6kv line-to-line Hi-potential Test Meets UL508 (2 x rated V +1000V for 1 minute) Vibration IEC 68-2-6, 10-55Hz, 1mm peak-to-peak, 2 hours, 3 axis Shock IEC 68-2-27, 30g, 3 axis, 11ms duration, half-sine pulse
MMee cchhaanniiccaall
Dimensions 3.1"H x 5.1"D x 3.9"W Termnal Torque 7 inch•lb Enclosure Material Polycarbonate Weight 1.2 lbs Maximum Conductor Size Through 777 0.65" with insulation
EEnnvviirr oo nn mm ee nn tt aa ll
Temperature Range Ambient Operating: -20° - 70° C (-4° - 158° F)
Ambient Storage: -40° - 80° C (-40° - 176° F) Pollution Degree 3 Class of Protection IP20, NEMA 1 Relative Humidity 10-95%, non-condensing per IEC 68-2-3
PPrroo ggrraammmmaabbll ee OOppee rraattiinn gg PPooiinntt ss RRaa nnggee
LV- Low Voltage Threshold 170V (450V*) - HV Setting HV- High Voltage Threshold LV Setting - 528V (660V*) VUB- Voltage Unbalance Threshold 2 - 15% or 999 TS- Temperature Sensor ON/OFF MULT- # of Conductors or CT Ratio (XXX:5) 1-10 Conductors or 100-800 Ratio OC- Overcurrent Threshold (20 to 100A) ÷ MULT or 80 to 120% of CT Primary; LR, (2 to 10A) ÷ MULT UC- Undercurrent Threshold (0, 10 to 98A) ÷ MULT or 40 to 100% of CT Primary; LR. (0, 1 to 9.8A) ÷ MULT CUB- Current Unbalance Threshold 2 - 25% or 999 TC- Overcurrent Trip Class ** 5, J5, 10, J10, 15, J15, 20, J20, 30, J30 RD1- Rapid Cycle Timer 0, 2 - 500 Seconds RD2- Restart Delay After All Faults Except Undercurrent 2 - 500 Minutes
(motor cool down timer)
RD3- Restart Delay After Undercurrent 2 - 500 Minutes
(dry well recovery timer) #RU- Number of Restarts After Undercurrent 0, 1, 2, 3, 4, A(Automatic) ADDR- RS485 Address A01- A99 #RF-Number of Restarts After All Faults Except Undercurrent*** 0, 1, oc1, 2, oc2, 3, oc3, 4, oc4, A, ocA UCTD- Undercurrent Trip Delay 2 - 60 Seconds GF- Ground Fault Current Threshold (3 to 20A) ÷ MULT or 10 to 30% of CT Primary or OFF; LR, (0.3 to 2.0A) ÷ MULT or OFF
SymCom warrants its microcontroller based products against defects in material or workmanship for a period of five (5) years from the date of manufacture. All other products manufactured by SymCom shall be warranted against defects in material and workmanship for a period of two (2) years from the date of manufacture.For complete information on warranty, liability, terms returns, and cancellations, please refer to the SymCom Terms and Conditions of Sale document.