Electrical
Input Voltage 200-480 VAC, 3Ø(Standard)
500-600VAC for model 777-575
Frequency 50-60 Hz
Motor Full Load Amp Range
777, 777-575 777-LR, 777-575-LR
2-25 Amps, 3Ø (Loops Required) 1-4.5 Amps, 3Ø(Loops Required)
25-90 Amps, 3Ø(Direct) 2-9 Amps, 3Ø(Direct)
80-800 Amps, 3Ø(External CTs)
Short Circuit Rating 10kA
Power Consumption 10W (Maximum)
Output Contact Rating SPDT (Form C) Pilot duty rating: 480 VA @ 240 VAC
General purpose: 10A @ 240 VAC
Expected Life
Mechanical
Accuracy at 25° C (77° F)
Voltage ±1%
Current ±3%(<100 Amps Direct)
GF Current ±15%
Timing 5% ± 1 second
Repeatability
Voltage ± 0.5% of nominal voltage
Current ± 1% (<100 amps direct)
Trip Times (Those not shown have user selectable trip times.)
Ground Fault Trip Time Trip time
101%-200% of Setpoint 8 seconds ± 1 second
201%-300% of Setpoint 4 seconds ± 1 second
301%-400% of Setpoint 3 seconds ± 1 second
401% or Greater 2 seconds ± 1 second
Current Unbalance Trip Times
% Over Setpoint Trip time % Over Setpoint Trip time
1% 30 seconds 5% 6 seconds
2% 15 seconds 6% 5 seconds
3% 10 seconds 10% 3 seconds
4% 7.5 s econ ds 15% 2 sec onds
Safety Marks
UL UL508, UL1053
CE IEC 60947-1, IEC 60947-5-1
Standards Passed
Electrostatic Discharge (ESD) IEC 1000-4-2, Level 3, 6kV contact, 8kV air
Radio Frequency Immunity (RFI), Conducted IEC 1000-4-6, Level 3 10V/m
Radio Frequency Immunity (RFI), Radiated IEC 1000-4-3, Level 3 10V/m
Fast Transient Burst IEC 1000-4-4, Level 3, 3.5 kV input power
Surge
IEC 1000-4-5
Level 3, 2kV line-to-line; Level 4, 4kV line-to-ground
ANSI/IEEE C62.41 Surge and Ring Wave Compliance to a level of 6kV line-to-line
Hi-potential Test Meets UL508 (2 x rated V +1000V for 1 minute)
Vibration IEC 68-2-6, 10-55Hz, 1mm peak-to-peak, 2 hours, 3 axis
Shock IEC 68-2-27, 30g, 3 axis, 11ms duration, half-sine pulse
Mechanical
Dimensions 3.1"H x 5.1"D x 3.9"W
Termnal Torque 7 inch•lb
Enclosure Material Polycarbonate
Weight 1.2 lbs
Maximum Conductor Size Through 777 0.65" with insulation
Environmental
Temperature Range Ambient Operating: -20° - 70° C (-4° - 158° F)
Ambient Storage: -40° - 80° C (-40° - 176° F)
Pollution Degree 3
Class of Protection IP20, NEMA 1
Relative Humidity 10-95%, non-condensing per IEC 68-2-3
Programmable Operating Points Range
LV- Low Voltage Threshold 170V (450V*) - HV Setting
HV- High Voltage Threshold LV Setting - 528V (660V*)
VUB- Voltage Unbalance Threshold 2 - 15% or 999
MULT- # of Conductors or CT Ratio (XXX:5) 1-10 Conductors or 100-800 Ratio
OC- Over Current Threshold (20 to 100A) ÷ MULT or 80 to 120% of CT Primary; LR, (2 to 10A) ÷ MULT
UC- Under Current Threshold (0, 10 to 98A) ÷ MULT or 40 to 100% of CT Primary; LR. (0, 1 to 9.8A) ÷ MULT
CUB- Current Unbalance Threshold 2 - 25% or 999
TC- Over Current Trip Class ** 5, J5, 10, J10, 15, J15, 20, J20, 30, J30, J00 (J00 = Linear)
RD1- Rapid Cycle Timer 0, 2 - 500 Seconds (x 0.5 if TC = J00)
MA- Motor Accelleration Timer (0 to 500) x 0.158 Seconds = (0 to 79 Seconds)
RD2- Restart Delay After All Faults Except Under Current 2 - 500 Minutes (x 0.5 if TC = J00)
(motor cool down timer)
OCTD - Overcurrent Trip Delay (Linear) (2 to 500) x 0.158 Seconds = (0.32 to 79 Seconds)
RD3- Restart Delay After Under Current 2 - 500 Minutes (x 0.5 if TC = J00)
(dry well recovery timer)
#RU- Number of Restarts After Under Current 0, 1, 2, 3, 4, A(Automatic)
ADDR- RS485 Address A01- A99
#RF-Number of Restarts After All Faults Except Undercurrent*** 0, 1, oc1, 2, oc2, 3, oc3, 4, oc4, A, ocA
UCTD- Under Current Trip Delay 2 - 60 Seconds
GF- Ground Fault Current Threshold (3 to 20A) ÷ MULT or 10 to 30% of CT Primary or OFF; LR, (0.3 to 2.0A) ÷ MULT or OFF