Symcom 777, 777-LR, 777-575 Catalog Page

Recordable voltage, current, last 4 faults, KWh usage, and power factor is available when using communications package.
Digitally programmable for precise customizing.
Last fault memory provides instant trouble­shooting diagnostics.
UL and cUL listed as an overload relay.
RS485 communication port for use with computerized systems using Modbus protocol.
2880 North Plaza Drive • Rapid City, SD 57702 (800) 843-8848 • (605) 348-5580 • FAX (605) 348-5685 www.symcominc.com • email: sales@symcominc.com
7/04
Features
Applications
Description
The Model 777 can be used on any 3-phase motor drawing 2-800 amps. Applications include CONVEYOR SYSTEMS, HVAC EQUIPMENT, PUMPS, SAWS, GRINDERS AND OTHER 3-PHASE ELECTRIC MOTORS.
The Model 777 is a fully-programmable electronic overload relay. An alphanumeric LED display provides programming and diagnostic information. Sixteen parameters can be programmed in the Model 777:
1) Low Voltage Setpoint 9) Rapid-Cycle Timer (RD1)
2) High Voltage Setpoint 10) Fault Restart Delay (RD2 - Motor Cool-down Timer)
3) Voltage Unbalance Setpoint 11) Underload Restart Delay (RD3 - Dry Well Recovery Timer)
4) CT Size/Loop Setting 12) No. of restarts after an overload (Manual or Automatic)
5) Overcurrent Trip Point 13) RS485 Address
6) Undercurrent Trip Point 14) No. of restarts after an underload fault
7) Current Unbalance Trip Point 15) Underload Trip Delay
8) Trip Class (5, 10, 15, 20, 30) 16) Ground Fault Trip Point
Programming the Model 777 is an easy four step process: 1) Rotate the MODE SELECT switch to the parameter to be programmed; 2) Depress and hold the RESET/PROGRAM button;
3) Rotate the DISPLAY/PROGRAM dial to the desired setting as shown in the LED display; and 4) Release the RESET/PROGRAM button.
An RS-485 port allows the Model 777 to be connected to an RM-1000 or RM-2000 remote monitor or directly to a computer or PLC. The RM-2000/777 motor management system combines unsurpassed electronic motor protection and critical, user friendly motor monitoring. SymCom's Solutions Software (sold separately) can be used to monitor and control up to 99 Model 777s from a central computer. Using Solutions Software, an operator can control motors, view the operating parameters, and record the following operating parameters:
• Line - Line Voltages (Recordable) • Restart Delay Timers
• Line Currents (Recordable) • KWH Usage (Recordable)
• Last 4 Faults (Recordable) • Power Factor (Recordable)
Model 777 Model 777-LR Model 777-575
Overload Relays
Engineered
Protection
•Overload
•Underload
•Jams
•Undervoltage
•Overvoltage
•Single phasing
•Unbalance (voltage & current)
•Ground fault (Class II)
•Rapid cycling
•Phase reversal
•Fully programmable
•UL and cUL listed
•CE compliant
•CSA approved
•Automatic or manual reset
•Tamper guard
•RS485 communications port
•Surface mount or DIN rail mount
•Alphanumeric LED diagnostic display
•Last fault memory
•5 year warranty
•Made in USA
•Network programmable
•Ability to clear last fault
Protects 3-Phase motors from:
Standard Features
New Features
2880 North Plaza Drive • Rapid City, SD 57702 (800) 843-8848 • (605) 348-5580 • FAX (605) 348-5685 www.symcominc.com • email: sales@symcominc.com
7/04
777 777-LR 777-575
Overload Relays
ABC
CONTACTOR
H1
X1
H1
X1
H1
X1
12 - 16 AWG
Stranded Wire
3 0
MOTOR
CURRENT TRANSFORMER WIRING DIAGRAM FOR MODEL 777 (80 TO 800 AMPS)
SYMCOM RECOMMENDS USING CTs WITH TERMINALS TO SIMPLIFY INSTALLATION.
Note: All CTs must face the same direction and all CT secondaries must be wired identically, i.e. all X1 terminals enter the main (round) window and returns to H1 terminal after exiting the loop conductor window (rectangle).
Every CT secondary must make five passes through the correspondin
g
main conductor window on the model 777.
DISPLAY / PROGRAM
L 3
-L 1
L3-L1
L
B
E
+
O
V
AVG
A VG
T
L1-L2
L1-L2
L2-L3
L2-L3
C
N
T
C
E
A
A
G
A
V G
AVG
R
R
U
RD2
UCTD
CUB
LV
MULT
UC OC
HV
VUB
RD1
TC
GF RUN
#RU / ADDR
RD3
#RF
MODE SELECT
L1 L2
L3
NO C NC
MODEL 777
OVERLOAD RELAY
DISPLAY MESSAGE
RESET/
PROGRAM
800-843-8848SYMCOM, INC. RAPID CITY, SD
Wiring configuration based on motor amps. Overload T rip Classes
777
External CTs required. See wiring diagram for external CTs
777-LR
Model
1 - 2 2 - 9
Full Load
Amps
# of
Loops
1 0
# of Conductors
through A, B and C
2 1
MULT to Program
(CT Ratio)
2 1
8 - 12 12 - 25 25 - 90
80 - 110 110 - 160 160 - 220 220 - 320 320 - 420 400 - 520 480 - 600 560 - 800
2 1 0
4 4 4 4 4 4 4 4
3 2 1
5 5 5 5 5 5 5 5
3 2 1
100 (100:5) 150 (150:5) 200 (200:5) 300 (300:5) 400 (400:5) 500 (500:5) 600 (600:5) 800 (800:5)
10000
1000
100
10
0 300 400 500
% of OC Setting
Trip Time (Seconds)
600 700 800 900 1000
Class 10
Class 30
Class 20 Class 15
Class 5
200100
1
Wiring Diagrams
Charts
777 Manual Remote Reset Kit
The manual remote reset allows the 777 line of MotorSaver®and PumpSaver®products to be manually reset without opening the panel door. Simply connect the 9-pin adapter to the 777 communication port and mount the reset switch in a convenient location.
RM-1000
The RM-1000 is a local display/controller with RS-485 Modbus network capabilities. Its modular design allows for flexible, inexpensive installation yet provides robust motor management. Plant personnel safety is also enhanced by allowing system troubleshooting and control without opening the starter box.
2880 North Plaza Drive • Rapid City, SD 57702 (800) 843-8848 • (605) 348-5580 • FAX (605) 348-5685 www.symcominc.com • email: sales@symcominc.com
7/04
Dimensions for All 777 Units
777 777-LR 777-575
Overload Relays
4.5"
4.0"
3.3"
777 Angle Mounting Bracket
777 Angle Mounting Bracket allows the 777 line of
MotorSaver®and PumpSaver®products to be mounted into
shallow panels such as the Furnas Size 1 and other low
profile panels. The angle bracket reduces the
installed depth from 5.05" to 4.25".
RS485MS-2W
The optional RS485MS-2W communications module
is required if Model 777-type products are used on a
Modbus network or with RM-1000 or RM-2000
remote displays. The communications module
provides RS-485 bus drive capabilities and optical
isolation from the overload electronics and po werline.
Accessories
Dimensions
RM-2000
The RM-2000 motor monitoring device used in conjunction
with SymCom’s Model 777 provides a complete motor
management system. This system provides full electronic
motor protection, historical data and critical, user-friendly
motor-monitoring information. The RM-2000 also features
a real-time clock, 2x20 backlit LCD, one upstream RS-485
Modbus communication port and is rated NEMA-3R when
mounted on a panel door.
Specifications Model 777, Model 777-LR & Model 777-575
SymCom w arrants its microcontroller based products against defects in material or workmanship for a per iod of fiv e (5) y ears from the date of manufacture. All other products manufactured by SymCom shall be w arranted against def ects in material and workmanship for a period of two (2) years from the date of manufacture. For complete information on w arranty, liability , ter ms retur ns, and cancellations , please ref er to the SymCom Terms and Conditions of Sale document.
EElleeccttrr ii ccaa ll
Input Voltage 200-480 VAC, 3Ø(Standard)
Frequency 50-60 Hz Motor Full Load Amp Range
777, 777-575 777-LR, 777-575-LR
2-25 Amps, 3Ø (Loops Required) 1-4.5 Amps, 3Ø(Loops Required) 25-90 Amps, 3Ø(Direct) 2-9 Amps, 3Ø(Direct)
80-800 Amps, 3Ø(External CTs) Short Circuit Rating 100kA Power Consumption 10W (Maximum) Output Contact Rating SPDT (Form C) Pilot duty rating: 480 VA @ 240 VAC
Expected Life
Mechanical 1 x 106 operations
Electrical 1 x 105 operations at rated load Accuracy at 25° C (77° F)
Voltage ±1% Current ±3%(<100 Amps Direct) GF Current ±15% Timing 5% ± 1 second
Repeatability
Voltage ± 0.5% of nominal voltage Current ± 1% (<100 amps direct)
Trip Times (Those not shown have user selectable trip times.)
Ground Fault Trip Time Trip time
101%-200% of Setpoint 8 seconds ± 1 second
201%-300% of Setpoint 4 seconds ± 1 second
301%-400% of Setpoint 3 seconds ± 1 second
401% or Greater 2 seconds ± 1 second
Current Unbalance Trip Times
% Over Setpoint Trip time % Over Setpoint Trip time
1% 30 seconds 5% 6 seconds 2% 15 seconds 6% 5 seconds 3% 10 seconds 10% 3 seconds 4% 7.5 seconds 15% 2 seconds
Safety Marks
UL UL508, UL1053 CE IEC 60947-1, IEC 60947-5-1 CSA
Standards Passed
Electrostatic Discharge (ESD) IEC 1000-4-2, Level 3, 6kv contact, 8kv air Radio Frequency Immunity (RFI), Conducted IEC 1000-4-6, Level 3 10V/m Radio Frequency Immunity (RFI), Radiated IEC 1000-4-3, Level 3 10V/m Fast Transient Burst IEC 1000-4-4, Level 3, 3.5 kv input power Surge
IEC 1000-4-5
ANSI/IEEE C62.41 Surge and Ring Wave Compliance to a level of 6kv line-to-line Hi-potential Test Meets UL508 (2 x rated V +1000V for 1 minute) Vibration IEC 68-2-6, 10-55Hz, 1mm peak-to-peak, 2 hours, 3 axis Shock IEC 68-2-27, 30g, 3 axis, 11ms duration, half-sine pulse
MMee cchhaann iicc aall
Dimensions 3.1"H x 5.1"D x 3.9"W Termnal Torque 7 inch•lb Enclosure Material Polycarbonate Weight 1.2 lbs Maximum Conductor Size Through 777 0.65" with insulation
EEnnvv iirroonnmmeenn tt aa ll
Temperature Range Ambient Operating: -20° - 70° C (-4° - 158° F)
Pollution Degree 3 Class of Protection IP20, NEMA 1 Relative Humidity 10-95%, non-condensing per IEC 68-2-3
PPrrooggrraa mmmmaabbllee OOppee rraattiinn gg PP ooiinnttss RRaa nnggee
LV- Low Voltage Threshold 170V (450V*) - HV Setting HV- High Voltage Threshold LV Setting - 528V (660V*) VUB- Voltage Unbalance Threshold 2 - 15% or 999 MULT- # of Conductors or CT Ratio (XXX:5) 1-10 Conductors or 100-800 Ratio OC- Overcurrent Threshold (20 to 100A) ÷ MULT or 80 to 120% of CT Primary; LR, (2 to 10A) ÷ MULT UC- Undercurrent Threshold (0, 10 to 98A) ÷ MULT or 40 to 100% of CT Primary; LR. (0, 1 to 9.8A) ÷ MULT CUB- Current Unbalance Threshold 2 - 25% or 999 TC- Overcurrent Trip Class ** 5, J5, 10, J10, 15, J15, 20, J20, 30, J30 RD1- Rapid Cycle Timer 0, 2 - 500 Seconds RD2- Restart Delay After All Faults Except Undercurrent 2 - 500 Minutes
(motor cool down timer) RD3- Restart Delay After Undercurrent 2 - 500 Minutes
(dry well recovery timer) #RU- Number of Restarts After Undercurrent 0, 1, 2, 3, 4, A(Automatic) ADDR- RS485 Address A01- A99 #RF-Number of Restarts After All Faults Except Undercurrent*** 0, 1, oc1, 2, oc2, 3, oc3, 4, oc4, A, ocA UCTD- Undercurrent Trip Delay 2 - 60 Seconds GF- Ground Fault Current Threshold (3 to 20A) ÷ MULT or 10 to 30% of CT Primary or OFF; LR, (0.3 to 2.0A) ÷ MULT or OFF
500-600VAC for model 777-575
General purpose: 10A @ 240 VAC
Level 3, 2kv line-to-line; Level 4, 4kv line-to-ground
Ambient Storage: -40° - 80° C (-40° - 176° F)
NOTES: SymCom's 777 & 777-LR can be preprog rammed prior to installation by applying 120 VAC between the L1 and L2 terminals. * 575 volt Model (MS 777-575) ** If J prefix is displayed in trip class setting, jam protection is enabled. *** If "oc" is disabled in the #RF setting, the o vercurrent will be included as a nor mal fault and the relay will automatically
restart after RD2 expires,otherwise, manual reset is required after an overcurrent fault.
7/04