Symcom 50R SERIES Catalog Page

Protection Relays
Voltage Monitoring Relays
50R SERIES
Single-phase voltage monitor
Description
The 50R Series single-phase voltage monitor has a voltage­sensing circuit which constantly monitors the single-phase power for a low voltage condition. Single-phase motors on fans, compressors, air conditioners, heat pumps, well pumps, sump pumps and small conveyor motors are all applicable to the 50R Series.
When a harmful condition is detected, the MotorSaver’s output relay is deactivated after a specified trip delay. The output relay reactivates after power line conditions return to an acceptable level and a specified amount of time has elapsed (restart delay). The trip delay prevents nuisance tripping due to rapidly fluctuating power line conditions.
Wiring Diagram
50R
Features & Benefits
FEATURES BENEFITS
Proprietary voltage sensing circuitry
Adjustable trip delay (-3 models) and restart delay (-2 models) settings
High voltage detection (-9 models)
600V rated relay contacts available on some models
Constant monitoring of single-phase power for a low voltage condition
Prevent nuisance tripping due to rapidly fluctuating power line conditions and allows staggered start up of multiple motors, after a fault, to prevent a low voltage condition
Trips and resets at a fixed percentage of the setpoint: trip 110%, reset 107%.
Eliminates the need for a control transformer to step voltage down to 120 - 240V for a control circuit
Ordering Information
MODEL LINE VOTAGE DESCRIPTION
50R-100 95-120VAC Fixed trip and restart delay
50R-100-2 95-120VAC Fixed trip and variable restart delay (manual, 2-300s)
50R200 190-240VAC Fixed trip and restart delay
50R2002 190-240VAC Fixed trip and variable restart delay (manual, 2-300s)
50R2003 190-240VAC Fixed restart and variable trip delay (2-30s)
50R20029 190-240VAC Fixed trip and variable restart delay (manual, 2-300s) plus high voltage detection
50R400 380-480VAC Fixed trip and restart delay
50R4002 380-480VAC Fixed trip and variable restart delay (manual, 2-300s)
50R4003 380-480VAC Fixed restart and variable trip delay (2-30s)
50R40029 380-480VAC Fixed trip and variable restart delay (manual, 2-300s) plus high voltage detection
Rev: 1-A-062716
Protection Relays
Voltage Monitoring Relays
50R SERIES
Specifications
Input Characteristics
Line Voltage 50R-10 0 95 -120VAC 50R200 190 -240VAC 50R400 380-480VAC Frequency 50 */60Hz
Functional Characteristics
Low Voltage: Trip (% of setpoint) 90% Reset (% of setpoint) 93% Delay Time (Nominal) Trip 4 seconds Restart (low voltage) 2 seconds Restart (complete power loss) 2 seconds
Output Characteristics
Output Contact Rating (SPDT - 1 Form C) 50R-100, 50R200 Pilot Duty 48 0VA @ 24 0VAC General Purpose 10A @ 240VAC 50R400 Pilot Duty 470VA @ 60 0VAC
General Characteristics
Ambient Temperature Range Operating -20° to 70°C (-4° to 158°F) Storage -40° to 80°C (-40° to 176°F) Maximum Input Power 5 W Relative Humidity 10-95%, non-condensing per IEC 68-2-3 Terminal Torque 7 in.-lbs. Wire Size 12-18 AWG Electrostatic Discharge (ESD) IEC 61000-4-2, Level 3, 6kV contact, 8kV air Fast Transient Burst IEC 61000-4-4, Level 3, 3.5kV input power
and controls
Transient Protection (Internal) IEC 61000-4-5; 1995 ±6kV Safety Marks UL UL508 (File #E68520) CE IEC 60947-6-2 Dimensions H 74.4 mm (2.93”); W 133.9 mm (5.27”); D 74.9 mm (2.95”) Weight 0.98 lb. (15.68 oz., 444.52 g) Mounting Method #8 screws
Special Options
Opt. 2: Variable Restart Delay Manual, 2-300 seconds Opt. 3: Variable Trip Delay 2-30 seconds Opt. 9: High Voltage Detection Operating Points Trip (% of Setpoint) 110 % Reset (% of Setpoint) 107%
*Note: 50Hz will increase all delay timers by 20%
Rev: 1-A-062716