Protection Relays
Voltage Monitoring Relays
50R SERIES
Single-phase voltage monitor
Description
The 50R Series single-phase voltage monitor has a voltagesensing circuit which constantly monitors the single-phase
power for a low voltage condition. Single-phase motors on fans,
compressors, air conditioners, heat pumps, well pumps, sump
pumps and small conveyor motors are all applicable to the
50R Series.
When a harmful condition is detected, the MotorSaver’s output
relay is deactivated after a specified trip delay. The output relay
reactivates after power line conditions return to an acceptable
level and a specified amount of time has elapsed (restart
delay). The trip delay prevents nuisance tripping due to rapidly
fluctuating power line conditions.
Wiring Diagram
50R
Features & Benefits
FEATURES BENEFITS
Proprietary voltage
sensing circuitry
Adjustable trip delay
(-3 models) and restart
delay (-2 models) settings
High voltage detection
(-9 models)
600V rated relay
contacts available
on some models
Constant monitoring of single-phase power for a
low voltage condition
Prevent nuisance tripping due to rapidly fluctuating
power line conditions and allows staggered start up
of multiple motors, after a fault, to prevent a low
voltage condition
Trips and resets at a fixed percentage of the
setpoint: trip 110%, reset 107%.
Eliminates the need for a control transformer to step
voltage down to 120 - 240V for a control circuit
Ordering Information
MODEL LINE VOTAGE DESCRIPTION
50R-100 95-120VAC Fixed trip and restart delay
50R-100-2 95-120VAC Fixed trip and variable restart delay (manual, 2-300s)
50R200 190-240VAC Fixed trip and restart delay
50R2002 190-240VAC Fixed trip and variable restart delay (manual, 2-300s)
50R2003 190-240VAC Fixed restart and variable trip delay (2-30s)
50R20029 190-240VAC Fixed trip and variable restart delay (manual, 2-300s) plus high voltage detection
50R400 380-480VAC Fixed trip and restart delay
50R4002 380-480VAC Fixed trip and variable restart delay (manual, 2-300s)
50R4003 380-480VAC Fixed restart and variable trip delay (2-30s)
50R40029 380-480VAC Fixed trip and variable restart delay (manual, 2-300s) plus high voltage detection
Rev: 1-A-062716
![](/html/28/28d7/28d7e3d26bdf583b7d52114a6f8fa9442063db2e4d6f9a2926a80e48d2c0e1f5/bg2.png)
Protection Relays
Voltage Monitoring Relays
50R SERIES
Specifications
Input Characteristics
Line Voltage
50R-10 0 95 -120VAC
50R200 190 -240VAC
50R400 380-480VAC
Frequency 50 */60Hz
Functional Characteristics
Low Voltage:
Trip (% of setpoint) 90%
Reset (% of setpoint) 93%
Delay Time (Nominal)
Trip 4 seconds
Restart (low voltage) 2 seconds
Restart (complete power loss) 2 seconds
Output Characteristics
Output Contact Rating
(SPDT - 1 Form C)
50R-100, 50R200
Pilot Duty 48 0VA @ 24 0VAC
General Purpose 10A @ 240VAC
50R400
Pilot Duty 470VA @ 60 0VAC
General Characteristics
Ambient Temperature Range
Operating -20° to 70°C (-4° to 158°F)
Storage -40° to 80°C (-40° to 176°F)
Maximum Input Power 5 W
Relative Humidity 10-95%, non-condensing per IEC 68-2-3
Terminal
Torque 7 in.-lbs.
Wire Size 12-18 AWG
Electrostatic Discharge (ESD) IEC 61000-4-2, Level 3, 6kV contact, 8kV air
Fast Transient Burst IEC 61000-4-4, Level 3, 3.5kV input power
and controls
Transient Protection
(Internal) IEC 61000-4-5; 1995 ±6kV
Safety Marks
UL UL508 (File #E68520)
CE IEC 60947-6-2
Dimensions H 74.4 mm (2.93”); W 133.9 mm (5.27”);
D 74.9 mm (2.95”)
Weight 0.98 lb. (15.68 oz., 444.52 g)
Mounting Method #8 screws
Special Options
Opt. 2: Variable Restart Delay Manual, 2-300 seconds
Opt. 3: Variable Trip Delay 2-30 seconds
Opt. 9: High Voltage
Detection Operating Points
Trip (% of Setpoint) 110 %
Reset (% of Setpoint) 107%
*Note: 50Hz will increase all delay timers by 20%
Rev: 1-A-062716