Symcom 460-XXX-SP Catalog Page

Page 1
2880 North Plaza Drive • Rapid City, SD 57702 (800) 843-8848 • (605) 348-5580 • FAX (605) 348-5685 www.symcominc.com • email:sales@symcominc.com
Features
Model
460-XXX-SP
Single-Phase
Voltage Monitor
Engineered
Protection
Microcontroller
Based
Universal range from 95-120 or 190-240VAC, 50/60 Hz provides the versatility needed to handle global applications.
Two adjustment pots provide versatility for all kinds of applications.
Diagnostic LEDs indicate trip status and provide simple troubleshooting.
Microcontroller-based circuitry provides better accuracy and higher reliability than analog designs.
Transient protection meets IEEE and IEC standards to allow operation under tough conditions.
The Model 460-XXX-SP protects single-phase motors from damage caused by low and high voltage and rapid cycling.Controls are provided to set the nominal voltage (190-240VAC) and the desired restart delay time (1-500 sec.).
A unique microcontroller-based, voltage-sensing circuit constantly monitors the voltage to detect harmful power line conditions.When a harmful condition is detected, the MotorSaver's output relay is deactivated after a specified trip delay. The output relay reactivates after power line conditions return to an acceptable level for a specified amount of time (restart delay). The restart delay is also a power-up delay and can be utilized to stagger-start motors on the same system. The trip delay prevents nuisance tripping due to rapidly fluctuating power line conditions.
Protects Single-Phase Motors From:
• Low voltage
• High voltage
• Rapid cycling
Additional Features:
• Compact design
• Standard 1-500 sec. variable restart delay
• Standard surface or DIN rail mountable
• Finger-safe terminals
• One 10 Amp general purpose Form C relay
• Optional manual reset
• UL and cUL listed
• CE compliant
• 5-year warranty
• Made in USA
100
5001
VOLTAGE ADJ. (VAC) RESTART (SEC)
MODEL 460-XXX-SP
220
230
20 250
240
200
190
208
LED STATUS
RUN RESTART DELAY
HIGH / LOW VOLTAGE
GREEN
GREEN
RED
21
4
5
6
3
10/05
Page 2
2880 North Plaza Drive • Rapid City, SD 57702 (800) 843-8848 • (605) 348-5580 • FAX (605) 348-5685 www.symcominc.com • email:sales@symcominc.com
SymCom warrants its microcontroller based products against defects in material or workmanship for a period of five (5) years from the date of manufacture. All other products manufactured by SymCom shall be warranted against defects in material and workmanship for a period of two (2) years from the date of manufacture. For complete information on warranty, liability, terms, returns, and cancellations, please refer to the SymCom Terms and Conditions of Sale document.
Specifications
Operating Points
Special Options
Specifications
Single-Phase Line Voltage
460-100-SP ............................................95-120VAC
460-200-SP ............................................190-240VAC
Frequency..............................................50*/60 Hz
Low Voltage (% of setpoint)
•Trip ........................................................90% ±1%
•Reset......................................................93% ±1%
High Voltage (% of setpoint)
•Trip ........................................................110% ±1%
•Reset......................................................107% ±1%
Trip Delay Time
•Low or High Voltage ..............................4 seconds
Restart Delay Time
•After a Fault ..........................................1-500 seconds adjustable
•After a Complete Power Loss ................1-500 seconds adjustable
Output Contact Rating
•1-Form C................................................10 A General Pur pose @ 240VAC
................................................................Pilot Duty 480VA @ 240VAC, B300
Power Consumption ............................6 Watts (max.)
Weight ..................................................14 oz.
Enclosure ..............................................Polycarbonate
Terminal T or que ....................................6 in.-lbs.
Wire Type................................................Stranded or solid 12-20 AWG, one per terminal
Safety Marks
•UL ..........................................................UL508
•CE..........................................................IEC 60947-6-2
Standards Passed
•Electrostatic Discharge (ESD) ..............IEC 1000-4-2, Level 3, 6kV contact, 8kV air
•Radio Frequency Immunity, Radiated....150 MHz, 10V/m
•Fast Tr ansient Burst ..............................IEC 1000-4-4, Level 3, 3.5 kV input power & controls
Surge
•IEC ........................................................IEC 1000-4-5, Level 3, 4kV line-to-line;
................................................................Level 4, 4kV line-to-ground
•ANSI/IEEE ............................................C62.41 Surge and Ring Wave Compliance
................................................................to a level of 6kV line-to-line
•Hi-potential Test ....................................Meets UL508 (2 x rated V +1000V for 1 minute)
Environmental
Temperature Range ................................Ambient Operating: -20° to 70° C (-4° to 158°F)
................................................................Ambient Storage: -40° to 80° C (-40° to 176°F)
Class of Protection ..................................IP20, NEMA 1 (finger safe)
Relative Humidity....................................10-95%, non-condensing per IEC 68-2-3
Special Options
Manual Reset..........................................External momentary pushbutton required.
*Note: 50 Hz will increase all delay timers by 20%
10/05
100
5001
VOLTAGE ADJ. (VAC) RESTART (SEC)
MODEL 460-SP
220
230
20 250
240
200
190
208
LED STATUS
RUN RESTART DELAY
HIGH / LOW VOLTAGE
GREEN
GREEN
RED
Model 460-XXX-SP
Single-Phase
Voltage Monitor
FRONT VIEW
BOTTOM VIEW
SIDE VIEW
TYPICAL WIRING DIAGRAM