Symcom 460-MR Installation Guide

Page 1
INSTALLATION INSTRUCTIONS FOR
SYMCOM’S MOTORSAVER
MODEL 460-MR
®
BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION!
FOLLOW NATIONAL, STATE AND LOCAL CODES.
READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION.
The Model 460-MR MotorSaver® is an auto-ranging voltage monitor designed to protect 3-phase motors regardless of size. The MotorSaver from damage caused by single-phasing, low voltage, high voltage, phase reversal, and voltage unbalance. The Model 460-MR features an optional manual reset mode. In addition, when the MotorSaver displayed until the unit is manually reset, even if power is removed and reapplied.
CONNECTIONS
1. Mount the MotorSaver® in a convenient location in or near the motor control panel. If the
2. Connect L1, L2 and L3 on the MotorSaver’s terminal strip to the LINE SIDE of the motor starter
3. Connect the output relay to the circuitry to be controlled. For motor control, connect the
4. The Model 460-MR is shipped with a jumper across the two manual reset pins (see Fig. 3). This
®
is in the manual reset mode and a fault condition occurs, the fault code will be
location is wet or dusty, the MotorSaver MotorSaver
®
can be mounted to a back panel using two #6 or #8 x 5/8 screws or can be
snapped onto a DIN rail.
(see Figure 1).
normally open contact in series with the magnetic coil of the motor starter as shown in Figure 1. For alarm operation, connect the normally closed contact in series with the control circuit as in Figure 2.
will allow the MotorSaver
®
to operate in automatic reset mode. To operate the MotorSaver® in manual reset mode, the jumper must be removed and replaced with an NO (normally open) pushbutton switch. A pre-assembled connector and 12” cable are shipped with each MotorSaver
®
(pushbutton not included). The connector must be plugged into the MotorSaver®
with the locking tabs facing downward.
®
is used on 190-480VAC, 50/60 Hz motors to protect
®
should be mounted in a NEMA 4 or 12 enclosure. The
2880 North Plaza Drive, Rapid City, SD 57702
(800) 843-8848 · (605) 348-5580
www.symcominc.com
Page 2
Figure 1. Control Wiring Diagram
Figure 2. Alarm Wiring Diagram
Figure 3. Manual Reset Connections
2
7/05
Page 3
SETTINGS
1. Line voltage adjustment: Rotate the VOLTAGE ADJ. (VAC) to the nominal 3-phase line voltage feeding the motor to be protected.
2. Restart delay adjustment: Rotate the RESTART (SEC) adjustment to the desired position. The restart delay is the time between the MotorSaver and the MotorSaver compressor applications, the restart delay should be set for the approximate time it takes for the head pressure to bleed off of the compressor. For other applications, the restart delay is typically set between 2 and 10 seconds.
NOTE: The restart delay adjustment is inoperative when configured for manual reset.
3. Trip delay adjustment: Rotate the TRIP DELAY (SEC) adjustment to the desired setting. This adjustment does not affect the trip delay on phasing faults. Typically, the trip delay adjustment is set between 1 and 5 seconds. In areas where voltage fluctuations are frequent, the trip delay adjustment may be set greater than 10 seconds.
4. Voltage unbalance adjustment: Rotate the UNBALANCE TRIP (NEMA%) adjustment to the desired unbalance trip level. The NEMA MG1 standard does not recommend operating a motor above 1% voltage unbalance without derating the motor. The NEMA MG1 standard also recommends against operating a motor above a 5% voltage unbalance under any circumstances. SymCom recommends consulting the motor manufacturer for specific tolerances.
Percent Unbalance = Maximum deviation from the average
Average
Example: The measured line-to-line voltages are 203, 210, and 212.
Average = 203 + 210 + 212
The maximum deviation from the average is the largest difference between the average voltage (208.3) and any one voltage reading.
®
closing its output contacts. For
3
208.3 - 203 = 5.3 210 - 208.3 = 1.7 212 - 208.3 = 3.7 The maximum deviation from the average is 5.3.
®
seeing acceptable voltage
= 208.3
x 100 = 2.5% unbalance
5.3
208.3
x 100%
3
7/05
Page 4
MANUAL RESET SWITCH OPERATION
The MotorSaver® always requires a manual reset after a power loss when operated in manual reset mode. If no faults are currently detected, and no faults were detected before power was removed, both lights will flash in unison until the reset button is pressed. When a fault is detected, the MotorSaver
®
will flash the fault code until the fault condition clears and the reset button is pressed. If the fault clears but the reset button has not been pressed, the MotorSaver fault. If power is lost before the MotorSaver to flash the corresponding fault code once power is reapplied. This allows for identification of the last fault even after power conditions have returned to normal. As soon as the reset button is pressed, the MotorSaver
®
will resume normal operation.
NOTE: If the jumper is left in place, or the manual reset button is pressed when the 460-MR is powered-up, it will operate in automatic reset mode. If an automatic restart would be a hazard to equipment or personnel, use the manual reset mode.
POWER-UP
Automatic Reset Mode: With the jumper in place, or the manual reset button pressed, apply 3-
phase power to the motor. The MotorSaver’s green RUN light will blink during the RESTART delay. After the RESTART delay, the MotorSaver will illuminate. If the contacts do not energize and the RUN light does not illuminate, see the TROUBLESHOOTING section.
Manual Reset Mode: With the jumper removed and the manual reset button released, apply 3­phase power to the motor. The MotorSaver’s green and red lights will blink in unison until the manual reset button is pressed – then the contacts will energize and the RUN light will illuminate.
NOTE: Upon power up, if a light pattern other than the red and green lights blinking in unison is displayed (while in manual reset mode), the Model 460-MR is in a fault condition or was in a fault condition before it lost power. The fault code will be displayed until the unit is manually reset.
®
®
is reset, it will remember the previous fault and continue
®
will energize its output contacts and the green RUN light
will continue flashing the
DIAGNOSTIC INDICATOR LIGHTS
RUN GREEN
RESTART DELAY
GREEN
REVERSE PHASE
UNBALANCE / SINGLE PHASE
HIGH / LOW VOLTAGE RED
MANUAL RESET REQUIRED
GREEN & RED
4
RED
RED
7/05
Page 5
TROUBLESHOOTING
SYMPTOM
No lights are on -
the unit seems
completely dead
Red light is blinking (on initial power-up)
Red light is blinking (after the motor has
previously been running)
Red light is blinking in
this pattern
Red light is on steady
LIGHT
PATTERN
N/A
RED
RED
RED
RED
SOLUTION
Measure the three line-to-line voltages. If any of the voltages are below 150VAC, the MotorSaver operate its internal electronics. If the voltages are correct, call SymCom at (800) 843-8848 or (605) 348-5580.
Turn off the 3-phase power. Swap any two leads powering the MotorSaver There is a 50-50 chance of connecting L1, L2 and L3 correctly the first time. Reapply 3-phase power.
The incoming lines have been reverse-phased. The MotorSaver running backwards. Correct the phase sequence.
The voltage is unbalanced or single-phased. Measure the incoming line voltages and calculate the % unbalance. If the voltage unbalance does not exceed the % unbalance reset value, call SymCom at (800) 843-8848 or (605) 348-5580.
The voltage is out of tolerance. Measure the three line-to-line voltages. Calculate the average of the three voltages. If the average is 7% above or below the nominal voltage as selected by the LINE VOLTAGE ADJUST, the MotorSaver voltage is within ±7% of the selected line voltage, call SymCom at (800) 843-8848 or (605) 348-5580.
®
does not have enough power to
®
(L1, L2, or L3)
®
is preventing the motor from
®
is functioning properly. If the
Green light blinks and
motor is not running
Green light is on steady,
but motor does not start
Green and red lights
blink in unison and motor does not run
GREEN
GREEN
GREEN & RED
The MotorSaver delay – this occurs only when the manual reset
®
is timing through the restart
jumper is in place.
The MotorSaver
®
is in run mode. Ensure other control devices are allowing the motor to start. Check control circuit for loose wires or malfunctioning switches.
The MotorSaver
®
is waiting for a manual reset.
5
7/05
Page 6
MOTORSAVER® 460-MR SPECIFICATIONS
3-Phase Line Voltage 475-600VAC (optional) 95-120VAC (optional) Frequency Low Voltage (% of setpoint)
Trip 90% ±1% Reset 93% ±1% High Voltage (% of setpoint) Trip 110% ±1% Reset 107% ±1% Voltage Unbalance (NEMA) Trip 2-8% adjustable
Reset
Trip Delay Time (automatic restart mode only)
Low, High and unbalanced voltage 1-30 seconds adjustable
Single-phasing faults (>25% UB) 1 second fixed
Restart Delay Time After a fault or power loss 1-500 seconds adjustable Output Contact Rating – SPDT
Pilot Duty 480VA @ 240VAC General Purpose 10A @ 240VAC
Power Consumption Weight Enclosure Terminal
Torque 6 in.-lbs. Wire AWG 12-20 AWG Safety Marks UL UL508 (File #E68520) CE IEC 60947-6-2 Standards Passed
Electrostatic Discharge (ESD)
Radio Frequency Immunity, Radiated
Fast Transient Burst
Surge
IEC
ANSI/IEEE
Hi-Potential Test
Environmental
Temperature Range Class of Protection IP20, NEMA 1 (Finger Safe) Relative Humidity 10-95%, non-condensing per IEC 68-2-3
*NOTE: 50Hz will increase all delay timers by 20%
190-480VAC
50*/60Hz
Trip setting minus 1% (5-8%) Trip setting minus 0.5% (2-4%)
6 Watts 14 oz. Polycarbonate
IEC 100-4-2, Level 3, 6kV contact, 8kV air
159 MHz, 10V/m
IEC 1000-4-4, Level 3, 3.5kV input power and controls
IEC 1000-4-5, Level 3, 4kV line-to-line; Level 4, 4kV line-to-ground
C62.41 Surge and Ring Wave Compliance to a level of 6kV line-to-line
Meets UL508 (2 x rated V +1000 V for 1 minute)
Ambient Operating: -20° to 70°C (-4° to 158°F)
6
7/05
Page 7
DIMENSIONS
SymCom, Inc. warrants its microcontroller-based products against defects in material or workmanship for a period of five (5) years from the date of manufacture. All other products manufactured by SymCom shall be warranted against defects in material or workmanship for a period of two (2) years from the date of manufacture. For complete information on warranty, liability, terms, and conditions, please refer to the SymCom Terms and Conditions of Sale document.
7
7/05
Page 8
Visit our website at www.symcominc.com for our
complete catalog and product listings!
2880 North Plaza Drive, Rapid City, SD 57702
(800) 843-8848 · (605) 348-5580
www.symcominc.com
8
7/05
Loading...