BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION!
FOLLOW NATIONAL, STATE, AND LOCAL CODES!
READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION!
The Model 460-575 MotorSaver is an auto ranging voltage monitor designed
to protect three-phase motors regardless of size. The MotorSaver is used on
475-600 VAC, 50 to 60 Hz motors to protect from damage caused by single
phasing, low voltage, high voltage, phase reversal, and voltage unbalance.
CONNECTIONS
1. Mount the MotorSaver in a convenient location in or near the motor
control panel. If the location is wet or dusty, the MotorSaver should
be mounted in a NEMA 4 or 12 enclosure. The MotorSaver can be
mounted to a back panel using two #6 or #8 x 5/8 screws or can be
snapped onto a DIN rail.
2. Connect L1, L2 and L3 on the MotorSaver’s terminal strip to the LINE SIDE
of the motor starter. (See Figure 1).
3. Connect the output relay to the circuitry to be controlled. For motor control,
connect the normally open contact in series with the magnetic coil of the
motor starter as shown in Figure 1. For alarm operation, connect the
normally closed contact in series with the control circuit as shown in Figure
2.
2880 North Plaza Drive, Rapid City, SD 57702 • (800) 843-8848
Page 2
MODEL 460-575
FIGURE 1: CONTROL WIRING DIAGRAM
LIGHT
MODEL 460-575
FIGURE 2: ALARM WIRING DIAGRAM
10/04 -2-
Page 3
SETTINGS
MODEL 460
475
500
520 550
575
600
Percent Unbalance =
Maximum Deviation from the Average
Average
x 100
Example: The measured line-to-line voltages are 203, 210, and 212.
Average =
203 + 210 + 212
3
= 208.3
The maximum deviation from the average is the largest difference
between the average voltage (208.3) and any one voltage reading.
1. Line voltage adjustment: Rotate the
“VOLTAGE ADJ. (VAC)” to the nominal
three-phase line voltage feeding the motor
to be protected.
2. Restart delay adjustment: Rotate the
“RESTART (SEC)” adjustment to the
desired position. The restart delay is the
time between MotorSaver seeing
acceptable voltage and the MotorSaver
closing its output contacts. For
compressor applications, the restart delay
should be set for the approximate time it
takes for the head pressure to bleed
off of the compressor. For other
applications, the restart delay is typically
set between 2 and 10 seconds.
3. Trip delay adjustment: Rotate the “TRIP DELAY (SEC)” adjustment to the desired
setting. This adjustment does not affect the
trip delay on phasing faults. Typically, the
trip delay adjustment is set between 1 and 5
seconds. In areas where voltage uctuations are frequent, the trip delay
adjustment may be set greater than 10 seconds.
4. Voltage unbalance adjustment: Rotate the “UNBALANCE TRIP (NEMA%)”
adjustment to the desired unbalance trip level. The NEMA MG1 standard
does not recommend operating a motor above 1% voltage unbalance without
derating the motor. The NEMA MG1 standard also recommends against
operating a motor above a 5% voltage unbalance under any circumstances.
SymCom recommends consulting the motor manufacturer for specic
tolerances.
-3- 10/04
Page 4
POWER-UP
Turn on the 3-phase power to the motor. The MotorSaver’s green RUN light will
blink during the RESTART delay. After the RESTART delay, the MotorSaver® will
energize its output contacts and the green RUN light will illuminate. If the
contacts do not energize and the RUN light does not illuminate, see the
TROUBLESHOOTING section.
DIAGNOSTIC INDICATOR LIGHTS
RUN
RESTART DELAY
REVERSE PHASE
UNBALANCE / SINGLE PHASE
HIGH / LOW VOLTAGE
CONGRATULATIONS!!
YOU HAVE JUST INSTALLED THE FINEST
MOTOR PROTECTION AVAILABLE!!
10/04 -4-
Page 5
TROUBLESHOOTING
RED
RED
SYMPTOM
No lights are on.
The unit seems
completely dead.
Red light is
blinking (on initial
power up).
Red light is
blinking (after the
motor has been
previously
running).
Red light is
blinking in this
pattern.
Red light is on
steady.
Green light blinks
and motor is not
running.
Green light is on
steady, but motor
does not start.
LIGHT
PATTERN
N / A
SOLUTION
Measure the three line-to-line voltages. If
any of the voltages are below 350 VAC, the
MotorSaver does not have enough power
to operate its internal electronics. This
may occur on a single-phased system. If
the voltages are correct, call SymCom at
1-800-843-8848 or 1-605-348-5580.
Turn off the three-phase power. Swap any
two leads powering the MotorSaver (L1,
L2, or L3). There is a 50-50 chance of
connecting L1, L2, and L3 correctly the rst
time. Re-apply the three-phase power.
The incoming lines have been reverse
phased. The MotorSaver is preventing
the motor from running backwards. Correct
the phase sequence.
The voltage is unbalanced or
single-phased. Measure the incoming line
voltages and calculate the % unbalance. If
the voltage unbalance does not exceed the
% unbalance reset value, call SymCom at
1-800-843-8848 or 1-605-348-5580.
The voltage is out of tolerance. Measure
the three line-to-line voltages. Calculate
the average of the three voltages. If the
average is 7% above or below the nominal
voltage as selected by the LINE VOLTAGE
ADJUST, the MotorSaver is functioning
properly. If the voltage is within ±7% of the
selected line voltage, call SymCom at
1-800-843-8848 or 1-605-348-5580.
The MotorSaver is in restart delay.
The MotorSaver is in run mode. Ensure
other control devices are allowing the
motor to start. Check control circuit for
loose wires or malfunctioning switches.
Any questions or comments call SymCom at 1-800-843-8848 or
1-605-348-5580
-5- 10/04
Page 6
SPECIFICATIONS
3 - Phase Line Voltage475 - 600 VAC
Frequency50* - 60 Hz
Low Voltage (% of setpoint)
Trip90% ±1%
Reset93% ±1%
High Voltage (% of setpoint)
Trip110% ±1%
Reset107% ±1%
Voltage Unbalance (NEMA)
Trip2 - 8% Adjustable
Reset
Trip Setting minus 1% (5 - 8%)
Trip Setting minus 0.5% (2 - 4%)
Trip Delay Time
Low, High, and Unbalanced Voltage1 - 30 Seconds Adjustable
Single-phasing faults (>25% UB)1 Second Fixed
Restart Delay Time
After a fault or complete power loss1 - 500 Seconds Adjustable
Output Contact Rating - SPDT
Pilot Duty480 VA @ 240 VAC
General Purpose10 A @ 240 VAC
Power Consumption6 Watts (maximum)
Weight14 oz
EnclosurePolycarbonate
Terminal
Torque6 Inch-Pounds
Wire AWG12 - 20 AWG
Safety Marks
ULUL508 (File # E68520)
CEIEC 60947-6-2
Standards Passed
Electrostatic Discharge (ESD)
IEC 1000-4-2, Level 3, 6 kv contact,
8 kv air
Radio Frequency Immunity, Radiated 159 MHz, 10 V/m
Fast Transient Burst
IEC 1000-4-4, Level 3, 3.5 kv input
power and controls
*NOTE: 50 Hz will increase all delay timers by 20%
C62.41 Surge and Ring Wave Compliance
to a level of 6kv line-to-line
Meets UL508 (2 x rated V +1000V for 1
minute)
Environmental
Temperature Range
Ambient Operating: -20° - 70° C (-4° - 158°F)
Ambient Storage: -40° - 80° C (-40° - 176°F)
Class of ProtectionIP20, NEMA 1 (Finger Safe)
Relative Humidity10-95%, non-condensing per IEC 68-2-3
DIMENSIONS
SymCom warrants its microcontroller based products against defects in material or workmanship
for a period of ve (5) years* from the date of manufacture. All other products manufactured by
SymCom shall be warranted against defects in material and workmanship for a period of two (2)
years from the date of manufacture. For complete information on warranty, liability, terms, and
conditions, please refer to the SymCom Terms and Conditions of Sale document.
-7- 10/04
Page 8
Visit our website at www.symcominc.com for our
complete catalog and new product listings!
2880 North Plaza Drive, Rapid City, SD 57702
Phone: (800) 843-8848 or (605) 348-5580
FAX: (605) 348-5685
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.