Symcom 460-575 Installation Guide

Page 1
INSTALLATION INSTRUCTIONS
FOR SYMCOM’S MOTORSAVER
MODEL 460-575
BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION!
FOLLOW NATIONAL, STATE, AND LOCAL CODES!
READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION!
The Model 460-575 MotorSaver is an auto ranging voltage monitor designed to protect three-phase motors regardless of size. The MotorSaver is used on 475-600 VAC, 50 to 60 Hz motors to protect from damage caused by single phasing, low voltage, high voltage, phase reversal, and voltage unbalance.
CONNECTIONS
1. Mount the MotorSaver in a convenient location in or near the motor control panel. If the location is wet or dusty, the MotorSaver should be mounted in a NEMA 4 or 12 enclosure. The MotorSaver can be mounted to a back panel using two #6 or #8 x 5/8 screws or can be snapped onto a DIN rail.
2. Connect L1, L2 and L3 on the MotorSaver’s terminal strip to the LINE SIDE of the motor starter. (See Figure 1).
3. Connect the output relay to the circuitry to be controlled. For motor control, connect the normally open contact in series with the magnetic coil of the motor starter as shown in Figure 1. For alarm operation, connect the normally closed contact in series with the control circuit as shown in Figure
2.
2880 North Plaza Drive, Rapid City, SD 57702 • (800) 843-8848
Page 2
MODEL 460-575
FIGURE 1: CONTROL WIRING DIAGRAM
LIGHT
MODEL 460-575
FIGURE 2: ALARM WIRING DIAGRAM
10/04 -2-
Page 3
SETTINGS
MODEL 460
475
500
520 550
575
600
Percent Unbalance =
Maximum Deviation from the Average
Average
x 100
Example: The measured line-to-line voltages are 203, 210, and 212.
Average =
203 + 210 + 212
3
= 208.3
The maximum deviation from the average is the largest difference between the average voltage (208.3) and any one voltage reading.
208.3 - 203 = 5.3 210 - 208.3 = 1.7 212 - 208.3 = 3.7
The maximum deviation from the average is 5.3.
5.3
208.3
x 100 = 2.5% Unbalance
1. Line voltage adjustment: Rotate the “VOLTAGE ADJ. (VAC)” to the nominal three-phase line voltage feeding the motor to be protected.
2. Restart delay adjustment: Rotate the “RESTART (SEC)” adjustment to the desired position. The restart delay is the time between MotorSaver seeing acceptable voltage and the MotorSaver closing its output contacts. For compressor applications, the restart delay should be set for the approximate time it takes for the head pressure to bleed off of the compressor. For other applications, the restart delay is typically set between 2 and 10 seconds.
3. Trip delay adjustment: Rotate the “TRIP DELAY (SEC)” adjustment to the desired setting. This adjustment does not affect the trip delay on phasing faults. Typically, the trip delay adjustment is set between 1 and 5 seconds. In areas where voltage uctuations are frequent, the trip delay adjustment may be set greater than 10 seconds.
4. Voltage unbalance adjustment: Rotate the “UNBALANCE TRIP (NEMA%)” adjustment to the desired unbalance trip level. The NEMA MG1 standard does not recommend operating a motor above 1% voltage unbalance without derating the motor. The NEMA MG1 standard also recommends against operating a motor above a 5% voltage unbalance under any circumstances. SymCom recommends consulting the motor manufacturer for specic tolerances.
-3- 10/04
Page 4
POWER-UP
Turn on the 3-phase power to the motor. The MotorSaver’s green RUN light will blink during the RESTART delay. After the RESTART delay, the MotorSaver® will energize its output contacts and the green RUN light will illuminate. If the contacts do not energize and the RUN light does not illuminate, see the
TROUBLESHOOTING section.
DIAGNOSTIC INDICATOR LIGHTS
RUN
RESTART DELAY
REVERSE PHASE
UNBALANCE / SINGLE PHASE
HIGH / LOW VOLTAGE
CONGRATULATIONS!!
YOU HAVE JUST INSTALLED THE FINEST
MOTOR PROTECTION AVAILABLE!!
10/04 -4-
Page 5
TROUBLESHOOTING
RED
RED
SYMPTOM
No lights are on.
The unit seems
completely dead.
Red light is
blinking (on initial
power up).
Red light is
blinking (after the
motor has been
previously
running).
Red light is
blinking in this
pattern.
Red light is on
steady.
Green light blinks
and motor is not
running.
Green light is on
steady, but motor
does not start.
LIGHT
PATTERN
N / A
SOLUTION
Measure the three line-to-line voltages. If any of the voltages are below 350 VAC, the MotorSaver does not have enough power to operate its internal electronics. This may occur on a single-phased system. If the voltages are correct, call SymCom at 1-800-843-8848 or 1-605-348-5580.
Turn off the three-phase power. Swap any two leads powering the MotorSaver (L1, L2, or L3). There is a 50-50 chance of connecting L1, L2, and L3 correctly the rst time. Re-apply the three-phase power.
The incoming lines have been reverse phased. The MotorSaver is preventing the motor from running backwards. Correct the phase sequence.
The voltage is unbalanced or single-phased. Measure the incoming line voltages and calculate the % unbalance. If the voltage unbalance does not exceed the % unbalance reset value, call SymCom at 1-800-843-8848 or 1-605-348-5580.
The voltage is out of tolerance. Measure the three line-to-line voltages. Calculate the average of the three voltages. If the average is 7% above or below the nominal voltage as selected by the LINE VOLTAGE ADJUST, the MotorSaver is functioning properly. If the voltage is within ±7% of the selected line voltage, call SymCom at 1-800-843-8848 or 1-605-348-5580.
The MotorSaver is in restart delay.
The MotorSaver is in run mode. Ensure other control devices are allowing the motor to start. Check control circuit for loose wires or malfunctioning switches.
Any questions or comments call SymCom at 1-800-843-8848 or
1-605-348-5580
-5- 10/04
Page 6
SPECIFICATIONS
3 - Phase Line Voltage 475 - 600 VAC
Frequency 50* - 60 Hz
Low Voltage (% of setpoint)
Trip 90% ±1%
Reset 93% ±1%
High Voltage (% of setpoint)
Trip 110% ±1%
Reset 107% ±1%
Voltage Unbalance (NEMA)
Trip 2 - 8% Adjustable
Reset
Trip Setting minus 1% (5 - 8%)
Trip Setting minus 0.5% (2 - 4%)
Trip Delay Time
Low, High, and Unbalanced Voltage 1 - 30 Seconds Adjustable
Single-phasing faults (>25% UB) 1 Second Fixed
Restart Delay Time
After a fault or complete power loss 1 - 500 Seconds Adjustable
Output Contact Rating - SPDT
Pilot Duty 480 VA @ 240 VAC
General Purpose 10 A @ 240 VAC
Power Consumption 6 Watts (maximum)
Weight 14 oz
Enclosure Polycarbonate
Terminal
Torque 6 Inch-Pounds
Wire AWG 12 - 20 AWG
Safety Marks
UL UL508 (File # E68520)
CE IEC 60947-6-2
Standards Passed
Electrostatic Discharge (ESD)
IEC 1000-4-2, Level 3, 6 kv contact, 8 kv air
Radio Frequency Immunity, Radiated 159 MHz, 10 V/m
Fast Transient Burst
IEC 1000-4-4, Level 3, 3.5 kv input power and controls
*NOTE: 50 Hz will increase all delay timers by 20%
10/04 -6-
Page 7
Surge
2.350
IEC
ANSI / IEEE
Hi-potential Test
IEC 1000-4-5, Level 3, 4kv line-to-line; Level 4, 4kv line-to-ground
C62.41 Surge and Ring Wave Compliance to a level of 6kv line-to-line
Meets UL508 (2 x rated V +1000V for 1 minute)
Environmental
Temperature Range
Ambient Operating: -20° - 70° C (-4° - 158°F) Ambient Storage: -40° - 80° C (-40° - 176°F)
Class of Protection IP20, NEMA 1 (Finger Safe)
Relative Humidity 10-95%, non-condensing per IEC 68-2-3
DIMENSIONS
SymCom warrants its microcontroller based products against defects in material or workmanship for a period of ve (5) years* from the date of manufacture. All other products manufactured by SymCom shall be warranted against defects in material and workmanship for a period of two (2) years from the date of manufacture. For complete information on warranty, liability, terms, and conditions, please refer to the SymCom Terms and Conditions of Sale document.
-7- 10/04
Page 8
Visit our website at www.symcominc.com for our
complete catalog and new product listings!
2880 North Plaza Drive, Rapid City, SD 57702
Phone: (800) 843-8848 or (605) 348-5580
FAX: (605) 348-5685
Loading...