![](/html/c7/c7b7/c7b704b3ee3598f906eabc337d6be2e0c29a09a7b827d72d54602152d0e2f28f/bg1.png)
Single-Phase Voltage Monitor
Model 202-200-SP
Features:
• Protects motor from:
• High voltage
• Low voltage
• Small compact size saves precious panel space
• Quick mounting with a single screw
• Standard ¼” quick connects
• Adjustable restart delay
• Diagnostic LED
• UL listed*
• 5-year warranty
• Made in USA
The Model 202-200-SP is a voltage monitor designed to protect singlephase motors regardless of size. It is used on 190-240VAC, 50/60Hz motors
to prevent damage caused by low voltage or high voltage.
A unique microcontroller-based voltage sensing circuit constantly monitors
the single-phase voltage to detect harmful power line conditions. When a
harmful condition is detected, the 202-200-SP’s output relay is deactivated
after a xed trip delay. The output relay reactivates after power line
conditions return to an acceptable level and a specied amount of time has
elapsed (restart delay). The trip delay prevents nuisance tripping due to
rapidly uctuating power line conditions.
* Note: To obtain UL listing for the 202-200-SP, use insulated ¼” UL
recognized female quick connects.
(605) 348.5580 / (800) 843.8848 / Fax (605) 348.5685
customerservice@symcom.com / technicalsupport@symcom.com
Rev. 0610
![](/html/c7/c7b7/c7b704b3ee3598f906eabc337d6be2e0c29a09a7b827d72d54602152d0e2f28f/bg2.png)
Specications
Functional Specications
Low Voltage (% of setpoint)
Trip
Reset
High Voltage (% of setpoint)
Trip
Reset
Trip Delay Time
High and Low Voltage
Restart Delay Time
After a fault of complete power loss
90%
93%
110%
107%
4 seconds
Manual, 2-300 seconds (adjustable)
Input Characteristics
Supply Voltage
Frequency
190-240VAC +10%
50/60Hz (note: 50Hz will increase all delay timers by 20%)
Output Characteristics
Output Contact Rating-SPDT 480VA@240VAC Pilot Duty
10A@240VAC General Purpose
General Characteristics
Operating Temperature
Ambient
Maximum Input Power
Relative Humidity
Standards Passed
Electrostatic Discharge (ESD)
Surge
Safety Marks
UL
Dimensions
Weight
Mounting Method
-40o to 70o C (-40o to 158o F)
5 W
95%, non-condensing
IEC 61000-4-2, ±4kV
IEC 61000-4-5
UL508 (#E68520)
2.663” H x 2.663” W x 1.427” D
8 oz.
Surface Mount (with #8 screw)
Enclosure Dimensions
2.663
2.663
1.427
How to order:
Part Number: 202-200-SP
1.000
(605) 348.5580 / (800) 843.8848 / Fax (605) 348.5685
customerservice@symcom.com / technicalsupport@symcom.com
Rev. 0610