![](/html/7c/7c46/7c46b53873283e70cf658b0b88546e12efe34bf3688296415b9e8239e335bbba/bg1.png)
3-Phase Voltage Monitor
102-600
Features:
• Protects motor from:
• Phase loss (single phasing)
• Phase reversal
• Low voltage
• Voltage unbalance
• Diagnostic LED
• UL listed
• 5-year warranty
• Made in USA
The Model 102-600 is a voltage monitor designed to protect 3-phase, 475600VAC, 50/60Hz motors from damage caused by low voltage, voltage
unbalance, single phasing, and phase reversal.
A unique microcontroller-based voltage sensing circuit constantly monitors
the single-phase voltages to detect harmful power line conditions. When
a harmful condition is detected, the102-600’s output relay is deactivated
after a xed trip delay. The output relay reactivates after power line
conditions return to an acceptable level and a xed amount of time has
elapsed (restart delay). The trip delay prevents nuisance tripping due to
rapidly uctuating power line conditions.
(605) 348.5580 / (800) 843.8848 / Fax (605) 348.5685
customerservice@symcom.com / technicalsupport@symcom.com
Rev. 0610
![](/html/7c/7c46/7c46b53873283e70cf658b0b88546e12efe34bf3688296415b9e8239e335bbba/bg2.png)
Specications
Functional Characteristics
Low Voltage (% of setpoint)
Trip
Reset
Voltage Unbalance
Trip
Reset
Trip Delay Times
Low voltage
Unbalanced voltage and single-phasing faults (>15%UB)
Restart Delay Times
After a fault
Input Characteristics
Supply Voltage
Frequency
Output Characteristics
Output Contact Rating - SPDT
Pilot Duty
General Purpose
General Characteristics
Operating Temperature (Surrounding Air)
Maximum Input Power
Relative Humidity
Terminal Torque
Wire Gauge
Standards Passed
Electrostatic Discharge (ESD)
Radio Frequency Immunity (RFI), Radiated
Fast Transient Burst
Surge Immunity
IEC
Safety Marks
UL listed
Dimensions
Weight
Mounting Method
90% +1%
93% +1%
6%
4.5%
4 seconds
2 seconds
2 seconds
475-600VAC
50/60 Hz (note: 50Hz will increase all delay timers by 20%)
480VA @ 240VAC
10A @ 240VAC
-40o to 70o C (-40o to 158o F)
5 W
10-95%, non-condensing per IEC 68-2-3
7 in.-lbs.
12-22 AWG Solid or stranded
IEC 61000-4-2, Level 3, 6kV contact discharge and 8kV air discharge
10V/m
IEC 61000-4-4, Level 3, 4kV input power, 2kV inputs/outputs
IEC 61000-4-5, +6kV line to line, +6kV line to ground
UL508 (File #E68520)
2.93” H x 5.275” W x 2.95” D
14 oz.
Surface mountable, #8 screws
Enclosure Dimensions
4.50in
114.3mm
5.27in
133.9mm
0.15in[3.81mm] Typ.
1.47in
2.17in
Typ.
37.2mm
0.38in
55mm
2.93in
9.5mm
[74.9mm]
74.4mm
2.95in
Max
How to order:
Part Number: 102-600
(605) 348.5580 / (800) 843.8848 / Fax (605) 348.5685
customerservice@symcom.com / technicalsupport@symcom.com