Symcom 102600 Installation Guide

INSTALLATION INSTRUCTIONS
FOR SYMCOM’S MOTORSAVER
MODEL 102600
The Model 102600 is a three-phase voltage monitor designed to protect 600 VAC motors regardless of horsepower. It will protect 50 to 60 Hz motors from damage caused by single phasing, phase reversal, voltage unbalance, and low voltage.
CONNECTIONS
1.Mount the MotorSaver® in a convenient location in or near the motor control panel. If the location is wet or dusty, the MotorSaver® should be mounted in a NEMA 4 or 12 enclosure.
2.Connect the three lines of the motor’s three-phase power supply to L1, L2, and L3 on the MotorSaver® (see Figure No. 1).
3.Connect the output relay to the circuitry to be controlled (see Figure No. 1 and Figure No. 2). A. To control a motor, connect the normally open contact in series with the magnetic coil of the motor starter as shown in Figure 1. B. To sound an alarm, connect the normally closed contact in series with the alarm as shown in Figure 2.
Figure No.1: Typical Motor Control Wiring Diagram
2880 North Plaza Drive, Rapid City, SD 57702 • (800) 843-8848
Figure 2: Typical Alarm Wiring Diagram
SETTINGS
1.LINE VOLTAGE ADJUSTMENT: Rotate the LINE VOLTAGE ADJUSTMENT to the nominal three-phase line voltage feeding the motor.
POWER-UP
Turn on the power to the motor. The MotorSaver® then goes through its restart delay and the LED will flash green (see Table 1). After the restart delay, the MotorSaver® will energize its output contacts and the RUN LIGHT will turn solid green. If the contacts do not energize and the RUN LIGHT does not turn solid green, then see the TROUBLESHOOTING section.
RUN
RESTART DELAY
REVERSE PHASE
UNBALANCE / SINGLE PHASE
HIGH / LOW VOLTAGE
Table 1: Diagnostic Indicator Lights
07/09/03 -2-
TROUBLESHOOTING
SYMPTOM
No lights are on. The unit
seems completely dead
Red light is blinking
(On initial installation
power up).
Red light is blinking
(After the motor has been
previously running).
Red light is blinking in this
pattern.
Red light is on steady.
Green light blinks, but
motor is not running.
Green light is on steady, but motor does not start.
LIGHT
PATTERN SOLUTION
Measure the three line-to-line voltages. If any of the voltages are below 150 VAC, the MotorSaver
N/A
does not have enough power to operate its internal electronics. This may occur on a single-phased system. If the voltages are correct, call SymCom at 1-800-843-8848 or 1-605-348-5580.
Turn off the three-phase power. Swap any two leads powering the MotorSaver (L1, L2, or L3). There is a 50-50 chance of connecting L1, L2, and L3 correctly the rst time. Re-apply the three-phase power.
The incoming lines have been reverse phased. The MotorSaver is preventing the motor from running backwards. Correct the phase sequence.
The voltage is unbalanced or single-phased. Measure the incoming line voltages and calculate the % unbalance. If the voltage unbalance does not exceed the % unbalance reset value, call SymCom at 1-800-843-8848 or 1-605-348-5580.
The voltage is out of tolerance. Measure the three line-to-line voltages. Calculate the average of the three voltages. If the average is 7% above or below the nominal voltage as selected by the LINE VOLTAGE ADJUST, the MotorSaver is functioning properly. If the voltage is within ±7% of the selected line voltage, call SymCom at 1-800-843-8848 or 1-605-348-5580.
The MotorSaver is in restart delay.
The MotorSaver is in run mode. Ensure other con­trol devices are allowing the motor to start. Check control circuit for loose wires or malfunctioning switches.
SymCom warrants its microcontroller based products against defects in material or workmanship for a period of ve (5) years* from the date of manufacture. All other products manufactured by SymCom shall be warranted against defects in material and workmanship for a period of two (2) years from the date of manufacture. For complete information on warranty, liability, terms, and conditions, please refer to the SymCom Terms and Conditions of Sale document.
* The 520 Series has a one (1) year warranty and the LSRU series has a two (2) year warranty.
-3- 07/09/03
SPECIFICATIONS
3-Phase Line Voltage 475 to 600 VAC
Frequency 50 or 60 Hz
Note: 50 Hz will increase all delay timers by 20%
Low Voltage (% of setpoint)
Trip 90%
Reset 93%
Voltage Unbalance (NEMA)
Trip 6%
Reset 4.5%
Trip Delay Time
Low Voltage Faults 4 Seconds
Unbalance / Phasing Faults 2 Seconds
Restart Delay Time
After a fault or complete power loss 2 Seconds
Output Contact Rating - SPDT
Pilot Duty
General Purpose
Transient Protection IEC 1000-4-5 ; 1995 ± 6 kv
Power Consumption 5 Watts (maximum)
Weight 14 Ounces
Terminal
Wire AWG 12-22 Gauge
Maximum Torque 7 inch-pounds
Operating Temperature -40o to +70o C
UL E68520
480 VA @ 240 VAC
10 A @ 240 VAC
Visit our website at www.symcominc.com for our
complete catalog and new product listings!
2880 North Plaza Drive, Rapid City, SD 57702
Phone:(800) 843-8848 or (605) 348-5580
FAX: (605) 348-5685
Loading...