Symcom 102600 Installation Guide

INSTALLATION INSTRUCTIONS
FOR SYMCOM’S MOTORSAVER
MODEL 102600
The Model 102600 is a three-phase voltage monitor designed to protect 600 VAC motors regardless of horsepower. It will protect 50 to 60 Hz motors from damage caused by single phasing, phase reversal, voltage unbalance, and low voltage.
CONNECTIONS
1.Mount the MotorSaver® in a convenient location in or near the motor control panel. If the location is wet or dusty, the MotorSaver® should be mounted in a NEMA 4 or 12 enclosure.
2.Connect the three lines of the motor’s three-phase power supply to L1, L2, and L3 on the MotorSaver® (see Figure No. 1).
3.Connect the output relay to the circuitry to be controlled (see Figure No. 1 and Figure No. 2). A. To control a motor, connect the normally open contact in series with the magnetic coil of the motor starter as shown in Figure 1. B. To sound an alarm, connect the normally closed contact in series with the alarm as shown in Figure 2.
Figure No.1: Typical Motor Control Wiring Diagram
2880 North Plaza Drive, Rapid City, SD 57702 • (800) 843-8848
Figure 2: Typical Alarm Wiring Diagram
SETTINGS
1.LINE VOLTAGE ADJUSTMENT: Rotate the LINE VOLTAGE ADJUSTMENT to the nominal three-phase line voltage feeding the motor.
POWER-UP
Turn on the power to the motor. The MotorSaver® then goes through its restart delay and the LED will flash green (see Table 1). After the restart delay, the MotorSaver® will energize its output contacts and the RUN LIGHT will turn solid green. If the contacts do not energize and the RUN LIGHT does not turn solid green, then see the TROUBLESHOOTING section.
RUN
RESTART DELAY
REVERSE PHASE
UNBALANCE / SINGLE PHASE
HIGH / LOW VOLTAGE
Table 1: Diagnostic Indicator Lights
07/09/03 -2-
Loading...
+ 2 hidden pages