www.sylvania.com
QUICKTRONIC®DALI T8 Dimming
Professional Series
Lamp/Ballast Guide
32W T8 - OCTRON
1-lamp QTP1x32T8/DALI 2-lamp QTP2x32T8/DALI
Operates Lamp Types:
FO32 FBO32 FBO31
Key System Features
• Digital Addressable Control
• Individual control of fixtures
• Up to 16 groups
• Up to 16 scenes
• Programmable fade rates
• 1.0 ballast factor at full power
T8 DALI
• Universal input voltage (120/277V)
• Programmed rapid start
• QUICK 60+®lamp and ballast warranty
• Anti-flash circuitry – turns on at previous light level
• Operates >40kHz to reduce potential IR interference
• Control may be wired for Class 1 or Class 2 applications
• Wiretrap connectors
• UL, cUL, FCC
Application Information
SYLVANIA QUICKTRONIC DALI Dimming is ideally suited for:
• All size offices
• Daylight harvesting
• Energy management
• Load shedding
• A/V presentations
• Conference rooms
• Occupancy sensors
• Creative lighting designs
For optimal dimming performance, fluorescent lamps may require seasoning up to 100 hours prior to dimming to the lowest light levels.
®
SYLVANIA QUICKTRONIC DALI Dimming
combines digital control technology with full-range continuous dimming to provide a new level of lighting system performance. This allows for greater flexibility and control of the lighting environment than can be achieved with traditional 0-10VDC dimming systems. The communications protocol is “DALI”, an acronym for “Digital Addressable Lighting Interface”. This is a worldwide standard for digital lighting control that has been accepted by all the leading lighting suppliers.
SYSTEM 32 DALI controls OCTRON T8 lamps over a wide (100-1%) range of light level settings, from 1.0 ballast factor to .01 ballast factor. Control wiring is simplified by two polarity-free connections that can be routed in the same raceway as power wires.
SYSTEM 32 DALI is available in one and two lamp models that operate at 120V or 277V input line voltage, eliminating “wrong voltage” wiring errors and reducing the number of models in inventory by half.
System Information
Programmed rapid start ballasts provide optimum starting conditions to provide up to 100,000 switching cycles for use on occupancy sensor and building control system applications.
Individual addressability allows the user to dim any particular fixture or groups of fixtures at one time. Simple controller programming steps allow for:
1. Fade rates, dim levels, time of day, groups and scenes to be customized.
2. Flexibility in grouping fixtures; (no need to re-wire fixtures when groups need to be changed.
3. Systems are scalable and can be expanded anytime user needs change, without the need for costly re-wiring. Additional fixtures are added to groupings simply by means of software.
Electronic T8 Fluorescent
Digital Dimming Systems
SYSTEM 32 DALI offers full rated lamp output (1.0 ballast factor) at the maximum light setting. Compared to “normal” systems (0.88 ballast factor), this allows for higher light levels when desired and can be used to compensate for lamp lumen depreciation. Setting the standard for quality, SYSTEM 32 DALI is also
$ SAVINGS PER YEAR* vs LIGHT LEVEL
$25.00
$20.00
$15.00
$10.00
$ SAVINGS Per Year
$5.00
$0.00
0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
When used in conjunction with appro­priate controls, feedback can be obtained on operating conditions, such as operating hours, light-level or failed lamps. This lamp fault-reporting feature can save significant cost by quickly identifying the location, especially in large facilities or in applications where lamps are concealed by lenses.
(FO32T8 Lamps, QUICKTRONIC DALI T8 Ballasts)
$23.20
2 Lamp Fixture
$12.00
1 Lamp Fixture
covered by our QUICK 60+ first and most comprehensive system warranty in the industry.
Light Level
*Based on 4,000 burn hrs/yr & $0.10/kWh
SYSTEM 32 DALI lighting systems can also be integrated with Building Management Systems (BMS) by installing gateways that translate between the DALI and BMS systems. Specification of DALI compatible gateways, controls and ballasts ensure flawless operation of the lighting system.
®
warranty, the
92
SPECIFICATION DATA
QTP1x32T8/UNV DALI
LAMP
Green White Black
Purple Purple
DALI
DIMMING
BALLAST
1 2 3 4
Red
Red Blue Blue
DALI Control Leads (non-polarized) Class 1 or Class 2 Circuit
G N L
LAMP 2
LAMP 1
QTP2x32T8/UNV DALI
DALI
DIMMING
BALLAST
1 2 3 4 5 6
Red Red Yel lo w
Yel lo w Blue Blue
Green
White Black
Purple Purple
DALI Control Leads (non-polarized) Class 1 or Class 2 Circuit
G N L
Width
Height
Mounting
Length
Length
Catalog # Date Type
Project Prepared by
Comments
T8 DALI
Professional Series
Electronic DALI T8 Fluorescent Controllable Lighting Systems (120/277V)
Input Rated Ballast Input System Item Current Lamp Lumens No. of Factor System Power Efficacy Number Description (AMPS) Type (lm) Lamps (BF) Lumens (Watts) (lm/W) BEF
51350 QTP 1x32T8/UNV DALI 0.31/0.13 FO32XP 3000 1 1.00 3000 36 83 2.78
0.01 30 6
51352 QTP 2x32T8/UNV DALI 0.61/0.26 FO32XP 3000 2 1.00 6000 72/70 83/86 1.43
0.01 60 12
1: Ballast Efficiency Factor (BEF) = (Ballast Factor x 100) divided by Input Power (Note: calculation based on lowest wattage value).
Wiring Diagrams:
Wiring: Push-in (wiretrap) connections Use 18 AWG solid copper wire only
Performance Guide
Data shown based upon SYLVANIA
®
OCTRON TRONIC®DALI ballasts are also
1
FO32/XP™lamps. QUICK-
compatible with other manufacturers equivalent lamp types that meet ANSI specifications.
Specifications
Starting Method: Programmed
Rapid Start
Circuit Type: Series Lamp Frequency: >40kHz Lamp CCF: <1.7 Starting Temp: 50°F (10°C) min. Input Frequency: 50/60 Hz THD: <10% @ full output Power Factor: >98% @ full output Voltage Range: ±10% of 120/277
rated voltage
UL Listed Class P, Indoor cUL Certified Temp. Test Point (Tc) on ballast label: 1 lamp model: 65°C max 2 lamp model: 70°C max. All other points on ballast: 75°C max. FCC 47CFR Part 18 Non-Consumer Class A Sound Rating ANSI C62.41 Cat. A Transient Protection No Remote or Tandem Wiring
T8 DALI
Packaging:
Quantity: 25 pieces Weight: 1.2 lbs each (approx.)
Dimensions:
Units L ML W H
inches 18.05 17.70 1.18 1.18
mm 458.5 449.6 30.0 30.0
Item Number 51352 QTP 2 x 32T8 / UNV DALI
QUICKTRONIC PROFESSIONAL
Number of Lamps
Specifications subject to change without notice.
Control Information
QUICKTRONIC DALI ballasts are compatible with DALI digital controllers available from various manufacturers. For a list of DALI control manufacturers, please contact OSRAM SYLVANIA.
Refer to pages 100 & 101 for controls information.
Control Specifications:
Two wire non-polarized control. May be wired as Class 1 or Class 2 circuit, consult Local and National Electrical Codes.
OSRAM SYLVANIA National Customer Service and Sales Center
System Type - DALI
Line Voltage (120/277V)
Primary Lamp Type (F32T8)
1-800-LIGHTBULB (1-800-544-4828) www.sylvania.com