dimming inputs from 0-10V and/
or two-wire AC dimming providing
maximum flexibility
• Compatible with low voltage and
power line fluorescent dimmers
• High Efciency
• NEMA Premium Electronic Ballast
Program compliant
• Lamp Detection Technology
• Universal voltage (120-277V)
• 100 - 5% Dimming Range
• PROStart® Programmed Rapid Start
• Anti-ash circuitry - turns on in
dimmed mode
• Operates at >42kHz
• QUICK 60+ ballast and lamp warranty
• RoHS compliant
• Lead-free solder and manufacturing
process
Application Information
SYLVANIA QUICKTRONIC
POWERSENSE ballasts
are ideally suited for:
• Occupancy sensors
• Daylight harvesting
• Energy management
• Load shedding
• New construction
• Retrot
ECS201R2 - 8/2011
SYLVANIA QUICKTRONIC High Efficiency,
POWERSENSE T8 electronic ballasts offer
several advantages:
• Wide Dimming Range: operate linear
fluorescent T8 lamps over a 100-5%
dimming range and provide true
versatility in controls selection.
• Industry’s Most Adaptable Dimming
Ballast: ballasts feature micro-controller
technology for compatibility with:
• low voltage controls
• power line uorescent dimmers
• any line voltage from 120V to 277V
• Unmatched Performance: patented
lamp detection technology that virtually
eliminates variations in brightness from
lamp-to-lamp and provides uniform
lighting throughout the dimming range.
At light levels of >75% unnecessary
lamp-coil power is turned off, delivering
energy efficiences comparable to nondimming Instant start electronic ballast.
This technology also eases installation
and troubleshooting by recognizing
failed lamps, faulty wiring or loose
connections, and shutting down.
System Information
QUICKTRONIC POWERSENSE ballasts operate from standard low
voltage (0-10VDC) fluorescent controllers or compatible 2-wire
power line fluorescent dimmers, making them ideal for individual
office lighting or automated building applications, both in new
construction and retrofit projects.
For the individual office or conference room, installation can be
streamlined by using a 2-wire power line fluorescent dimmer;
eliminating the need for additional control wires.
For more advanced systems, such as daylight harvesting or
building automation applications, standard low voltage devices
SAVINGS PER YEAR* vs LIGHT LEVEL
$50.00
$38.28
$40.00
$30.00
$19.80
$20.00
Savings per Year ($)
2 Lamp Fixture
$10.00
$0.00
0%25%50%75%100%
* FO32/XP lamps with QUICKTRONIC T8 POWERSENSE ballast
* Based on 4000 hrs/yr, $0.11/kWh, and 120V operation
* Savings per Year (@Light Level) = Cost of operation (100% Light Level) - Cost of operation (@Light Level)
(QTP T8 Dimming Ballast)
Light Level (%)
4 Lamp Fixture
When the problem is corrected,
the system restarts automatically.
• NEMA Premium Electronic Ballast
Program compliant. This program
promotes the use of high efficiency
T8 electronic ballasts by meeting
or exceeding the Ballast Efficiency
Factors, (BEF) established by the CEE,
(Consortium for Energy Efficiency). For
additional information on this program
go to: www.cee1.org or www.nema.org
(0-10VDC, Class 1 or 2) are used to control the lighting system.
In this daylight harvesting example, each lighting fixture (or
xture row) is controlled by it’s own photosensor; regulating
the light output to compensate for changes in natural daylight.
Depending upon the specific application, energy savings of up
to 60% compared to fixed output T8 electronic systems can be
realized.
All QUICKTRONIC POWERSENSE ballasts include a line voltage
protection circuit, which protects the ballast in the event that line
voltage is inadvertently applied to the low voltage control inputs.
Fixture
Window / Natural Light Source
Fluorescent Controllable
Lighting Systems
These ballasts are RoHS compliant
and feature lead-free solder and
manufacturing process.
Setting the standard for quality,
QUICKTRONIC POWERSENSE ballasts
are covered by the QUICK 60+®
warranty, the first and most
comprehensive lamp & ballast
system warranty in the industry.
DAYLIGHT HARVESTING SCENARIO
Light
1
Sensor 1
Fixture
2
Light
Sensor 2
Fixture
3
Desired Illuminance E
Constant setpoint value
Light
Sensor 3
POWERSENSE
T8 DIM
r
Page 2
QTP2x28T5/UNV DIM TCL
POWERLINE CONTROL
LINE
BLACK
NEUTRAL
WHITE
INSULATEUNUSED LEADS
VIOLET
(+)
GREY(-)
SPECIFICATION DATA
Catalog # Date Type
Project Prepared by
Comments
T8 POWERSENSE
High Efficiency
QUICKTRONIC® POWERSENSE® Controls Information
Fluorescent Building
Controls Powerline 0-10 VDC Photo Occupancy Management
Manufacturer Controllers Controllers Cells Sensors Systems
Cooper Greengate
http://greengate.coopercontrol.com
CONTROLS
Encelium
POWERSENSE
www.encelium.com
Hunt Dimming
www.huntdimming.com
Lehigh Electric Products
www.lehighdim.com
Leviton
www.leviton.com
Sensor Switch
www.sensorswitch.com
Siemens Building Technology
http://sbt.siemens.com
Starfield Controls
www.starfieldcorp.com
Watt Stopper
www.wattstopper.com
Please contact controls manfacturer to order/specify controls. For the latest controls list go to www.sylvania.com
Also, for more information, refer to the LCA (Lighting Controls Association) site: http://lightingcontrolsassociation.org
Dimensions:
1 & 2 lamp enclosure
Overall: 9.5" L x 1.68" W x 1.0" H (241 x 43 x 25 mm)
Mounting: 8.90" (226 mm)
Weight: 1.1 lbs each (500 g)
3 & 4 lamp enclosure
Overall: 16.7" L x 1.68" W x 1.0" H (425 x 43 x 25 mm)
Mounting:16.2" (411 mm)
Weight: 2.1 lbs each (950 g)
Wiring:
Leads Only
Input & Control
Wiring Options:
LOW-VOLTAGE CONTROL
LINE
NEUTRAL
Class 1 or
Class 2
Please consult manufacturers listed for their latest control models and to order their controls.
Specifications subject to change without notice.
X X X X X
X X X X X
X X X X X
X X X X
X X X X
X X X
X X X
X X X X
X X
X X X X
X X X X X
Mounting
Length
Length
Mounting
411.3mm
(16.2")
Length
425mm
(16.7")
Height
25.4mm
(1.0")
Height
8.70 mm
Slot
Width
POWERLINE CONTROL
BLACK
WHITE
VIOLET
GREY (-)
(+)
0-10V
< 0.5mA
BLACK
WHITE
VIOLET
(+)
DC
GREY (-)
LINE
NEUTRAL
INSULATE
UNUSED LEADS
Control Specifications/model numbers may change.
Width
43mm
(1.68")
Controls Guide
X
Install and wire these ballast and controls
in accordance with the National Electrical
Code (NEC), all applicable Federal, State and
local electrical codes, as well as the specific
instructions provided with the compatible
control that you purchased. Installation should
be performed by qualified personnel only.
These instructions are guidelines only.
Installation may vary for different controls/
fixtures/applications. Be sure to follow the
control instructions and all applicable codes
and standards when installing dimming
systems.
Please contact controls manufacturer listed
in the OSRAM SYLVANIA Inc. controls cross
reference for compatible controls and
instruction wiring.
NOTES:
1. Dimming ballasts source < 0.5mA
(0-10VDC control input).
2. Powerline controls must be rated for the
type (e.g. Fluorescent Phase-control)
and size (e.g. 600W, 1000W, 1500W &
2000W etc.) of the connected load. Do
NOT use incandescent powerline controls;
incandescent dimmers are not rated for
fluorescent loads and are NOT compatible
with POWERSENSE ballasts.
OSRAM SYLVANIA
National Customer
Service and Sales Center
1-800-LIGHTBULB
(1-800-544-4828)
www.sylvania.com
Warning
Page 3
To
Fluorescent
Lamps
Violet (+)
DIMMING
BALLAST
Black
White
Photo Sensor 0-10V Wiring Example
0-10V DC Control with POWERSENSE Ballasts
0-10V
Control
Gray (-)
Neutral (White)
120 or 277V
Black (Hot)
LINE
Gray
Violet
Class 1 or Class 2 circuit
To
Fluorescent
Lamps
Violet (+)
DIMMING
BALLAST
Black
White
Gray (-)
To
Additional
Ballasts
Photo
Sensor
0-10V
Standard
Line Voltage
Switch
Black
Photo Sensor 0-10V Wiring Example
0-10V DC Control with POWERSENSE Ballasts
SPECIFICATION DATA
Catalog # Date Type
Project Prepared by
Comments
QUICKTRONIC® POWERSENSE® T8 Dimming UNV - Dimming Control Wiring Examples
Industry’s 1st Ballast That Allows POWERLINE Fluorescent Control AND 0-10Vdc Control Input Simultaneously
T8 POWERSENSE
High Efficiency
2-wire Powerline AND 0-10Vdc Control with POWERSENSE Ballasts
2-wire
Fluorescent
Fluorescent AC Dimming
No Control Wires
• Occupant Wallbox Dimming
• Lighting Panel Dimming
• Excellent for Retrofit
0-10Vdc Low Voltage
Industry Standard Interface
• Daylight Harvesting
• Building Management
• Demand Response Override
120 or 277V
Black (Hot)
LINE
Neutral (White)
Powerline Dimmer
Black
0-10V
Control
Violet
Black
White
Violet (+)
Gray (-)
Gray
DIMMING
BALLAST
Class 1 or Class 2 circuit
Wallbox Style 2-wire Powerline Control Wiring Example
Specification-grade controls are available for 120V or 277V
Powerline Control Specs:
operation of controllable analog electronic fluorescent ballasts.
Controls must be suitably rated for both the type (e.g. Fluorescent
Phase-control) and size (e.g. 600W) of the connected load.
ELOGIC™ MANUAL CONTROL SLIDE FLUORESCENT PHASE CUT DIMMER
Maximum Input Current (A)
Item OSRAM SYLVANIA (# of gangs) Input Integral
Number Description Single Double Triple Voltage (V) Color Switch
45045 ELMC-SL-FLPCWALL/120-WH
45046 ELMC-SL-FLPCWALL/277-WH
5.0A 4.5A 4.0A
2.2A 2.0A 1.7A
120
277
Black (Hot)
LINE
Neutral (White)
White
White
2-wire Powerline Control with POWERSENSE Ballasts
2-wire
Fluorescent
Powerline Dimmer
Single Pole
Wallbox Style 0-10V Control with Power Switch Wiring Example
Black
White
To
Fluorescent
Lamps
Black
Black
White
Violet (+)
Gray (-)
For 2-wire Powerline wiring, individually insulate (cap-off)
DIMMING
Violet (+)
BALLAST
Gray (-)
DIMMING
BALLAST
CAUTION:
all unused Violet & Gray leads as shown.
To
Fluorescent
Lamps
To
Fluorescent
Lamps
To
Additional
Ballasts
Black
White
Violet (+)
Gray (-)
DIMMING
BALLAST
To
Fluorescent
Lamps
Examples: Leviton IPX series operate as
single pole or 3-way models. Available in
120V and 277V models. Leviton 6668-1W
(white) 120V single pole fluorescent dimmer.
To
Additional
Ballasts
WIRING & CONTROLS
POWERSENSE
Examples: Lithonia model ISD BC
or Leviton IP 710 Series (These
0-10V dc, 120/277V models can be
wired for single pole application
(shown); these models can also be
wired for 3-way applications.)
OSRAM SYLVANIA National Customer Service and Sales Center 1-800-LIGHTBULB (1-800-544-4828) www.sylvania.com
Specifications subject to change without notice.
0-10V DC Control with POWERSENSE Ballasts
120 or 277V
Black (Hot)
LINE
Neutral (White)
0-10Vdc
Wallbox
Control with
Line Voltage
Switch
Black
Line
Voltage
Switch
0-10V
Control
Black
White
DIMMING
Violet (+)
BALLAST
Gray (-)
Class 1 or Class 2 circuit
Black
Violet
Gray
Photo Sensor 0-10V Wiring Example
Ballast Output Max.
Item OSRAM SYLVANIA Control Voltage Input Lamp
Number Description Type Method (VDC) Current (mA) Type
45030 ELSC-DLH-TVLAMP/BUS
Daylight Harvesting
To
Fluorescent
Lamps
On/Off
Switch (120/277V)
Slide Dimmer
0-10V
Black
White
DIMMING
Violet (+)
BALLAST
Gray (-)
ELOGIC DAYLIGHT SENSOR ORDERING INFORMATION
Sensor & Control for
To
Fluorescent
Lamps
Analog 0-10V 6 T8 or T5 or T5HO
To
Additional
Ballasts
Page 4
SPECIFICATION DATA
BlackWhite
Violet (+)Grey (-)
RedRed
BlueBlue
LAMP 1
ELECTRONIC
BALLAST
Catalog # Date Type
Project Prepared by
Comments
T8 POWERSENSE
High Efficiency
®
High Efficiency, T8 Controllable Lighting Systems, UNV (120-277V)
Input Rated Ballast Input System
Item OSRAM SYLVANIA Current Lamp Lumens No. of Factor System Mean Power (W) Efficacy
Number Description (AMPS) Type (lm) Lamps (BF) Lumens Lumens 120V 277V (lm/W) BEF
Products are all 10-pack. *Striation might occur with SUPERSAVER lamps.
1: System Efficacy calculation based on lowest input power value.
2: Ballast Efficiency Factor (BEF) shown = (Ballast Factor x 100) divided by Input Power (Note: calculation based on lowest wattage value).
Wiring Diagrams
ballast diagram. Lamp Seasoning: For optimal performance, fluorescent lamps may require seasoning for up to 12 hours prior to low temperature starting &
low level dimming. Refer to NEMA LSD 23-2002 Lighting Systems Division: Recommended Practice — Lamp Seasoning for Fluorescent Dimming Systems
1 lamp
Black
White
Violet (+)
Grey (-)
3 lamp
Black
White
Violet (+)
Grey (-)
Item Number 50707 QTP 2 x 32T8 / UNV DIM-TC
QUICKTRONIC
Number of Lamps (1, 2, 3, 4)
SYLVANIA, the system solution, QUICK60+, POWERSENSE, See the World in a New Light, PROStart, OCTRON and SUPERSAVER are registered trademarks of OSRAM SYLVANIA Inc.
ELOGIC is a trademark of OSRAM SYLVANIA Inc. QUICKTRONIC is a registered trademark of OSRAM AG. NEMA Premium is a registered trademark of National Electrical Manufacturers Association.
ELECTRONIC
BALLAST
ELECTRONIC
BALLAST
LAMP 1
Red
Red/White
Red/Black
Red/White
Yellow
Yel/Blk
Yellow
Blue
Output Wiring: Lamp wiring for dimming ballasts can differ significantly from non-dimming ballasts and from
other manufacturers dimming ballasts. Take care to connect lamp lead wires as shown on the applicable
2 lamp
Black
Red
Red
Blue
Blue
White
Violet (+)
Grey (-)
ELECTRONIC
BALLAST
LAMP 1
LAMP 1
LAMP 2
4 lamp
LAMP 1
LAMP 2
LAMP 3
Black
White
Violet (+)
Grey (-)
ELECTRONIC
BALLAST
Red
Red/White
Red/Black
Red/White
Yellow
Yellow/Black
Yellow
Blue/White
Blue/Black
Blue/White
Blue
Red
Red
Blue
Blue
Yel/Blk
Yellow
Yellow
LAMP 1
LAMP 2
LAMP 3
LAMP 4
System Type - DIMMING/Case Size
Line Voltage (120-277V)
Primary Lamp Wattage
Performance Guide
1
Data based on SYLVANIA OCTRON® lamps
shown. QUICKTRONIC® POWERSENSE
ballasts are also compatible with other
2
manufacturers equivalent lamp types that
meet ANSI specifications, including F17,
F25, F32, U-Bend equivalent lamps and
SUPERSAVER lamps.
Specifications
Data based on F32T8
Starting Method: Programmed Rapid Start
Circuit Type: Series
Lamp Frequency: >40 kHz
Lamp CCF: Less than 1.7
Starting Temp: 50°F/10°C minimum
for OCTRON T8 lamps
Input Voltage: 120-277V, ±10%
Input Frequency: 50/60 Hz
THD: <10% @ Full Output
Power Factor: >98% @ Full Output
UL Listed Class P, Type 1 Outdoor
CSA or C/UL Certified
70°C Max Case Temperature
FCC 47CFR Part 18 Non-Consumer
Class A Sound Rating
RoHS compliant
3
ANSI C62.41 Cat. A Transient Protection
Remote mounting (Max. wire length from
ballast case to lampholder)
• up to 8ft for full wattage T8s
• no remote mounting for SUPERSAVER
3 Complies with European Union Restriction
of Hazardous Substances Directive (Directive
EC 2002/95)
Control Information
QUICKTRONIC POWERSENSE ballasts are
compatible with a wide range of low voltage
(0-10VDC) and power line fluorescent controllers
available from various manufacturers.
Low Voltage Control Specs: Ballast will source
up to 0.5mA for 0-10VDC control purposes.
May be wired as a Class 1 or Class 2 circuitconsult Local and National Electrical Codes.
Power Line Control Specs: Specificationgrade fluorescent controls are available
for 120V or 277V operation of controllable
analog electronic fluorescent ballasts.
Controls must be suitably rated for both the
type (e.g. Fluorescent Phasecontrol) and size
(e.g. 600W) of the connected load.
System Life / Warranty
QUICKTRONIC products are covered by the
QUICK 60+® warranty, a comprehensive
lamp and ballast system warranty. For
additional details, refer to the QUICK 60+
warranty bulletin.
OSRAM SYLVANIA
National Customer
Service and Sales Center