32W T8 - SYLVANIA OCTRON® lamps
1-lamp QTP1x32T8/UNV DIM 2-lamp QTP2x32T8/UNV DIM 3-lamp QTP3x32T8/UNV DIM 4-lamp QTP4x32T8/UNV DIM
Primary Lamp Types
FO32, FBO32 & FBO31
Also operates:
FO30/SS, FO28/SS, FO25/SS, FO25, FO17, FBO24 & FBO16
Key System Features
• Industry’s rst ballast that combines
dimming inputs from 0-10V and/ or two-wire AC dimming providing maximum flexibility
• Compatible with low voltage and
power line fluorescent dimmers
• High Efciency
• NEMA Premium Electronic Ballast
Program compliant
• Lamp Detection Technology
• Universal voltage (120-277V)
• 100 - 5% Dimming Range
• PROStart® Programmed Rapid Start
• Anti-ash circuitry - turns on in
dimmed mode
• Operates at >42kHz
• QUICK 60+ ballast and lamp warranty
• RoHS compliant
• Lead-free solder, printed circuit board
and manufacturing process
Application Information
SYLVANIA QUICKTRONIC POWERSENSE ballasts
are ideally suited for:
• Occupancy sensors
• Daylight harvesting
• Energy management
• New construction
• Retrot
SYLVANIA QUICKTRONIC High Efficiency, POWERSENSE T8 electronic ballasts offer
several advantages:
• Wide Dimming Range: operate linear fluorescent T8 lamps over a 100-5% dimming range and provide true versa­tility in controls selection.
• Industry’s Most Adaptable Dimming
Ballast: ballasts feature micro-controller technology for compatibility with:
• low voltage controls
• power line uorescent dimmers
• any line voltage from 120V to 277V
• Unmatched Performance: patented lamp detection technology that virtually eliminates variations in brightness from lamp-to-lamp and provides uniform lighting throughout the dimming range. At light levels of >75% unnecessary lamp-coil power is turned off, delivering energy efficiences comparable to non­dimming Instant start electronic ballast. This technology also eases installation and troubleshooting by recognizing failed lamps, faulty wiring or loose connections, and shutting down.
System Information
QUICKTRONIC POWERSENSE ballasts operate from standard low voltage (0-10VDC) fluorescent controllers or compatible 2-wire power line fluorescent dimmers, making them ideal for individual office lighting or automated building applications, both in new construction and retrofit projects.
For the individual office or conference room, installation can be streamlined by using a 2-wire power line fluorescent dimmer; eliminating the need for additional control wires.
For more advanced systems, such as daylight harvesting or building automation applications, standard low voltage devices (0-10VDC, Class 1 or 2) are used to control the lighting system. In this daylight harvesting example, each lighting fixture (or fixture row) is controlled by it’s own photosensor; regulating the light output
When the problem is corrected, the system restarts automatically.
• NEMA Premium Electronic Ballast
Program compliant. This program promotes the use of high efficiency T8 electronic ballasts by meeting or exceeding the Ballast Efficiency Factors, (BEF) established by the CEE, (Consortium for Energy Efficiency). For additional information on this program
to compensate for changes in natural daylight. Depending upon the specific application, energy savings of up to 60% compared to fixed output T8 electronic systems can be realized.
Daylight Harvesting Scenario
Fixture
Light Sensor 1 Light Sensor 2 Light Sensor 3
1
Window / Natural Light Source
Fluorescent Controllable
Lighting Systems
go to: www.cee1.org or www.nema.org
These ballasts are RoHS compliant and feature lead-free solder, printed circuit boards and manufacturing process.
Setting the standard for quality, QUICKTRONIC POWERSENSE ballasts are covered by the QUICK 60+® warranty, the first and most comprehensive lamp & ballast system warranty in the industry.
All QUICKTRONIC POWERSENSE ballasts include a line voltage protection circuit, which protects the ballast in the event that line voltage is inadvertently applied to the low voltage control inputs.
Fixture
2
Fixture
3
Desired Illuminance E
Constant setpoint value
r
P O W E R S E N S E
T 8 D I M
ECS201 – 2/2011
QTP2x28T5/UNV DIM TCL
POWERLINE CONTROL
LINE
BLACK
NEUTRAL
WHITE
INSULATE UNUSED LEADS
VIOLET
(+)
GREY (-)
SPECIFICATION DATA
Catalog # Date Type
Project Prepared by
Comments
T8 POWERSENSE
High Efficiency
QUICKTRONIC® POWERSENSE® Controls Information
Fluorescent Building Controls Powerline 0-10 VDC Photo Occupancy Management Manufacturer Controllers Controllers Cells Sensors Systems
SYLVANIA ELOGIC™ Controls 1-800-LIGHTBULB www.sylvania.com x x x x
Encelium www.encelium.com x
Hunt Dimming www.huntdimming.com x x x x x
Lehigh Electronic Products
C O N T R O L S
www.lehighdim.com x x x x x
P O W E R S E N S E
Leviton Lighting Controls www.leviton.com x x x x
Lightolier Controls www.lolcontrols.com x x x x x
Lithonia Controls www.lithonia.com x x x x x
Lumisys www.lumisys1.com x x x
PCI www.pcilightingcontrols.com x x
Sensorswitch www.sensorswitch.com x x
Siemens Energy & Automation www.sea.siemens.com x
Starfield Controls www.starfieldcontrols.com x x x x
The Watt Stopper, Inc www.wattstopper.com x x
Please contact controls manufacturers to order/specify controls. For the latest controls list go to www.sylvania.com
Also for more information, check out the LCA (Lighting Controls Association) site: www.aboutlightingcontrols.org
Dimensions: 1 & 2 lamp enclosure
Overall: 9.5" L x 1.68" W x 1.0" H (241 x 43 x 25 mm) Mounting: 8.90" (226 mm) Weight: 1.1 lbs each (500 g)
3 & 4 lamp enclosure
Overall: 16.7" L x 1.68" W x 1.0" H (425 x 43 x 25 mm) Mounting:16.2" (411 mm) Weight: 2.1 lbs each (950 g)
Wiring:
Leads Only
Input & Control Wiring Options:
LOW-VOLTAGE CONTROL
LINE
NEUTRAL
0-10V
< 0.5mA
DC
Class 1 o r Class 2
Control Specifications/model numbers may change.
Please consult manufacturers listed for their latest control models and to order their controls.
Specifications subject to change without notice.
BLACK
WHITE
VIOLET
GREY (-)
(+)
Height
25.4mm (1.0")
Height
8.70 mm Slot
Width
Mounting
Length
Length
Mounting
411.3mm (16.2")
Length 425mm (16.7")
POWERLINE CONTROL
LINE
NEUTRAL
INSULATE UNUSED LEADS
BLACK
WHITE
VIOLET
GREY (-)
(+)
Width 43mm (1.68")
Controls Guide
Warning
Install and wire these ballast and controls in accordance with the National Electrical Code (NEC), all applicable Federal, State and local electrical codes, as well as the specific instructions provided with the compatible control that you purchased. Installation should be performed by qualified personnel only.
These instructions are guidelines only. Installation may vary for different controls/ fixtures/applications. Be sure to follow the control instructions and all applicable codes and standards when installing dimming systems.
Please contact controls manufacturer listed in the OSRAM SYLVANIA Inc. controls cross reference for compatible controls and instruction wiring.
NOTES:
1. Dimming ballasts source < 0.5mA (0-10VDC control input).
2. Powerline controls must be rated for the type (e.g. Fluorescent Phase-control) and size (e.g. 600W, 1000W, 1500W & 2000W etc.) of the connected load. Do NOT use incandescent powerline controls; incandescent dimmers are not rated for fluorescent loads and are NOT compatible with POWERSENSE ballasts.
OSRAM SYLVANIA National Customer Service and Sales Center
1-800-LIGHTBULB (1-800-544-4828) www.sylvania.com
To Fluorescent Lamps
Violet (+)
DIMMING BALLAST
Black White
Photo Sensor 0-10V Wiring Example
0-10V DC Control with POWERSENSE Ballasts
0-10V
Control
Gray (-)
Neutral (White)
120 or 277V Black (Hot)
LINE
Gray
Violet
Class 1 or Class 2 circuit
To Fluorescent Lamps
Violet (+)
DIMMING
BALLAST
Black White
Gray (-)
To Additional Ballasts
Photo
Sensor
0-10V
Standard
Line Voltage
Switch
Black
Photo Sensor 0-10V Wiring Example
0-10V DC Control with POWERSENSE Ballasts
SPECIFICATION DATA
Catalog # Date Type
Project Prepared by
Comments
QUICKTRONIC® POWERSENSE® T8 Dimming UNV - Dimming Control Wiring Examples
Industry’s 1st Ballast That Allows POWERLINE Fluorescent Control AND 0-10Vdc Control Input Simultaneously
T8 POWERSENSE
High Efficiency
2-wire Powerline AND 0-10Vdc Control with POWERSENSE Ballasts
2-wire Fluorescent
Fluorescent AC Dimming No Control Wires
• Occupant Wallbox Dimming
• Lighting Panel Dimming
• Excellent for Retrofit
0-10Vdc Low Voltage Industry Standard Interface
• Daylight Harvesting
• Building Management
• Demand Response Override
120 or 277V Black (Hot)
LINE
Neutral (White)
Powerline Dimmer
Black
0-10V
Control
Violet
Black White
Violet (+)
Gray (-)
Gray
DIMMING BALLAST
0-10V
Class 1 or Class 2 circuit
Wallbox Style 2-wire Powerline Control Wiring Example
Specification-grade controls are available for 120V or 277V
Powerline Control Specs:
operation of controllable analog electronic fluorescent ballasts.
Controls must be suitably rated for both the type (e.g. Fluorescent
Phase-control) and size (e.g. 600W) of the connected load.
ELOGIC™ MANUAL CONTROL SLIDE FLUORESCENT PHASE CUT DIMMER
Maximum Input Current (A) Item OSRAM SYLVANIA (# of gangs) Input Integral Number Description Single Double Triple Voltage (V) Color Switch
45045 ELMC-SL-FLPCWALL/120-WH
45046 ELMC-SL-FLPCWALL/277-WH
5.0A 4.5A 4.0A
2.2A 2.0A 1.7A
120
277
Black (Hot)
LINE
Neutral (White)
White
White
2-wire Powerline Control with POWERSENSE Ballasts
2-wire Fluorescent Powerline Dimmer
Single Pole
Wallbox Style 0-10V Control with Power Switch Wiring Example
Black
DIMMING
To Fluorescent Lamps
Black
White
Violet (+)
BALLAST
Gray (-)
Black White
Violet (+)
Gray (-)
For 2-wire Powerline wiring, individually insulate (cap-off)
all unused Violet & Gray leads as shown.
DIMMING BALLAST
CAUTION:
0-10V
To Fluorescent Lamps
To Fluorescent Lamps
To Additional Ballasts
Black White
Violet (+)
Gray (-)
DIMMING BALLAST
To Fluorescent Lamps
Examples: Leviton IPX series operate as single pole or 3-way models. Available in 120V and 277V models. Leviton 6668-1W (white) 120V single pole fluorescent dimmer.
To Additional Ballasts
WI R I NG & C ONTR O L S
PO W E RSEN S E
Examples: Lithonia model ISD BC or Leviton IP 710 Series (These 0-10V dc, 120/277V models can be wired for single pole application (shown); these models can also be wired for 3-way applications.)
OSRAM SYLVANIA National Customer Service and Sales Center 1-800-LIGHTBULB (1-800-544-4828) www.sylvania.com
Specifications subject to change without notice.
0-10V DC Control with POWERSENSE Ballasts
120 or 277V Black (Hot)
LINE
Neutral (White)
0-10Vdc
Wallbox Control with Line Voltage
Switch
Black
Line
Voltage
Switch
0-10V
Control
Black White
DIMMING
Violet (+)
BALLAST
Gray (-)
Class 1 or Class 2 circuit
Black
Violet
Gray
Photo Sensor 0-10V Wiring Example
Ballast Output Max. Item OSRAM SYLVANIA Control Voltage Input Lamp Number Description Type Method (VDC) Current (mA) Type
45030 ELSC-DLH-TVLAMP/BUS Daylight Harvesting
To Fluorescent Lamps
On/Off
Switch (120/277V)
Slide Dimmer
0-10V
Black White
DIMMING
Violet (+)
BALLAST
Gray (-)
ELOGIC DAYLIGHT SENSOR ORDERING INFORMATION
Sensor & Control for
To Fluorescent Lamps
Analog 0-10V 6 T8 or T5 or T5HO
To Additional Ballasts
SPECIFICATION DATA
Black White
Violet (+) Grey (-)
Red Red
Blue Blue
LAMP 1
ELECTRONIC
BALLAST
Catalog # Date Type
Project Prepared by
Comments
T8 POWERSENSE
High Efficiency
®
High Efficiency, T8 Controllable Lighting Systems, UNV (120-277V)
Input Rated Ballast Input System Item OSRAM SYLVANIA Current Lamp Lumens No. of Factor System Mean Power (W) Efficacy Number Description (AMPS) Type (lm) Lamps (BF) Lumens Lumens 120V 277V (lm/W) BEF
50705 QTP 1x32T8/UNV DIM-TC 0.27/0.12 FO32XP 3000 1 0.88 2640 2480 30 30 88 2.93
0.05 150 140 8 8
0.24/0.11 FO30/SS 2850 1 0.88 2510 2360 28 28 90 3.14
0.05 145 135 8 8
0.22/0.10 FO28/SS 2725 1 0.88 2400 2255 25 25 96 3.52
0.05 135 130 8 8
0.20/0.09 FO25/SS 2475 1 0.88 2180 2045 23 23 95 3.83
0.05 125 115 7 7
T 8 D I M
50707 QTP 2x32T8/UNV DIM-TC 0.51/0.24 FO32XP 3000 2 0.88 5280 4965 59 57 93 1.54
0.05 300 280 14 14
P O W E R S E N S E
0.48/0.20 FO30/SS 2850 2 0.88 5015 4715 55 53 95 1.66
0.05 285 270 14 14
0.43/0.18 FO28/SS 2725 2 0.88 4795 4510 51 49 98 1.80
0.05 275 255 13 13
0.39/0.16 FO25/SS 2475 2 0.88 4355 4095 45 44 99 2.00
0.05 250 235 13 13
50714 QTP 3x32T8/UNV DIM-TCL 0.73/0.30 FO32XP 3000 3 0.88 7920 7445 87 84 94 1.05
0.05 450 425 20 20
0.68/0.30 FO30/SS 2850 3 0.88 7525 7075 81 78 96 1.13
0.05 430 400 20 20
0.62/0.26 FO28/SS 2725 3 0.88 7195 6760 73 72 100 1.22
0.05 410 385 19 19
0.56/0.24 FO25/SS 2475 3 0.88 6535 6140 67 66 99 1.33
0.05 370 350 19 19
50716 QTP 4x32T8/UNV DIM-TCL 0.96/0.40 FO32XP 3000 4 0.88 10,560 9925 114 110 96 0.80
0.05 600 565 27 27
0.92/0.39 FO30/SS 2850 4 0.88 10,030 9430 107 104 96 0.85
0.05 570 535 26 26
0.82/0.35 FO28/SS 2725 4 0.88 9590 9015 98 95 101 0.93
0.05 545 510 25 25
0.74/0.32 FO25/SS 2475 4 0.88 8710 8190 91 89 98 0.99
0.05 495 465 24 24
Products are all 10-pack. *Striation might occur with SUPERSAVER lamps. 1: System Efficacy calculation based on lowest input power value. 2: Ballast Efficiency Factor (BEF) shown = (Ballast Factor x 100) divided by Input Power (Note: calculation based on lowest wattage value).
Wiring Diagrams
Output Wiring: Lamp wiring for dimming ballasts can differ significantly from non-dimming ballasts and from
other manufacturers dimming ballasts. Take care to connect lamp lead wires as shown on the applicable ballast diagram. Lamp Seasoning: For optimal performance, fluorescent lamps may require seasoning for up to 12 hours prior to low temperature starting & low level dimming. Refer to NEMA LSD 23-2002 Lighting Systems Division: Recommended Practice — Lamp Seasoning for Fluorescent Dimming Systems
1 lamp
Black White
Violet (+) Grey (-)
ELECTRONIC
BALLAST
LAMP 1
3 lamp
Black
White
ELECTRONIC
Violet (+)
Grey (-)
BALLAST
Item Number 50707 QTP 2 x 32T8 / UNV DIM-TC
Red
Red/White Red/Black
Red/White
Yellow Yel/Blk
Yellow
Blue
Red Red
Blue Blue
LAMP 1
LAMP 2
LAMP 3
QUICKTRONIC
Number of Lamps (1, 2, 3, 4)
SYLVANIA, the system solution, QUICK60+, POWERSENSE, See the World in a New Light, PROStart, OCTRON and SUPERSAVER are registered trademarks of OSRAM SYLVANIA Inc. ELOGIC is a trademark of OSRAM SYLVANIA Inc. QUICKTRONIC is a registered trademark of OSRAM GmbH. NEMA Premium is a registered trademark of National Electrical Manufacturers Association.
2 lamp
4 lamp
Black
White
Violet (+) Grey (-)
Black White
Violet (+) Grey (-)
ELECTRONIC
BALLAST
Red Red
Red
Red/White Red/Black
Red/White
Yellow Yellow/Black
Yellow
Blue/White Blue/Black
Blue/White
Blue
Blue
Blue Yel/Blk Yellow Yellow
LAMP 1
LAMP 2
LAMP 3
LAMP 4
ELECTRONIC
BALLAST
LAMP 1
LAMP 1
LAMP 2
System Type - DIMMING/Case Size
Line Voltage (120-277V)
Primary Lamp Wattage
1
Performance Guide
Data based on SYLVANIA OCTRON® lamps shown. QUICKTRONIC® POWERSENSE ballasts are also compatible with other
2
manufacturers equivalent lamp types that meet ANSI specifications, including F17, F25, F32, U-Bend equivalent lamps and SUPERSAVER lamps.
Specifications
Data based on F32T8
Starting Method: Programmed Rapid Start Circuit Type: Series Lamp Frequency: >40 kHz Lamp CCF: Less than 1.7 Starting Temp: 50°F/10°C minimum
for OCTRON T8 lamps
Input Voltage: 120-277V, ±10% Input Frequency: 50/60 Hz THD: <10% @ Full Output Power Factor: >98% @ Full Output
UL Listed Class P, Type 1 Outdoor CSA or C/UL Certified 70°C Max Case Temperature FCC 47CFR Part 18 Non-Consumer Class A Sound Rating RoHS compliant
3
ANSI C62.41 Cat. A Transient Protection Remote mounting (Max. wire length from ballast case to lampholder)
• up to 8ft for full wattage T8s
• no remote mounting for SUPERSAVER
3 Complies with European Union Restriction
of Hazardous Substances Directive (Directive EC 2002/95)
Control Information
QUICKTRONIC POWERSENSE ballasts are compatible with a wide range of low voltage (0-10VDC) and power line fluorescent controllers available from various manufacturers. Low Voltage Control Specs: Ballast will source up to 0.5mA for 0-10VDC control purposes. May be wired as a Class 1 or Class 2 circuit­consult Local and National Electrical Codes. Power Line Control Specs: Specification­grade fluorescent controls are available for 120V or 277V operation of controllable analog electronic fluorescent ballasts. Controls must be suitably rated for both the type (e.g. Fluorescent Phasecontrol) and size (e.g. 600W) of the connected load.
System Life / Warranty
QUICKTRONIC products are covered by the QUICK 60+® warranty, a comprehensive lamp and ballast system warranty. For additional details, refer to the QUICK 60+ warranty bulletin.
OSRAM SYLVANIA National Customer Service and Sales Center
1-800-LIGHTBULB (1-800-544-4828) www.sylvania.com
Specifications subject to change without notice.
©20 11 O SRAM SYLVA NIA
Loading...