Sylvania QTP T8 8 FT DATASHEET

www.sylvania.com
QUICKTRONIC®T8 8' Instant Start Universal Voltage
Professional Series
Lamp/Ballast Guide
59W T8 8-Foot - OCTRON
2-lamp QTP2x59T8 UNV ISN SC
Primary Lamp Type:
FO96T8 (59W Lamp)
Also operates:
FO96T8/SS (55W Lamp) FO72T8 FO48T8
®
Key System Features
• Over 30% Energy savings
QTP T8 8 FT
• Provides 50% longer lamp life than standard magnetic T12 slimline lamps
• 88% Ballast factor
• Min. Starting Temp:
• 0°F (-18°C) for T8 lamps
• 60°F (16°C) for Energy Saving
T8 lamps
• Universal voltage (120-277V)
• <10% THD
• Virtually eliminates lamp flicker
Application Information
SYLVANIA QUICKTRONIC 59 ISN
is ideally suited for:
• Commercial
• Retail
• New construction
• Industrial
• Schools
• Retrofit
SYLVANIA QUICKTRONIC SYSTEM 59 ISN UNV electronic T8 ballasts offer several
advantages:
1. Operate OCTRON T8 lamps with maximum efficacy and high lumen output
• Over 30% energy savings when compared to F96T12 magnetically ballasted systems
2. Longer Lamp Life: provides 50% longer lamp life compared to standard magetic T12 slimline systems
3. Parallel Circuitry: keeps remaining lamp lit if one goes out
4. Small Can Enclosure for:
• low profile fixture design
• transportation, inventory and ergonomic benefits
5. New Banded Packaging
• Distributor-friendly for easy stocking and individual ballast sales
• Reduced waste
• Easy removable bands
• No tangled wires
System Information
SYLVANIA QUICKTRONIC SYSTEM 59 ISN UNV advantages:
• Operate from 120V through 277V
• Eliminates “wrong voltage” errors
• Reduces inventory by 50%
• Utilizes Instant Start operation for
• Highest System Efficacy
• Low temperature starting capability
• Very low harmonic distortion (<10%)THD
• Operate at >40kHz to reduce potential interference with infrared control systems
A complete OSRAM SYLVANIA System Performance Guide showing perfor­mance characteristics for all combina­tions of lamps and ballasts is available upon request.
Normal Ballast Factor
Setting the standard for quality, SYSTEM 59 ISN UNV is also covered by our QUICK
®
60+
warranty, the first and most compre­hensive lamp & ballast system warranty in the industry.
70%
150%
Relative
35% Energy Savings
94%
65%
QTP2x59-ISN
2-FO96T8/XP/SS
150%
Input Initial System Mean Mean Lamp
System Type (W) Lumens (LPW) Lumens Output Savings (%*)
Magnetic Ballast 2-F96T12 160 11,345 71 9985 100% 0% Baseline
Magnetic Ballast 2-F96T12/SS 125 9330 75 8210 82% 22% 100%
*3 hours/start
160%
140%
120%
100% 100% 100%
100%
80%
60%
40%
20%
0%
Magnetic Ballast
Power System Efficacy System Light Energy Life
% Relative Mean Light Output % System Wattage (Power) % Lamp Life
2-F96T12
22% Energy Savings
82%
78%
Magnetic Ballast
2-F96T12/SS
100%
30% Energy Savings
101%
QTP2x59-ISN 2-FO96T8/XP
42
SPECIFICATION DATA
Note: For one lamp application, cap any unused blue lead. Insulate to 600 volts.
QUICKTRONIC 2x59
BALLAST
Black White
Blue
Blue
Red
LAMP
LAMP
Catalog # Date Type
Project Prepared by
Comments
Normal Ballast Factor
59 T8 INSTANT START
Professional Series
Electronic T8 8-foot Fluorescent Systems Universal Voltage (120-277V)
Item OSRAM SYLVANIA Current Lamp Lumens No. of Factor System Mean Power Efficacy Number Description (AMPS) Type (lm) Lamps (BF) Lumens Lumens (W) (lm/W) BEF
QTP 2x59T8/UNV ISN-SC 0.93/0.40 FO96T8/700 (59W) 5700 2 0.88 10,030 9030 112/110 90/91 0.80
49590
Banded Pack
49598 10-Pack
49599 Pallet Pack
Banded Pack, (add “-B” to Description). Banded Pack and 10-Pack contain 10 pieces each. Pallet Pack contains 840 pieces, (add “-PAL” to Description). 1: Ballast Efficiency Factor (BEF) shown = (Ballast Factor X 100) divided by Input Power (Note: calculation based on lowest wattage value).
Input Rated Ballast Input System
0.93/0.40 FO96T8/XP (59W) 6100 2 0.88 10,735 10,090 112/110 96/98 0.80
0.85/0.36 FO96T8/XP/SS (55W) 5700 2 0.88 10,030 9430 104/102 96/98 0.86
0.70/0.31 FO72T8/XP 4650 2 0.89 8275 7780 86/85 96/97 1.05
0.47/0.21 FO48T8/XP 2850 2 0.89 5075 4770 58 88 1.53
0.56/0.25 FO96T8/XP (59W) 6100 1 1.02 6220 5850 67 93 1.52
0.51/0.22 FO96T8/XP/SS (55W) 5700 1 1.02 5815 5465 62 94 1.65
0.43/0.20 FO72T8/XP 4650 1 1.02 4745 4460 51 93 2.00
0.30/0.14 FO48T8/XP 2850 1 1.03 2935 2760 36 82 2.86
Performance Guide
Data based upon SYLVANIA OCTRON lamps shown. QUICKTRONIC®59 ISN­SC is also compatible with other lamp
1
manufacturers equivalent lamp types that meet ANSI specifications.
Complete performance data is available in the QUICKSYSTEMS section of the SYLVANIA Electronic Ballast Catalog.
Specifications
Data based on FO96T8
Starting Method: Instant Start Ballast Factor: 0.88 Circuit Type: Parallel Lamp Frequency: >40kHz Lamp CCF: Less than 1.7 Starting Temp:
0°F (-18°C) for OCTRON®96T8 lamps 60°F (16°C) for SUPERSAVER
Input Frequency: 50/60Hz Low THD: <10% Power Factor: >98% Voltage Range: ±10% of 120-277V
2
rated line (108-305V)
®
®
QTP T8 8 FT
lamps
Dimensions “SC” Small Enclosure:
Overall: 9.5" L x 1.68" W x 1.18" H Mounting: 8.90"
Product Weight:
1.6 lbs ea. (approx.)
Wiring:
Leads only,
Height
8.70 mm Slot
Width
no connectors provided
Item Number 49598 QTP 2 x 59T8 / UNV ISN SC
QUICKTRONIC PROFESSIONAL
Number of Lamps
Primary Lamp Type (59W FO96T8)
Specifications subject to change without notice.
Mounting
Length
Length
Case Size
Starting/Ballast Factor
Line Voltage (120-277V)
UL Listed Class P, Type 1 Outdoor CSA Certified 70°C Max Case Temperature FCC 47CFR Part 18 Non-Consumer Class A Sound Rating ANSI C62.41 Cat A. Transient Protection GFCI compatible Emergency ballast compatible Remote Mounting (Max. wire length from ballast case to lampholder):
• 20 ft: full wattage T8s
• 10 ft: energy saving T8s
2 Operation below 50ºF (10°C) may affect
light output or lamp operation – see “Low Temp. Starting” definition.
System Life / Warranty
QUICKTRONIC products are covered by our QUICK 60+ comprehensive lamp and ballast system warranty. For additional details, refer to our QUICK 60+ warranty bulletin.
OSRAM SYLVANIA National Customer Service and Sales Center
1-800-LIGHTBULB (1-800-544-4828) www.sylvania.com
®
warranty, a
43