Sylvania QHE DL40-28WSS ISN DATASHEET

www.sylvania.com
QUICKTRONIC®Instant Start DL40 Universal Voltage
High Efficiency Series
Lamp / Ballast Guide
40W T5 - DULUX®L
1 lamp QHE 1x40DL/UNV ISN-SC 2 lamp QHE 2x40DL/UNV ISN-SC 3-lamp QHE 3x 40DL/UNV ISN-SC
Primary Lamp Type:
FT40DL
Also operates:
FT40DL/28W/SS
QHE DL40/28WSS ISN
Key System Features
High Efficiency Systems over 90% efficient
• Universal voltage (120-277V)
• QUICKSENSE®ballast technology (end-of-lamp-life sensing)
• Min. Starting Temp:
• 0°F (-18°C) for FT40DL and
FT40DL/SS
• High luminous efficacy
• Virtually eliminates lamp flicker
• Quiet operation
• High power factor
• Low harmonic distortion
• Lightweight
• UL, CSA
• Auto Reset
Application Information
SYLVANIA QUICKTRONIC DL40
is ideally suited for:
• Commercial
• Retail
• Hospitality
• Institutional
• Schools
• New construction
• Direct lighting
• Indirect lighting
• Surface mount
• Cove lighting
SYLVANIA QUICKTRONIC High Efficiency (QHE) energy-saving electronic DULUX L
40W ballasts save up to 6 to 9% over standard electronic ballasts without compromising light output or lamp life. The added energy savings also provides for a quicker payback.
SYSTEM DL40 is available in a one lamp, two lamp and a three lamp model. All are Universal Voltage (120-277V) models.
SYSTEM DL40 provides over 30% more lumen output than 34T12 systems at nearly the same power input. Also, the small lamp diameter and sleek profile provide new design options and improved fixture optics.
SYSTEM DL40 ballasts contain QUICK­SENSE ballast technology, a patented circuitry designed to shut down the system reliably and safely when the lamps have reached their end-of-life.
System Information
SYSTEM DL40 uses instant start operation to provide the highest system efficacy and to assure low temperature starting capability. Instant start also provides for maximum remote wiring distances.
QUICKSENSE ballast technology helps to protect against overheated bases and sockets, as well as cracking of the glass wall, and uses dynamic end-of-lamp-life sensing to avoid false shutdowns caused by some static sensing methods. QUICK­SENSE ballast technology will auto reset when the lamps are replaced with new ones.
A complete OSRAM SYLVANIA System Performance Guide showing performance characteristics for all combinations of lamps and ballasts is available upon request.
SYLVANIA QUICKTRONIC High Efficiency (QHE) ballasts operate on input voltage from 120V through 277V, eliminating “wrong voltage” wiring errors and reducing the number of models in inventory by half.
<10% THD Electronic TT5
Fluorescent Ballast Systems
Setting the standard for quality, SYSTEM DL40 is also covered by our QUICK 60+ warranty, the first and most compre­hensive system warranty in the industry.
System Type Input Initial System (2 x 2) Power System Efficacy 2-Lamps (W) Lumens LPW
FB40T12 - Std. Magnetic Ballast 96 5795 60
FB34T12 - E.S. Magnetic Ballast 72 4575 66
FBO32T8 - Magnetic 71 5415 76
DL40 - QHE2x40DL/UNV ISN-SC 68/67 5670 83/84
DL40/28W/SS - QHE2x40DL/UNV ISN-SC 64/63 5990 94/95
System Type Input Initial System (2 x 2) Power System Efficacy 3-Lamps (W) Lumens LPW
DL40- Std. Electronic ISN Ballast (0.96 BF) 110 9070 82
DL40 - QHE3x 40DL/UNV ISN-SC 100/99 8505 85/86 DL40/28W/SS - QHE3x 40DL/UNV ISN-SC 95/94 8990 95/96
E.S. Magnetic Ballast 86 5795 67
Saves 14% … 15W with the new 3-Lamp QHE DL40/28W/IS SUPERSAVER System!
®
SAME LIGHT, LESS POWER
72
SPECIFICATION DATA
QUICKTRONIC 3x40DL
BALLAST
Black White
Blue
Blue
Blue
Red
Note: For two lamp application, cap any blue lead. Insulate to 600 volts.
BALLAST
Note: For one lamp application, cap any blue lead. Insulate to 600 volts.
QUICKTRONIC 2x40DL
Black
White
Blue Blue
Red
BALLAST
Black White
Blue
Red
Catalog # Date Type
Project Prepared by
Comments
DL40 INSTANT START
High Efficiency
High Efficiency Universal Voltage (120-277V)
Input Rated Ballast Mean Input System Item Current Lamp Number Description (AMPS) Type (lm) Lamps (BF) Lumens Lumens (W) (lm/W) BEF
49428 QHE 1x40DL/UNV ISN-SC 0.30/0.13 FT40T5 3150 1 0.90 2835 2440 35 81 2.57
49429 QHE 2x40DL/UNV ISN-SC 0.56/0.26 FT40T5 3150 2 0.90 5670 4875 68/67 83/84 1.34
49416 Pallet Pack
49430 QHE 3x40DL/UNV ISN-SC 0.84/0.36 FT40T5 3150 3 0.90 8505 7315 100/99 85/86 0.91
49417 Pallet Pack
Pallet Pack contains 500 pieces, (add “-PAL” to Description).
1: Ballast factor based upon 225mA nominal lamp current for FT40DL lamp and 190mA nominal lamp current for FT40DL/28W/SS lamp.
2: Ballast Efficiency Factor (BEF) shown = (Ballast Factor x 100) divided by Input Wattage (Note: calculation based on lowest input wattage).
0.27/0.12 FT40DL/28W/SS 2800 1 1.07 2995 2575 32 94 3.34
0.54/0.24 FT40DL/28W/SS 2800 2 1.07 5990 5150 64/63 94/95 1.70
0.79/0.35 FT40DL/28W/SS 2800 3 1.07 8990 7730 95/94 95/96 1.14
1
Lumens No. of Factor System System Wattage Efficacy
QUICKTRONIC®1x40DL/UNV ISN-SC
Performance Guide
Data based upon SYLVANIA DL40 lamps shown. QUICKTRONIC is also compatible with other lamp
2
manufacturers equivalent lamp types that meet ANSI specifications.
Specifications
Data based on FT40T5
Starting Method: Instant Start Ballast Factor: 0.90 Circuit Type: Parallel Lamp Frequency: >40kHz Lamp CCF: Less than 1.7 Starting Temp:30°F (-18°C) for FT40DL
and for FT40DL/SS
Input Frequency: 60 Hz Low THD: <10% Power Factor: >98% Voltage Range: ±10% of 120-277V
rated line (108-305V)
®
DL40
NEW!
QHE DL40/28WSS ISN
QUICKTRONIC®QHE 2x40DL/UNV ISN-SC
Dimensions:
Overall: 9.5" L x 1.68" W x 1.18" H Mounting: 8.90"
Packaging:
Quantity: 10 pieces Pallet Pack: 500 pieces Weight: 1.6 lbs each (approx)
Wiring:
Leads only (no connectors provided)
Item Number 49430 QHE 3 x 40DL / UNV ISN SC
QUICKTRONIC High Efficiency
Number of Lamps
Specifications subject to change without notice.
Height
8.70 mm Slot
Width
QUICKTRONIC®QHE 3x40DL/UNV ISN-SC
Mounting
Length
Length
Case Size
Starting/Ballast Factor
Line Voltage (120-277V)
Primary Lamp Wattage
UL Listed Class P, Type 1 Outdoor CSA Certified 70°C Max Case Temperature FCC 47CFR Part 18 Non-Consumer Class A Sound Rating ANSI C62.41 Cat. A Transient Protection Remote Mounting (Max. wire length from ballast case to lampholder): up to 18 feet
3 Operation below 50°F (10°C) may affect
light output or lamp operation – see “Low Temp. Starting” definition.
System Life / Warranty
QUICKTRONIC products are covered by our QUICK 60+ comprehensive lamp and ballast system warranty. For additional details, refer to our QUICK 60+ warranty bulletin.
OSRAM SYLVANIA National Customer Service and Sales Center
1-800-LIGHTBULB (1-800-544-4828) www.sylvania.com
®
warranty, a
73