www.sylvania.com
Note: For one lamp application, cap any unused blue lead. Insulate to 600 volts.
QUICKTRONIC 2x59
BALLAST
Black
White
Blue
Blue
Red
LAMP
LAMP
QUICKTRONIC®T8 Instant Start
347 Volt – Canada
Standard &
Professional Series
Normal, Low & High Ballast Factor
Lamp / Ballast Guide
32W T8 - OCTRON
1-lamp QTP1x32T8/347 ISN-SC
2-lamp QTP2x32T8/347 ISN-SC
3-lamp QTP3x32T8/347 ISN-SC
4-lamp QTP4x32T8/347 ISN-SC
2-lamp QT2x32T8/347 ISL-SC
4-lamp QT4x32T8/347 ISL-SC
Primary Lamp Types:
FO32, FBO32 & FBO31
Also operates:
FO17, FO25, FO40, FBO16, FBO24 &
SUPERSAVER®Equivalents (SS)
FO40T8 operations:
1 lamp on 2L ballast
2 lamps on 3L ballast
3 lamps on 4L ballast
Note: FO40T8 0°F (-18°C) Starting Temp.
2-lamp QT2x32T8/347 ISH-SC
Only operates lamp types FO32,
FO30/SS, FO28/SS, FO25/SS, FBO32,
FB031, FBO30/SS, FBO29/SS
59W T8 8-Foot OCTRON
2 lamp QT2x59/347 IS
Primary Lamp Types
FO96 T8 (59W lamp)
Also operates:
FO96T8/SS lamp (55W)
®
Key System Features
CANADA T8 347V
• 30-40% energy savings
• -20°F (-29°C) min. starting temp. for
QTP ballast operating OCTRON lamps
(See Starting Temp. details in
Specification section)
• Virtually eliminates lamp flicker
• CSA approved
Application Information
SYLVANIA QUICKTRONIC
Systems are ideally suited for:
• Commercial, retail, hospitality
• Institutional
• Schools
• New construction
• Retrofit
48
SYLVANIA QUICKTRONIC 32IS-SC
operates OCTRON T8 lamps with
maximum efficacy and provides 30-40%
energy savings when compared to
F40T12 magnetic systems.
SYLVANIA QUICKTRONIC 59ISN operates
OCTRON FO96 T8 lamps with maximum
efficacy and provides 30% energy
savings when compared to F96T12
magnetic systems.
System Information
New small can enclosure on select
models allows for low profile fixture
design and application. Small can size
also provides transportation, inventory
and ergonomic benefits. Parallel circuitry
is utilized to keep the remaining lamps
lit if one or more should go out.
Setting the standard for quality these
systems are covered by our QUICK 60+
warranty, the first and most comprehensive lamp & ballast system warranty
in the industry.
Wiring Diagram 2x59:
2-Lamp Systems Power System System System Light Energy
Lamp & Ballast Type (W) Lumens LPW Lumens Output Savings
2-F34T12CW
E.S. Magnetic Ballast
2-FO32/800/XP
QTP2x32 ISN-SC
2-FO28/SS
QTP2x32 ISN-SC
2-FO32/800/XP
QT2x32 ISL-SC
®
2-FO28/SS
QT2x32 ISL-SC
4-Lamp Systems Power System System System Light Energy
Lamp & Ballast Type (W) Lumens LPW Lumens Output Savings
4-F34T12CW
2-E.S. Mag Ballasts
4-FO32/800/XP
QTP4x32T8 ISN-SC
4-FO28/SS
QTP4x32 ISN-SC
4-FO32/800/XP
QT4x32T8 ISL-SC
4-FO28/SS
QT4x32 ISL-SC
2-Lamp Systems Power System System System Light Energy
Lamp & Ballast Type (W) Lumens LPW Lumens Output Savings
2-F96T12
Mag. Ballast
F96T12/SS
Mag. Ballast
FO96T8/XP
QT2x59 IS
FO96T8/XP/SS
QT2x59 IS
Input Initial Mean Mean %
72 4665 65 3965 100% 0%
59 5280 89 4965 125% 18%
52 4795 92 4510 114% 28%
51 4620 91 4345 110% 29%
45 4195 93 3945 99% 38%
Input Initial Mean Mean %
144 9330 65 7930 100% 0%
112 10,560 94 9925 125% 22%
99 9590 97 9015 114% 31%
98 9240 94 8685 110% 32%
86 8395 98 7890 99% 40%
Input Initial Mean Mean %
160 11,345 71 9985 100% 0%
125 9330 75 8210 82% 22%
110 10,735 98 10,090 101% 31%
103 10,030 97 9430 94% 36%
Relative
Relative
Relative
SPECIFICATION DATA
BALLAST
LAMP
Black/White
White
Blue
Red
QUICKTRONIC 1x32
LAMP
LAMP
Blue
Blue
Red
BALLAST
Black
White
Note: For one lamp application, cap any blue lead. Insulate to 600 volts.
QUICKTRONIC 2x32
LAMP
LAMP
LAMP
BALLAST
Blue
Blue
Blue
Red
Black
White
Note: For two lamp application, cap any blue lead. Insulate to 600 volts.
QUICKTRONIC 3x32
BALLAST
LAMP
LAMP
LAMP
LAMP
Black
White
Yellow
Yellow
Blue
Blue
Red
Red
Note: For three lamp application, cap any unused blue lead. Insulate to 600 volts.
QUICKTRONIC 4x32
Catalog # Date Type
Project Prepared by
Comments
Normal, Low, High BF
T8 Instant Start 347V
Standard & Professional
Electronic T8 Fluorescent Systems 347V
Item OSRAM SYLVANIA Current Lamp Lumens No. of Factor System Mean Power Efficacy
Number Description (AMPS) Type (lm) Lamps (BF) Lumens Lumens (W) (lm/W) BEF
QUICKTRONIC®Low Ballast Factor (0.77) <20% THD
49241 QT2x32T8/347 ISL-SC 0.15 FO32/XP 3000 2 0.77 4620 4345 51 91 1.51
49939 QT4x32T8/347 ISL-SC 0.28 FO32/XP 3000 4 0.77 9240 8685 98 94 0.79
QUICKTRONIC®PROFESSIONAL Normal Ballast Factor (0.88) <10% THD
49711 QTP1x32T8/347 ISN-SC 0.089 FO32/XP 3000 1 0.88 2640 2480 31 90 2.84
49713 QTP2x32T8/347 ISN-SC 0.165 FO32/XP 3000 2 0.88 5280 4965 59 89 1.49
49715
❂ QTP3x32T8/347 ISN-SC
49716 ❂Pallet Pack
49717 ❂ QTP4x32T8/347 ISN-SC
49718 ❂Pallet Pack
QUICKTRONIC®High Ballast Factor (1.20) <20% THD
49927 QT2x32T8/347 ISH-SC20.23 FO32/XP 3000 2 1.2 7200 6770 78 92 1.54
QUICKTRONIC 59T8 (8 Foot) Normal Ballast Factor (0.88) <20% THD
49217 QT2x59/347 IS 0.33 FO96T8 XP(59W) 6100 2 0.88 10,735 10,090 110 98 0.80
Products above are 10-pack unless noted. Pallet Pack contains 840 pieces, (add “-PAL” to Description).
1: Ballast Efficiency Factor (BEF) shown = (Ballast Factor x 100) divided by Input Power.
2: QT2x32T8/347 ISH-SC model only operates 2 lamps (no 1-lamp operation).
49715 QTP3x32T8/347 ISN-SC replaces 49993 QT3x32T8/347 ISN-SC and 49717 QTP4x32T8/347 ISN-SC replaces 49994 QT4x32T8/347 ISN-SC
Input Rated Ballast Input System
0.25 FO32/XP 3000 3 0.88 7920 7445 86 92 1.02
0.33 FO32/XP 3000 4 0.88 10,560 9925 112 94 0.78
❂
New Product.
Performance Guide
Data shown based upon SYLVANIA
®
FO32/XP®& FO96 T8 XP
1
OCTRON
Lamp(s).
QUICKTRONIC®ballasts are also
compatible with other lamp manufacturers’ equivalent lamp types that
meet ANSI specifications.
Specifications
Starting Method: Instant Start
Ballast Factor: 0.77, 0.88 & 1.20
Circuit Type: Parallel
Lamp Frequency:
All SC models >40kHz
Standard enclosure >20kHz
Lamp CCF: Less than 1.7
Starting Temp:
QTP models: -20°F (-29°C) for
QT models: 0°F (-18°C) for
60°F (16°C) for SUPERSAVER
0°F (-18°C) for FO40T8
Input Frequency: 60 Hz
THD: QTP <10%, QT <20%
Power Factor: >97%
Voltage Range: ±10% of Rated Input
UL Listed Class P, Type 1 Outdoor
CSA Certified
70°C Max Case Temperature
FCC 47 CFR Part 18 Non-Consumer
Class A Sound Rating
ANSI 62.41 Cat. A Transient Protection
GFCI compatible
Emergency ballast compatible
Remote Mounting (Max. wire length
from ballast case to lampholder):
• 20 ft: full wattage T8s
• 10 ft: energy saving T8s
• 4 ft: 25W energy saving T8s
3 Operation below 50°F (10°C) may affect
light output or lamp operation – see
“Low Temp. Starting” definition.
3
OCTRON T8 lamps
OCTRON T8 lamps
®
T8 lamps
NEW!
CANADA T8 347V
Dimensions Standard Enclosure: Dimensions “SC” Small Enclosure:
Overall: 9.5" L x 2.38" W x 1.6" H Overall: 9.5" L x 1.68" W x 1.18" H
Mounting: 8.90" Mounting: 8.90"
Product Weight:
2.8 lbs ea. (approx.)
Height
Wiring: Product Weight:
Leads only, 1.6 lbs ea. (approx.)
no connectors provided
Specifications subject to change without notice.
Item Number 49713 QTP 2 x 32T8 / 347 ISN - SC
QUICKTRONIC Professional
Number of Lamps (1, 2, 3, 4)
Width
Mounting
Length
Length
Height
8.70 mm
Slot
Width
Case Size
Starting/Ballast Factor
Line Voltage
Primary Lamp Wattage
Mounting
Length
Length
System Life / Warranty
QUICKTRONIC products are covered
by our QUICK 60+
comprehensive lamp and ballast
system warranty. For additional
details, refer to our QUICK 60+
warranty bulletin.
OSRAM SYLVANIA
National Customer
Service and Sales Center
1-800-LIGHTBULB
(1-800-544-4828)
www.sylvania.com
®
warranty, a
49