Sy-G SA1P1LVW, SA1P2HVW, SA1P3LVW, SA1P3HVW, SA1P1HVW User Manual

...
USER MANUAL
Online UPS Challenger Series
Stand Alone (SA) Rack Mount (RM)
Low Voltage & High Voltage
Models: SA1P1LVW/SA1P1HVW
SA1P2LVW/SA1P2HVW SA1P3LVW/SA1P3HVW
Capacity: 1 KVA - 2 KVA - 3 KVA
REVISION
DESCRIPTION
Date
Rev. 1.0
Formal Release
2015/11/25
Danger-For your safety
Indicate an imminently hazardous situation that, if not avoided, will result in death or serious injury.
Warning-Caution
Indicate that any unsafe practices must be avoided which could prejudice health and safety and cause financial damage.
Important
Indicate any important technical information that must not be neglected.
Contents
1. IMPORTANT SAFETY WARNING .................................................................... 1
1.1. Transportation .......................................................................................... 1
1.2. Preparation ................................................................................................ 1
1.3. Installation ................................................................................................. 1
1.4. Operation ................................................................................................... 2
1.5. Maintenance, service and faults ........................................................ 2
2. INSTALLATION AND SETUP ............................................................................ 4
2.1. Rear Panel View. ........................................................................................ 4
2.2. Setup the UPS ............................................................................................ 5
3. OPERATIONS .................................................................................................... 13
3.1. Button Operation ..................................................................................... 9
3.2. LCD Panel .................................................................................................. 10
3.3. Audible Alarm .......................................................................................... 11
3.4. LCD display wordings index ............................................................... 12
3.5. UPS Setting ............................................................................................... 12
3.6. Operating Mode Description ............................................................. 18
3.7. Faults Reference Code .......................................................................... 19
3.8. Warning indicator .................................................................................. 19
4. TROUBLE SHOOTING ..................................................................................... 21
5. STORAGE AND MAINTENANCE ................................................................... 21
6. TECHNICAL SPECIFICATIONS ....................................................................... 22
1
1. Important Safety Warning
Please comply with all warnings and operating instructions in this manual strictly. Save this
manual properly and read carefully the following instructions before installing the unit. Do not
operate this unit before reading through all safety information and operating instructions carefully.
1.1. Transportation
Please transport the UPS system only in the original package to protect against shock and
impact.
1.2. Preparation
o Condensation may occur if the UPS system is moved directly from cold to warm
environment.
The UPS system must be absolutely dry before being installed.
PLEASE ALLOW AT LEAST TWO HOURS FOR THE UPS SYSTEM TO ACCLIMATE THE
ENVIRONMENT.
o Do not install the UPS system near water or in moist environments. o Do not install the UPS system where it would be exposed to direct sunlight or near
heater.
o Do not block ventilation holes in the UPS housing.
1.3. Installation
o Do not connect appliances or devices which would overload the UPS system (e.g.
laser printers) to the UPS output sockets.
o Place cables in such a way that no one can step on or trip over them. o Do not connect domestic appliances such as hair dryers to UPS output sockets. o The UPS can be operated by any individuals with no previous experience. o Connect the UPS system only to an earthed shockproof outlet which must be easily
accessible and close to the UPS system.
o Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your
computer) to connect the UPS system to the building wiring outlet (shockproof
2
outlet).
o Please use only VDE-tested, CE-marked power cables to connect the loads to the
UPS system.
o When installing the equipment, it should ensure that the sum of the leakage current
of the UPS and the connected devices does not exceed 3.5mA.
1.4. Operation
o Do not disconnect the mains cable on the UPS system or the building wiring outlet
(shockproof socket outlet) during operations since this would cancel the protective
earthing of the UPS system and of all connected loads.
o The UPS system features its own, internal current source (batteries). The UPS output
sockets or output terminals block may be electrically live even if the UPS system is
not connected to the building wiring outlet.
o In order to fully disconnect the UPS system, first press the OFF/Enter button to
disconnect the mains.
o Prevent no fluids or other foreign objects from inside of the UPS system.
1.5. Maintenance, service and faults
THE UPS SYSTEM OPERATES WITH HAZARDOUS VOLTAGES. REPAIRS MAY BE CARRIED
OUT ONLY BY QUALIFIED MAINTENANCE PERSONNEL.
o Caution - risk of electric shock. Even after the unit is disconnected from the
mains (building wiring outlet), components inside the UPS system are still
connected to the battery and electrically live and dangerous.
o Before carrying out any kind of service and/or maintenance, disconnect the
batteries and verify that no current is present and no hazardous voltage exists
in the terminals of high capability capacitor such as BUS-capacitors.
o Only persons are adequately familiar with batteries and with the required
precautionary measures may replace batteries and supervise operations.
Unauthorized persons must be kept well away from the batteries.
o Caution - risk of electric shock. The battery circuit is not isolated from the input
voltage. Hazardous voltages may occur between the battery terminals and the
ground. Before touching, please verify that no voltage is present!
o Batteries may cause electric shock and have a high short-circuit current.
3
Please take the precautionary measures specified below and any other measures
necessary when working with batteries:
remove wristwatches, rings and other metal objects
use only tools with insulated grips and handles.
o When changing batteries, install the same number and same type of batteries. o Do not attempt to dispose of batteries by burning them. This could cause
battery explosion.
o Do not open or destroy batteries. Escaping electrolyte can cause injury to the
skin and eyes. It may be toxic.
o Please replace the fuse only with the same type and amperage in order to avoid
fire hazards.
o Do not dismantle the UPS system.
4
2. Installation and Setup
Before installation, please inspect the unit. Be sure that nothing inside the package is
damaged. Please keep the original package in a safe place for future use.
2.1. Rear Panel View.
5
6
1. AC input
2. Input circuit breaker
3. USB communication port
4. RS-232 communication port
5. SNMP intelligent slot (option)
6. External battery connection (only available for L model)
7. Output receptacles
8. Output terminal
9. Output circuit breaker
7
2.2. Install the UPS
Rack-mount Installation
This UPS can be mounted in the 19” rack chassis. Please follow below steps to position this
UPS.
Tower Installation
2.3. Setup the UPS
Step 1: Connect battery wires
If using rack UPS, the UPS is shipped out from factory without connecting battery wires for
safety consideration. Before installing the UPS, please follow below steps to re-connect battery
wires first.
8
Step 2: UPS input connection
Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension
cords.
o For 208/220/230/240VAC models: The power cord is supplied in the UPS package. o For 110/115/120/127VAC models: The power cord is attached to the UPS.
The input plug is a NEMA 5-15P for 1K model and NEMA 5-20P for 2K model.
Step 3: UPS output connection
o For socket-type outputs, simply connect devices to the outlets. o For terminal-type input or outputs, please follow below steps for the wiring
configuration:
a) Remove the small cover of the terminal block
b) Suggest using AWG14 or 2.1mm2 power cords for 3KVA (208/220/230/240VAC
models). Suggest using AWG12-10 or 3.3mm2-5.3mm2 power cords for 3KVA
(110/115/120/127VAC models). Please also install a circuit breaker (40A) between the
mains and AC input of UPS in 3KVA (110/115/120127VAC models) for safety operation.
c) Upon completion of the wiring configuration, please check whether the wires are
securely affixed.
d) Put the small cover back to the rear panel.
Step 4: Communication connection
Communication port:
USB port RS-232 port Intelligent slot
To allow for unattended UPS shutdown/start-up and status monitoring, connect the
communication cable one end to the USB/RS-232 port and the other to the communication
port of your PC. With the monitoring software installed, you can schedule UPS
shutdown/start-up and monitor UPS status through PC.
The UPS is equipped with intelligent slot perfect for either SNMP or AS400 card. When
9
installing either SNMP or AS400 card in the UPS, it will provide advanced communication and
monitoring options.
Step 5: Turn on the UPS
Press the ON/Mute button on the front panel for two seconds to power on the UPS.
NOTE: The battery charges fully during the first five hours of normal operation. Do not
expect full battery run capability during this initial charge period.
Step 6: Install software
For optimal computer system protection, install UPS monitoring software to fully configure
UPS shutdown. You may insert provided CD into CD-ROM to install the monitoring software. If
not, please follow steps below to download and install monitoring software from the internet:
1. Go to the website http://www.power-software-download.com.
2. Click View Power software icon and then choose your required OS to download the
software.
3. Follow the on-screen instructions to install the software.
4. When your computer restarts, the monitoring software will appear as an orange plug icon
located in the system tray, near the clock.
2.4. Battery Replacement
NOTICE: This UPS is equipped with internal batteries and user can replace the batteries
without shutting down the UPS or connected loads.(hot-swappable battery design)
Replacement is a safe procedure, isolated from electrical hazards.
CAUTION!! Consider all warnings, cautions, and notes before replacing batteries.
Note: Upon battery disconnection, equipment is not protected from power outages.
10
2.5. Battery Kit Assembly (OPTIONAL for rack UPS)
NOTICE: Please assemble battery kit first before installing it inside of UPS. Please
select correct battery kit procedure below to assemble it.
Batter Kit 2u
11
Batter Kit 3u
Batter Kit 4u
12
Batter Kit 6u
13
3. Operations
3.1. Button Operation
BUTTON
FUNCTION
ON/Mute
Button
o Turn on the UPS: Press and hold ON/Mute button for at least 2 seconds to turn
on the UPS.
o Mute the alarm: After the UPS is turned on in battery mode, press and hold this
button for at least 3 seconds to disable or enable the alarm system. But it’s not applied to the situations when warnings or errors occur.
o Up key: Press this button to display previous selection in UPS setting mode. o Switch to UPS self-test mode: Press ON/Mute buttons for 3 seconds to enter
UPS self-testing while in AC mode, ECO mode, or converter mode.
OFF/Enter
Button
o Turn off the UPS: Press and hold this button at least 2 seconds to turn off the
UPS. UPS will be in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by pressing this button.
o Confirm selection key: Press this button to confirm selection in UPS setting
mode.
Select Button
o Switch LCD message: Press this button to change the LCD message for input
voltage, input frequency, input current, battery voltage, battery current, battery capacity, ambient temperature, output voltage, output frequency, load current and load percent.
o Setting mode: Press and hold this button for 3 seconds to enter UPS setting
mode when Standby and Bypass mode.
o Down key: Press this button to display next selection in UPS setting mode.
ON/Mute + Select Button
o Switch to bypass mode: When the main power is normal, press ON/Mute and
Select buttons simultaneously for 3 seconds. Then UPS will enter to bypass mode. This action will be ineffective when the input voltage is out of acceptable range.
o Exit setting mode or return to the upper menu: When working in setting mode,
press ON/Mute and Select buttons simultaneously for 0.2 seconds to return to
the upper menu. If it’s already in top menu, press these two buttons at the same
time to exit the setting mode.
3.2. LCD Panel
14
DISPLAY
FUNCTION
REMAINING BACKUP TIME INFORMATION
Indicates the remaining backup time in pie chart.
Indicates the remaining backup time in numbers. H: hours, M: minute, S: second
FAULT INFORMATION
Indicates that the warning and fault occurs.
Indicates the warning and fault codes, and the codes are listed in details in 3-5 section.
MUTE OPERATION
Indicates that the UPS alarm is disabled.
OUTPUT & BATTERY VOLTAGE INFORMATION
Indicates the output voltage, frequency or battery voltage. Vac: output voltage, Vdc: battery voltage, Hz: frequency
LOAD INFORMATION
Indicates the load level by 0-25%, 26-50%, 51-75%, and 76-100%.
Indicates overload.
Indicates the load or the UPS output is short circuit.
MODE OPERATION INFORMATION
Indicates the UPS connects to the mains.
Indicates the battery is working.
Indicates the bypass circuit is working.
Indicates the ECO mode is enabled.
Indicates the Inverter circuit is working.
Indicates the output is working.
BATTERY INFORMATION
Indicates the Battery level by 0-25%, 26-50%, 51-75%, and 76-100%.
Indicates the battery is fault.
Indicates low battery level and low battery voltage.
INPUT & BATTERY VOLTAGE INFORMATION
Indicates the input voltage or frequency or battery voltage. Vac: Input voltage, Vdc: battery voltage, Hz: input frequency
15
3.3. Audible Alarm
Battery Mode
Sounding every 4 seconds
Low Battery
Sounding every seconds
Overload
Sounding twice every second
Fault
Continuously sounding
Bypass Mode
Sounding every 10 seconds
3.4. LCD display wordings index
ABBREVIATION
DISPLAY CONTENT
MEANING
ENA
Enable
DIS Disable
ESC
Escape
HLS
High loss
LLS Low loss
BAT
Battery
CF Converter
TP Temperature
CH Charger
FU Bypass frequency unstable
EE EEPROM error
3.5. UPS Setting
Parameter 1: It’s for program alternatives. Refer to below table.
Parameter 2 and 3: are the setting options or values for each program.
16
01: Output voltage setting.
INTERFACE
SETTING
Parameter 3: Output voltage
For 208/220/230/240 VAC models, you may choose the
following output voltage:
208: presents output voltage is 208Vac.
220: presents output voltage is 220Vac.
230: presents output voltage is 230Vac (Default).
240: presents output voltage is 240Vac.
For 110/115/120/127 VAC models, you may choose the
following output voltage:
110: presents output voltage is 110Vac.
115: presents output voltage is 115Vac.
120: presents output voltage is 120Vac (Default).
127: presents output voltage is 127Vac.
02: Frequency Converter enable/disable.
INTERFACE
SETTING
Parameter 2 & 3: Enable or disable converter mode.
CF ENA: Converter modes enable.
CF DIS: Converter mode disables(Default).
03: Output frequency setting.
INTERFACE
SETTING
Parameter 2 & 3: Output frequency setting.
You may set the initial frequency on battery mode:
BAT 50: presents output frequency is 50Hz.
BAT 60: presents output frequency is 60Hz.
If converter mode enable, you may choose the following
output frequency:
CF 50: presents output frequency is 50Hz.
CF 60: presents output frequency is 60Hz.
17
04: ECO enable/disable.
INTERFACE
SETTING
Parameter 3: Enable or disable ECO function.
ENA: ECO mode enable.
DIS: ECO mode disable (Default).
05: ECO voltage range setting.
INTERFACE
SETTING
Parameter 2 & 3: Set the acceptable high voltage
point and low voltage point for ECO mode.
Press the Down key or Up key.
HLS: High loss voltage in ECO mode.
For 208/220/230/240 VAC a model, the setting range is
from +7V to +24V of the nominal voltage (Default:
+12V).
For 110/115/120/127 VAC a model, the setting range is
from +3V to +12V of the nominal voltage (Default:
+6V).
LLS: Low loss voltage in ECO mode.
For 208/220/230/240 VAC models, the setting range is
from -7V to -24V of the nominal voltage. (Default: -12V).
For 110/115/120/127 VAC models, the setting range is
from -3V to -12V of the nominal voltage (Default: -6V).
06: Bypass mode enable/disable.
18
INTERFACE
SETTING
Parameter 3: Enable or disable Bypass function.
ENA: Bypass mode enable.
DIS: Bypass mode disable (Default).
07: Bypass voltage range setting.
INTERFACE
SETTING
Parameter 2 & 3: Set the acceptable high voltage
point and acceptable low voltage.
Press the Down key or Up key to set.
HLS: Bypass high voltage point.
For 208/220/230/240 VAC models:
235-264: setting the high voltage point from
235Vac to 264Vac (Default: 264Vac).
For 110/115/120/127 VAC models:
125-132: setting the high voltage point from
115Vac to 132Vac (Default: 132Vac).
LLS: Bypass low voltage point.
184-225: setting the low voltage point from
184Vac to 225Vac (Default: 195Vac).
For 110/115/120/127 VAC models:
98-115: setting the high voltage point from
98Vac to 115Vac (Default: 98Vac).
08: Autonomy limitation setting
INTERFACE
SETTING
19
Parameter 3: Set up backup time on battery mode
for general outlets.
0-999: setting the backup time in minutes from 0-999
for general outlets on battery mode.
0: When setting as “0”, the backup time will be
only 10 seconds.
999: When setting as “999”, the backup time
setting will be disabled. (Default)
00: Exit setting
3.6. Operating Mode Description
OPERATING
MODE
DESCRIPTION
LCD DISPLAY
Online mode
When the input voltage is within acceptable range, UPS will provide pure and stable AC power to output. The UPS will also charge the battery at online mode.
ECO mode
Energy saving mode: When the input voltage is within voltage regulation range, UPS will bypass voltage to output for energy saving.
Frequency
Converter mode
When input frequency is within 40 Hz to 70 Hz, the UPS can be set at a constant output frequency, 50 Hz or 60 Hz. The UPS will still charge battery under this mode.
Battery mode
When the input voltage is beyond the acceptable range or power failure and alarm is sounding every 4 second, UPS will backup power from battery.
Bypass mode
When input voltage is within acceptable range but UPS is overload, UPS will enter bypass mode or bypass mode can be set by front panel. Alarm is sounding every 10 second.
20
Standby mode
UPS is powered off and no output supply power, but still can charge batteries.
3.7. Faults Reference Code
FAULT EVENT
FAULT
CODE
ICON
FAULT EVENT
FAULT
CODE
ICON
Bus start fail
01
x
Inverter output short
14
Bus over
02
x
Battery voltage too high
27
Bus under
03
x
Battery voltage too low
28
Bus unbalance
04
x
Over temperature
41
x
Inverter soft start failure
11
x
Overload
43
Inverter voltage high
12
x
Charger failure
45
x
Inverter voltage Low
13
x
3.8. Warning indicator
21
4. Trouble Shooting
If the UPS system does not operate correctly, please solve the problem by using the table
below.
SYMPTOM
POSSIBLE CAUSE
REMEDY
No indication and alarm even
though the mains is normal.
The AC input power is not
connected well.
Check if input power cord
firmly connected to the
mains.
The AC input is connected to
the UPS output.
Plug AC input power cord to
AC input correctly.
The icon and flashing on
LCD display and alarm is sounding
every second.
The external or internal
battery is incorrectly
connected.
Check if all batteries are
connected well.
Fault code is shown as 27 or 28 and
the icon is lighting on LCD
display and alarm is continuously
sounding.
Battery voltage is too
high/low or the charger is
fault.
Contact your dealer.
The icon and is
flashing on LCD display and alarm is
sounding twice every second.
UPS is overload
Remove excess loads from
UPS output.
UPS is overloaded. Devices
connected to the UPS are
fed directly by the electrical
network via the Bypass.
Remove excess loads from
UPS output.
After repetitive overloads,
the UPS is locked in the Bypass mode. Connected devices are fed directly by
the mains.
Remove excess loads from
UPS output first. Then shut
down the UPS and restart it.
Fault code is shown as 43 and The
icon is lighting on LCD
display and alarm is continuously
sounding.
The UPS shut down
automatically because of
overload at the UPS output.
Remove excess loads from
UPS output and restart it.
Fault code is shown as 14 and the
icon is lighting on LCD display and alarm is continuously
sounding.
The UPS shut down
automatically because short
circuit occurs on the UPS
output.
Check output wiring and if
connected devices are in
short circuit status.
22
Fault code is shown as 01, 02, 03,
04, 11, 12, 13, 41 and 45 on LCD display and alarm is continuously
sounding.
A UPS internal fault has
occurred. There are two
possible results:
1. The load is still supplied, but directly from AC power
via bypass.
2. The load is no longer supplied by power.
Contact your dealer
SYMPTOM
POSSIBLE CAUSE
REMEDY
Battery backup time is shorter than
nominal value
Batteries are not fully
charged
Charge the batteries for at
least 5 hours and then check
capacity. If the problem still
persists, consult your dealer.
Batteries defect
Contact your dealer to
replace the battery.
Warning code” “is displayed in
LCD panel when turn on.
The internal temperature is
too high.
1. Temperature sensor problem. Please contact
your dealer.
2. Wait until internal temperature cool down.
Then, turn on the UPS
again.
5. Storage and Maintenance
Operation
The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at
25°C ambient temperature) has been exceeded, the batteries must be replaced. In this
case, please contact your dealer.
Storage
Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool, dry
location. During storage, recharge the battery in accordance with the following table:
BE SURE TO DELIVER THE SPENT BATTERY TO A RECYCLING FACILITY OR SHIP IT
TO YOUR DEALER IN THE REPLACEMENT BATTERY PACKING MATERIAL.
23
STORAGE TEMPERATURE
RECHARGE FREQUENCY
CHARGING DURATION
-25°C - 40°C
Every 3 months
1-2 hours
40°C - 45°C
Every 2 months
1-2 hours
6. Technical Specifications – Stand Alone.
24
MODEL SA1P1LVW/SA1P1HVW SA1P2LVW/SA1P2HVW SA1P3LVW/SA1P3HVW
Phase
Capacity
[1]
1000 VA / 900 W 2000 VA / 1800 W 3000 VA / 2700 W
INPUT
Nominal Voltage
Frequency Range Power Factor Rectifier
OUTPUT
Output Voltage
Voltage Regulation
Frequency Range (Synchronized Range)
Frequency Range (Batt. Mode)
Current Crest Ratio
Harmonic Distortion (THDv)
Transfer Time
Waveform
EFFICIENCY
AC Mode
88% 89% 90%
Battery Mode 83% 85% 88%
BATTERY
Battery Type Numbers 2 4 6 Typical Recharge Time Charging Current Charging Voltage 27.4VDC ± 1% 54.7 VDC ±1% 82.1 VDC ±1%
INDICATORS
LCD Display
ALARM
Battery Mode Low Battery Overload Fault
PHYSICAL
Dimensions (DxWxH) (mm) 282 x 145 x 220 397 x 145 x 220 421 x 190 x 318 Net Weight (kg)
9,8 17 27,6
ENVIRONMENT
Running Humidity & Temperature Noise Level
MANAGEMENT
Smart RS-232 /USB Optional SNMP
STANDARDS & CERTIFICATIONS
Quality Compliance
< 50 dB @ 1 meter
Supports Windows® 2000/2003/XP/Vista/2008, Windows®7/8, Linux, Unix and MAC
Power management from SNMP manager and web browser
12V/9 Ah
4 hours recover to 90% capacity
1.0 A
Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators
20 - 90 % RH (Non-condensing) @ 0 - 40°C
Sounding every 4 seconds
Sounding every seconds
Sounding twice every second
SY-G reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications on SY-G products previously or subsequently sold.
ISO 9001 ; ISO 14001
[1]
Derate to 80% of capacity in Frequency converter mode and to 80% when the output voltage is adjusted to 100/200/208 VAC
EN62040-3, EN61000, EN62040-2, EN62040 -1, CE
Voltage Range
60-150 VAC or 120-300 VAC @ 50% load
90-140 VAC or 180-280 VAC @ 100% load
50/60 Hz ± 0.5 %
≥ 0.99, Nominal Voltage (100% load)
IGBT
100
[1]
/110/115/120/127 VAC or 200
[1]
/208
[1]
/220/230/240 VAC
47 - 53 Hz or 57 - 63 Hz
Continuously sounding
Zero (AC to DC) ; 4 ms (Inverter to Bypass)
Pure Sine Wave
Single phase with ground
100/110/115/120/127 VAC or 200/208/220/230/240 VAC
≤ 3% THD (Linear Load) , ≤ 6% THD (Non-linear Load)
40 Hz - 70 Hz
± 1%
3:1
25
Technical Specifications – Rack Mount.
MODEL RM1P1LVW / RM1P1HVW RM1P2LVW / RM1P2HVW RM1P3LVW / RM1P3HVW
Phase
Capacity
[1]
1000 VA / 900 W 2000 VA / 1800 W 3000 VA / 2700 W
INPUT
Nominal Voltage
Power Factor Frequency Range Rectifier
OUTPUT
Output Voltage
Voltage Regulation
Frequency Range (Synchronized Range)
Frequency Range (Batt. Mode)
Current Crest Ratio
Harmonic Distortion (THDv)
Transfer Time
Waveform
EFFICIENCY
AC Mode
88% 89% 90%
Battery Mode 83% 87% 88%
BATTERY
Battery Type Numbers 2 4 6 Typical Recharge Time Charging Current Charging Voltage 27.4VDC ± 1% 54.7 VDC ±1% 82.1 VDC ±1%
INDICATORS
LCD Display
ALARM
Battery Mode Low Battery Overload Fault
PHYSICAL
Dimensions (DxWxH) (mm) 310 x 438 x 88 410 x 438 x 88 630 x 438 x 88 Net Weight (kg)
12 19 29.3
ENVIRONMENT
Running Humidity & Temperature Noise Level
MANAGEMENT
Smart RS-232 /USB Optional SNMP
STANDARDS & CERTIFICATIONS
Quality Compliance
ISO 9001 ; ISO 14001
[1]
Derate to 80% of capacity in Frequency converter mode and to 80% when the output voltage is adjusted to 100/200/208 VAC
SY-G reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications on SY-G products previously or subsequently sold.
EN62040-3, EN61000, EN62040-2, EN62040 -1, CE
Power management from SNMP manager and web browser
Sounding every 4 seconds
Sounding every seconds
Sounding twice every second
Continuously sounding
20 - 90 % RH (Non-condensing) @ 0 - 40°C
< 50 dB @ 1 meter
Supports Windows® 2000/2003/XP/Vista/2008, Windows®7/8, Linux, Unix and MAC
UPS status, load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
47 - 53 Hz or 57 - 63 Hz
50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz
≤ 3% THD (Linear Load) , ≤ 6% THD (Non-linear Load)
Zero (AC to DC) ; 4 ms (Inverter to Bypass)
Pure Sine Wave
12V/ 9 Ah
4 hours recover to 90% capacity
1.0 A
3:1
Voltage Range
60-145 VAC or 120-300 VAC @ 50% load
90-145 VAC or 180-300 VAC @ 100% load
≥ 0.99, Nominal Voltage (100% load)
40 Hz - 70 Hz
± 1%
Single phase with ground
100/110/115/120/127 VAC or 200/208/220/230/240 VAC
IGBT
100
[1]
/110/115/120/127 VAC or 200
[1]
/208
[1]
/220/230/240 VAC
26
ANNOTATION:
Sy-G reserves the right to alter the features of its products without prior notice.