Swema SwemaMan 7 Operating Instructions Manual

SwemaMan 7
Operating instructions
vers 1.13 MB_CW20180425
WARNING! Before start measuring please read chapter ”6. Set­tings (Set)”. At delivery k2-factor is turned on.
Contents: SWEMA AB Pepparv. 27 123 56 FARSTA Tel: +46 8 94 00 90 Fax: +46 8 93 44 93 E-mail: swema@swema.com Web page: www.swema.com
1. Introduction......................... 1
2. Technical data....................... 2
3. Start of instrument............... 2
4. Unit..................................... 3
5. Mode................................... 5
6. Settings (Set)....................... 9
7. Notebook............................ 10
1. Introduction
SwemaMan 7 is a micro manometer for differential pressure, air ow and air velocity. Differential pressure is measured in Pa, airow in l/s,
m3/h or CFM and air velocity in m/s or fpm. It’s possible to set baro­metric pressure and temperature to compensate for correct air density.
Measure airow either with k-factor or with area in duct. The area is
entered into the instrument directly, as diameter or as height x width. SwemaMan 7 can calculate minimum, maximum and average value. Saved measurements are easily transferred to a PC.
SwemaMan 7 has display light, usb connector and are delivered with two easily replaceable AA batteries.
Differential pressure
Key Up
Max
Key Left Average
Key Down
Min
Function keys
Enter
Key Right Zeroing
ON / OFF Display light
USB connector
Batteries
1.
2. Technical data
Differential pressure: -1000... 9999 Pa Air velocity: 2... 130 m/s
Measurement uncertainty at 23°C: ±1% read value, min ±0.5Pa
95% coverage probability in non condensing, non moist air, <80%RH, non aggressive gases.
Ambient temperature: 0... 50°C Memory: 300 Notes PC-communication: USB Battery: 2x 1,5V AA (Standard or rechargeable) Battery operating time: Up to 150h (24h with display light turned on) Size: 180x82X36mm Weight: 390g IP50 (dust)
2. Start of instrument
When starting the instrument (ON/OFF-button), the display shows
the battery voltage, rmware version and calibration date. After a
couple of seconds it’s in measuring mode. SwemaMan 7 will start in the same measuring mode it was set to when turned off.
Display light: The display light can be turned On and Off by pressing the ON/OFF-button (when instrument is turned on).
Turn Off: To turn off the instrument press and hold down the ON/ OFF-button for about 2 seconds until the text ”OFF” is shown on the
display.
Zeroing: To reset the pressure sensor to zero press Key Right. When the pressure sensor is zeroing the text ”Zero” and the digit ”0” will be shown on the display (see picture to the right). Note! Disconnect pressure from the pressure connectors before zeroing.
2.
Measurement: When in measuring mode press Enter to store a value in the volatile memory.
The number of measuring points stored in the volatile memory is shown on the display directly under the measured values, ”2P” (see picture to the right) means the two measuring points has been stored. When Enter is pressed an average of the measuring points is shown for a short while before the measured values is shown in real time again.
Average, Max & Min: To check the average, max or min value of the stored measurement points press Key Left (Average), Key Up (Max) or Key Down (Min), as long as the button is hold down the corresponding value will be shown on the display.
Save a measurement: After a measuring point has been stored it’s possible to save the measurement into SwemaMan 7:s Notebook by pressing Save. The display will show which note number the meas­urement is saved as (example n3 = note 3). To instead erase the measurement from the volatile memory press Clear.
4. Unit
Press Unit to alternate between the different units. The units Swema­Man 7 can display are:
• Pa
• m/s & Pa (fpm & Pa if US-unit is selected)
• l/s & Pa (cfm & Pa if US-unit is selected)
• m3/h & Pa (cfm & Pa if US-unit is selected)
• hPa & °C (inHg & °F if US-unit is selected)
Differential Pressure (Pa): Press Unit until SwemaMan 7 shows the unit Pa. A measurement with average, max and min and also saving of the measurement is possible. If pressure is big­ger than 10.000 Pa or lower than -1000 Pa (out
of range) the digit will ash.
Air Velocity (m/s & Pa): It’s possible to meas- ure air velocity with SwemaMan 7 by connecting a pito static tube. Press UNIT until SwemaMan 7 shows the units m/s and Pa. A measurement with average, max and min and also saving of the measurement is possible. Air velocity lower than 0.7 m/s will be shown as zero.
3.
Differential pressure meas­urement
Air velocity measurement