Application area
The product is a variable flow damper, constant flow damper or a constant pressure damper with integrated radio transmitter designed for comfort ventilation indoors within Swegon’s system for demand­controlled ventilation WISE. The product is used to regulate supply or extract air flow, alternatively constant pressure hold a static pressure in the ventilation duct.
The product may not be used for anything other than its intended use.
General
Read through the entire instructions for use before you install/ use the product and save the instructions for future reference. It is not permissible to make changes or modify this product other than those specified in this document.
The packaging contains the following items:
1 x WISE Damper
1 x Instructions for use
Protective equipment
Always use appropriate personal protective equipment for the work in question, in the form of gloves, respirators and protec­tive glasses during handling, installation, cleaning and service / maintenance.
Electrical safety
Permitted voltage, see “Electrical data”.
It is not permissible to insert foreign objects into the product’s contac­tor connections or the electronics's ventilation openings; risk for short
circuiting.
24 V isolation transformer to be connected should comply with the provisions of IEC 61558-1.
Cable sizing must be carried out for cabling between the product and the power supply source.
Disconnect the power supply when working on products that are not required to run in production.
Always follow the local/national rules for who shall be permitted to carry out this type of electrical installation.
If the product is equipped with a spring return actuator there is no release button, manual control is performed using the supplied hex key where the damper blade is cranked to the required position and then locked. Do not forget to disable the lock after working on it.
Other risk
When the product is voltage fed, the damper will be either open or close and there can be a certain risk for pinch injuries, for example, on the fingers if these are placed between the damper blade and ventilation duct when the damper blade rotates. The product’s actuator is equipped with a release button that permits manual control of the damper blade, always ensure this is activated before working on the internal parts of the damper.
Handling
• Always use appropriate transpor t and lifting devices when the prod­uct is to be handled to reduce ergonomic loads.
• The product must be handled with care.
• It is not permissible to carry the product by the measuring tube.
Installation
• Moist, cold and aggressive environments must be avoided.
• Avoid installing the product near a heat source.
• Assemble the product according to applicable industry regulations.
• Install the product so that it is not accessible by unauthorized per­sons, for example above a suspended ceiling.
• Install the product for easy access during service/maintenance.
• Supplement the duct system with a cleaning hatch in the vicinity of the product to facilitate cleaning.
• If the product is mounted above a fixed ceiling, the inspection hatch must be located so that the product is accessible for inspection.
• If the product is mounted so that it is possible to gain access to the inside of the product, it must be supplemented with appropriate protection, for example, a ventilation unit.
• If the product is mounted in cold areas, the whole product must be insulated on the outside against condensation.
• For installation, the accessor y FSR is recommended.
• The product can be installed position-independent.
• It is recommended to mount the product so that the product’s cover is visible from the floor.
• The product must be laid down prior to installation so that it cannot fall over.
• Check to make sure that the product does not have any visible defects.
• Check that the product is properly secured after it has been installed.
• Use the product’s eyes to secure the cables with cable ties.
• Check that all cables are properly secured in place after installation.
• Check that the cover is properly mounted in place.
WISE Damper
2
Swegon reserves the right to alter specications. 20180620
Figure 2. Installation in the duct system The ducts must be firmly fixed to the frame of the building on each side of WISE Damper.
1. WISE Damper
2. FSR Clamp
3. Sound attenuator
1. WISE Damper
2. FSR Clamp
Installation, torque, dimensions and weights
Circular design
Size Ø (mm)
A (mm)
Installation dimensions
(mm)
Normal
motor
Spring return
Flow range
Tolerance Q
*
± 5%
with at least ±x l /s
Min. (0.6
m/s)
Max. (10
m/s)
Torque ( Nm )
Weight (kg)
C (mm)
Torque ( Nm )
Weight (kg)
l/s
m
3
/h
l/s
m
3
/h
100 574 584 5 2.5 11 5 3.0 5 18 79 285 2
125 5 74 584 5 2.8 24 5 3.3 7 26 12 3 4 43 2
160 574 584 5 3.2 33 5 3.7 11 40 202 728 2
200 574 584 5 3.7 19 5 4.2 18 65 315 1134 3
250 574 584 5 4.3 13 5 4.8 30 108 491 176 8 5
315 600 610 10 5.2 0 10 6.2 50 180 780 2808 8
400 830 850 10 8.0 0 10 9.0 87 314 1257 4526 13
500 830 850 10 9.9 0 10 10.9 135 486 196 4 7071 20
630 9 15 935 15 13.5 0 20 14.5 187 674 3 118 11225 32
*
Installed according to the instructions
Figure 4. Dimensions, WISE Damper circular and WISE Damper circular with spring return.
125
125
A
ø
C
Figure 1. Requires a straight section of 2 x Ø for sound attenua­tors with baffle or centre body.
Installation – all designs
• WISE Dampers’ air flow measurement requires a straight section before and after the product (in the air direction) according to the installation figures.
• Instructions for Use are supplied with the product on delivery, but can also be downloaded from www. swegon.com.
Installation – circular version
• Installation is position dependent.
Figure 3. Straight section requirements, circular ducts. 1-5: Quantity Ø before the product: 0 x Ø. 6: Quantity Ø before the product: 2 x Ø.
*
Cleaning hatch
1.
2.
3*.
4.
5.
6.
3
20180620 Swegon reserves the right to alter specications.
WISE Damper
Rectangular design
Size BXH (mm)
Normal
motor
Spring return
Flow range
Tolerance Q
*
±5%
with at least ±x l /s
Torque (Nm)
Weight (kg)
Torque (Nm)
Weight (kg)
Min. (1 m/s) Max. (10 m/s)
l/s m
3
/h l/s m3/h
200 x 200 5 7. 2 5 8.0 34 12 3 400 14 4 0 4
300 x 200 5 8.4 5 9.2 50 18 0 600 2160 6
400 x 200 5 9.9 5 10.7 67 242 800 2880 8
500 x 200 5 11 .4 5 12.2 84 303 1000 3600 10
600 x 200 5 12. 9 5 13.7 10 0 360 1200 4320 12
700 x 200 5 14. 4 5 15.2 117 422 140 0 5040 14
800 x 200 5 15 .4 5 16.2 133 479 160 0 576 0 16
1000 x 200 10 18.4 10 19.9 167 602 2000 7200 20
300 x 300 5 10.9 5 11 . 3 76 274 900 3240 9
400 x 30 0 5 12.4 5 12.9 102 368 1200 4320 12
500 x 300 5 13 .9 5 14.4 127 458 150 0 5400 15
600 x 300 5 15 .4 5 15.9 152 548 18 00 6480 18
700 x 300 10 16.8 10 17. 8 178 641 2100 7560 21
800 x 30 0 10 18.4 10 19. 4 203 731 240 0 8640 24
1000 x 300 10 21. 4 10 22.4 254 915 3000 10800 30
400 x 400 5 14.0 5 14 .5 136 490 160 0 5760 16
500 x 40 0 10 16.0 10 18.0 171 616 2000 7200 20
600 x 40 0 10 17. 4 10 18 .5 205 738 2400 8640 24
700 x 400 10 19.6 10 20.6 250 900 2800 10080 28
800 x 400 10 21.1 10 22.2 273 983 3200 1152 0 32
1000 x 400 10 24. 2 10 25.2 341 12 28 4000 144 0 0 40
1200 x 400 15 27. 2 20 29.2 409 1473 4800 17280 48
1400 x 400 15 30.3 20 32.2 478 17 21 5600 2016 0 56
1600 x 400 15 33.3 20 35.3 546 196 6 6400 23040 64
500 x 500 10 18.5 10 19.5 214 771 250 0 9000 25
600 x 500 10 20.5 10 21. 6 257 926 3000 10800 30
700 x 500 10 22.6 10 23.6 300 1080 3500 12600 35
800 x 50 0 10 24.6 10 25.6 343 123 5 4000 14400 40
1000 x 500 15 28.6 20 30.6 429 1545 5000 18000 50
1200 x 500 15 32.7 20 34.6 514 1851 6000 21600 60
1400 x 500 15 36.8 20 38.7 600 2160 7000 25200 70
1600 x 500 15 40.8 20 42.8 686 2470 8000 2880 0 80
600 x 60 0 10 22.7 10 23.7 309 111 3 3600 12 960 36
700 x 600 10 24.8 10 25.8 361 13 0 0 4200 15120 42
800 x 60 0 15 26.8 20 2 7. 8 412 1484 4800 17 28 0 48
1000 x 600 15 30.9 20 32.9 515 1854 6000 2160 0 60
1200 x 600 15 35.0 20 37. 0 618 2225 7200 25920 72
1400 x 600 15 39.2 20
41.1 722 2600 8,400 30240 84
1600 x 600 15 43.3 20 45.2 825 2970 9600 34560 96
700 x 700 15 27.6 20 29.5 422 1520 4900 17640 49
800 x 700 15 30.3 20 32. 2 482 17 36 5600 2016 0 56
1000 x 700 15 34.9 20 36.8 603 2171 7000 25200 70
1200 x 700 15 40.6 20 42.6 723 2603 8,400 3024 0 84
1400 x 700 15 45.7 20 47. 7 844 3039 9800 35280 98
1600 x 700 15 51.0 20 52.9 964 3471 11 20 0 40320 112
*
Installed according to the instructions
20
H
20
220
250
20
20
B
104
Figure 7. Dimensions, WISE Damper rectangular and WISE Damper rectangular with spring return.
Installation – rectangular design
Dimension B in the figure and table below is found in the table “Rectangular design” to the left.
NOTE! Damper spindles must be installed horizontally.
Straight section before WISE Damper in rectangular ducts
Type of disruption
E (m
2
=5%) E (m2=10%)
One 90° bend E = 3 x B E = 2 x B
T piece E = 3 x B E = 2 x B
Figure 5. Straight section requirements, rectangular ducts.
Figure 6. Straight section requirements, rectangular WISE Damper and sound attenuator with baffle. Installation with straight section applies both to supply and extract air.
1 = Rectangular WISE Damper. 2 = Straight duct 500 mm. 3 = Sound attenuator with baffle.
Straight section before/after WISE Damper – sound attenuator with baffle
E
H
B
E
H
B
1
2
3
Loading...