Swegon WISE Damper a Instructions For Use Manual

WISE Damper a
Instructions for Use
20180620
Ar t. 15460 0 2
Symbol key
Symbols on the machine
Symbols in this user manual
Warning/Caution!
Risk of crushing
The document was originally written in Swedish.
Application area
The product is a variable flow damper, constant flow damper or a constant pressure damper with integrated radio transmitter designed for comfort ventilation indoors within Swegon’s system for demand­controlled ventilation WISE. The product is used to regulate supply or extract air flow, alternatively constant pressure hold a static pressure in the ventilation duct.
The product may not be used for anything other than its intended use.
General
Read through the entire instructions for use before you install/ use the product and save the instructions for future reference. It is not permissible to make changes or modify this product other than those specified in this document.
The packaging contains the following items:
1 x WISE Damper
1 x Instructions for use
Protective equipment
Always use appropriate personal protective equipment for the work in question, in the form of gloves, respirators and protec­tive glasses during handling, installation, cleaning and service / maintenance.
Electrical safety
Permitted voltage, see “Electrical data”.
It is not permissible to insert foreign objects into the product’s contac­tor connections or the electronics's ventilation openings; risk for short
circuiting.
24 V isolation transformer to be connected should comply with the provisions of IEC 61558-1.
Cable sizing must be carried out for cabling between the product and the power supply source.
Disconnect the power supply when working on products that are not required to run in production.
Always follow the local/national rules for who shall be permitted to carry out this type of electrical installation.
If the product is equipped with a spring return actuator there is no release button, manual control is performed using the supplied hex key where the damper blade is cranked to the required position and then locked. Do not forget to disable the lock after working on it.
Other risk
When the product is voltage fed, the damper will be either open or close and there can be a certain risk for pinch injuries, for example, on the fingers if these are placed between the damper blade and ventilation duct when the damper blade rotates. The product’s actuator is equipped with a release button that permits manual control of the damper blade, always ensure this is activated before working on the internal parts of the damper.
Handling
• Always use appropriate transpor t and lifting devices when the prod­uct is to be handled to reduce ergonomic loads.
• The product must be handled with care.
• It is not permissible to carry the product by the measuring tube.
Installation
• Moist, cold and aggressive environments must be avoided.
• Avoid installing the product near a heat source.
• Assemble the product according to applicable industry regulations.
• Install the product so that it is not accessible by unauthorized per­sons, for example above a suspended ceiling.
• Install the product for easy access during service/maintenance.
• Supplement the duct system with a cleaning hatch in the vicinity of the product to facilitate cleaning.
• If the product is mounted above a fixed ceiling, the inspection hatch must be located so that the product is accessible for inspection.
• If the product is mounted so that it is possible to gain access to the inside of the product, it must be supplemented with appropriate protection, for example, a ventilation unit.
• If the product is mounted in cold areas, the whole product must be insulated on the outside against condensation.
• For installation, the accessor y FSR is recommended.
• The product can be installed position-independent.
• It is recommended to mount the product so that the product’s cover is visible from the floor.
• The product must be laid down prior to installation so that it cannot fall over.
• Check to make sure that the product does not have any visible defects.
• Check that the product is properly secured after it has been installed.
• Use the product’s eyes to secure the cables with cable ties.
• Check that all cables are properly secured in place after installation.
• Check that the cover is properly mounted in place.
WISE Damper
2
Swegon reserves the right to alter specications. 20180620
Figure 2. Installation in the duct system The ducts must be firmly fixed to the frame of the building on each side of WISE Damper.
1. WISE Damper
2. FSR Clamp
3. Sound attenuator
1. WISE Damper
2. FSR Clamp
Installation, torque, dimensions and weights
Circular design
Size Ø (mm)
A (mm)
Installation dimensions
(mm)
Normal
motor
Spring return
Flow range
Tolerance Q
*
± 5%
with at least ±x l /s
Min. (0.6
m/s)
Max. (10
m/s)
Torque ( Nm )
Weight (kg)
C (mm)
Torque ( Nm )
Weight (kg)
l/s
m
3
/h
l/s
m
3
/h
100 574 584 5 2.5 11 5 3.0 5 18 79 285 2
125 5 74 584 5 2.8 24 5 3.3 7 26 12 3 4 43 2
160 574 584 5 3.2 33 5 3.7 11 40 202 728 2
200 574 584 5 3.7 19 5 4.2 18 65 315 1134 3
250 574 584 5 4.3 13 5 4.8 30 108 491 176 8 5
315 600 610 10 5.2 0 10 6.2 50 180 780 2808 8
400 830 850 10 8.0 0 10 9.0 87 314 1257 4526 13
500 830 850 10 9.9 0 10 10.9 135 486 196 4 7071 20
630 9 15 935 15 13.5 0 20 14.5 187 674 3 118 11225 32
*
Installed according to the instructions
Figure 4. Dimensions, WISE Damper circular and WISE Damper circular with spring return.
125
125
A
ø
C
Figure 1. Requires a straight section of 2 x Ø for sound attenua­tors with baffle or centre body.
Installation – all designs
• WISE Dampers’ air flow measurement requires a straight section before and after the product (in the air direction) according to the installation figures.
• Instructions for Use are supplied with the product on delivery, but can also be downloaded from www. swegon.com.
Installation – circular version
• Installation is position dependent.
Figure 3. Straight section requirements, circular ducts. 1-5: Quantity Ø before the product: 0 x Ø. 6: Quantity Ø before the product: 2 x Ø.
*
Cleaning hatch
1.
2.
3*.
4.
5.
6.
3
20180620 Swegon reserves the right to alter specications.
WISE Damper
Rectangular design
Size BXH (mm)
Normal
motor
Spring return
Flow range
Tolerance Q
*
±5%
with at least ±x l /s
Torque (Nm)
Weight (kg)
Torque (Nm)
Weight (kg)
Min. (1 m/s) Max. (10 m/s)
l/s m
3
/h l/s m3/h
200 x 200 5 7. 2 5 8.0 34 12 3 400 14 4 0 4
300 x 200 5 8.4 5 9.2 50 18 0 600 2160 6
400 x 200 5 9.9 5 10.7 67 242 800 2880 8
500 x 200 5 11 .4 5 12.2 84 303 1000 3600 10
600 x 200 5 12. 9 5 13.7 10 0 360 1200 4320 12
700 x 200 5 14. 4 5 15.2 117 422 140 0 5040 14
800 x 200 5 15 .4 5 16.2 133 479 160 0 576 0 16
1000 x 200 10 18.4 10 19.9 167 602 2000 7200 20
300 x 300 5 10.9 5 11 . 3 76 274 900 3240 9
400 x 30 0 5 12.4 5 12.9 102 368 1200 4320 12
500 x 300 5 13 .9 5 14.4 127 458 150 0 5400 15
600 x 300 5 15 .4 5 15.9 152 548 18 00 6480 18
700 x 300 10 16.8 10 17. 8 178 641 2100 7560 21
800 x 30 0 10 18.4 10 19. 4 203 731 240 0 8640 24
1000 x 300 10 21. 4 10 22.4 254 915 3000 10800 30
400 x 400 5 14.0 5 14 .5 136 490 160 0 5760 16
500 x 40 0 10 16.0 10 18.0 171 616 2000 7200 20
600 x 40 0 10 17. 4 10 18 .5 205 738 2400 8640 24
700 x 400 10 19.6 10 20.6 250 900 2800 10080 28
800 x 400 10 21.1 10 22.2 273 983 3200 1152 0 32
1000 x 400 10 24. 2 10 25.2 341 12 28 4000 144 0 0 40
1200 x 400 15 27. 2 20 29.2 409 1473 4800 17280 48
1400 x 400 15 30.3 20 32.2 478 17 21 5600 2016 0 56
1600 x 400 15 33.3 20 35.3 546 196 6 6400 23040 64
500 x 500 10 18.5 10 19.5 214 771 250 0 9000 25
600 x 500 10 20.5 10 21. 6 257 926 3000 10800 30
700 x 500 10 22.6 10 23.6 300 1080 3500 12600 35
800 x 50 0 10 24.6 10 25.6 343 123 5 4000 14400 40
1000 x 500 15 28.6 20 30.6 429 1545 5000 18000 50
1200 x 500 15 32.7 20 34.6 514 1851 6000 21600 60
1400 x 500 15 36.8 20 38.7 600 2160 7000 25200 70
1600 x 500 15 40.8 20 42.8 686 2470 8000 2880 0 80
600 x 60 0 10 22.7 10 23.7 309 111 3 3600 12 960 36
700 x 600 10 24.8 10 25.8 361 13 0 0 4200 15120 42
800 x 60 0 15 26.8 20 2 7. 8 412 1484 4800 17 28 0 48
1000 x 600 15 30.9 20 32.9 515 1854 6000 2160 0 60
1200 x 600 15 35.0 20 37. 0 618 2225 7200 25920 72
1400 x 600 15 39.2 20
41.1 722 2600 8,400 30240 84
1600 x 600 15 43.3 20 45.2 825 2970 9600 34560 96
700 x 700 15 27.6 20 29.5 422 1520 4900 17640 49
800 x 700 15 30.3 20 32. 2 482 17 36 5600 2016 0 56
1000 x 700 15 34.9 20 36.8 603 2171 7000 25200 70
1200 x 700 15 40.6 20 42.6 723 2603 8,400 3024 0 84
1400 x 700 15 45.7 20 47. 7 844 3039 9800 35280 98
1600 x 700 15 51.0 20 52.9 964 3471 11 20 0 40320 112
*
Installed according to the instructions
20
H
20
220
250
20
20
B
104
Figure 7. Dimensions, WISE Damper rectangular and WISE Damper rectangular with spring return.
Installation – rectangular design
Dimension B in the figure and table below is found in the table “Rectangular design” to the left.
NOTE! Damper spindles must be installed horizontally.
Straight section before WISE Damper in rectangular ducts
Type of disruption
E (m
2
=5%) E (m2=10%)
One 90° bend E = 3 x B E = 2 x B
T piece E = 3 x B E = 2 x B
Figure 5. Straight section requirements, rectangular ducts.
Figure 6. Straight section requirements, rectangular WISE Damper and sound attenuator with baffle. Installation with straight section applies both to supply and extract air.
1 = Rectangular WISE Damper. 2 = Straight duct 500 mm. 3 = Sound attenuator with baffle.
Straight section before/after WISE Damper – sound attenuator with baffle
E
H
B
E
H
B
1
2
3
WISE Damper
4
Swegon reserves the right to alter specications. 20180620
Figure 8. WISE Damper
1. WISE SMA (Sensor Module Advanced), accessory
2. Damper motor
3. Cover
4. WISE CU (Controller Unit)
5. Measuring tubes
6. Temperature sensor
1 (PS)
2
1 (PE)
2
Modbus RJ12
Modbus RJ12
Figure 10. Constant pressure regulation. WISE Damper can be used to maintain a constant pressure, supplement with WISE DPS Modbus.
1. WISE Damper
2. WISE DPS Modbus
1 2
3 4 5
6
WISE SMA (accessory)
24 V AC Valve actuator 1
& 2 (accessory)
Temp. sensor
Pressure
tube blue
Pressure tube red
24 V DC
U
Ground
Y
Figure 9. WISE Damper, connections.
Connections
LED - Explanation
Not paired
Colour Typ e
Energized White Permanent
Selected in TuneWISE White Flashing, fast
Prepared to be added to the system
White Flashing, slowly
To be added to the system
White Flashing, fast for 5 s
Paired
Colour Typ e
Normal operation Green Permanent
Stroke calibration Green Flashing
Restart Blue Permanent for 10 s
Initiation Blue Flashing
Boosted max. flow Orange Permanent
Boosted min. flow Orange Permanent
Comfort alarm Red Permanent
Function alarm Red Flashing
Emergency mode Green/Red Alternating
Test mode Green/Orange Alternating
WISE DPS Modbus (accessory)
LED, see table “LED -
Expla nat io n”
RJ9
R12
RJ45
5
20180620 Swegon reserves the right to alter specications.
WISE Damper
Use
Use TuneWISE for commissioning. Commissioning must be performed by qualified and trained WISE service engineers.
Use SuperWISE for settings, reading alarms, etc. refer to the documentation for SuperWISE II / SuperWISE II SC.
Trouble shooting
The product is not shown in the system:
• Make sure that the product is energized. (e.g. diode).
• Make sure that the product is paired.
• Make sure the product is in the right radio network.
The product shows incorrect/no air flow/pressure
• Make sure that the product is installed according to the recommended distance to disruptions, see “Installa­tion”.
• Check that there is air flow/pressure.
• Make sure that the product is correctly oriented in terms of air direction. The air flow must follow the instructions on the product.
• Check that the measuring tube is mounted correctly, plus to plus (red), minus to minus (blue).
• Check that the measuring tubes are undamaged.
The product does not regulate the air flow/pressure
• Check that the damper motor has not become detached from the damper spindle.
• Check that the damper motor works by pressing in the motor’s release button, turn the damper spindle, release the release knob and then see whether the damper motor starts to move.
• Check that the damper motor is connected to the right input.
The product shows incorrect/no temperature
• Make sure that the temperature sensor does not hang outside the product.
• Check that the temperature sensor is connected to the right input.
The product shows incorrect/no VOC
• Make sure that this product is delivered with this type of sensor, this is evident from the product label where it states “SMA”.
• Make sure that the VOC sensor does not hang outside the product.
• Check that the VOC sensor is connected to the right input.
Cleaning
Ideally the product should be cleaned in connection with the cleaning of the rest of the ventilation system.
Cleaning of electrical components
• If needed, use a dry cloth to clean the components.
• Never use water, detergent and cleaning solvent or a vacuum cleaner.
External cleaning
• If necessary use tepid water and a well-wrung cloth.
• Never use detergent and cleaning solvent or a vacuum cleaner.
Internal cleaning
• When cleaning the ventilation system, the product must be dismantled if there are no cleaning hatches close to the product.
• Cleaning equipment such as whisks and the like must not be fed through the damper.
• If necessary remove dust and other particles that can be present in the product.
• Never use detergent and cleaning solvent or a vacuum cleaner.
Service/maintenance
• The product does not require any maintenance, except for any cleaning when necessary.
• In connection with a service, mandatory ventilation inspection or cleaning of the ventilation system, check that the general condition of the products looks ok. Pay particular attention to the suspension, cables and that they sit firmly in place.
• It is not permissible to open or repair electrical compo­nents.
• If you suspect that the product or a component is defective, please contact Swegon.
• A defective product or component must be replaced by an original spare part from Swegon.
Materials and surface treatment
All sheet-metal parts are galvanized sheet steel (Z275).
Disposal
Waste must be handled according to local regulations.
Product warranty
The product warranty or service agreement will not be in effect/will not be extended if: (1) the product is repaired, modified or changed, unless such repair, modification or change has been approved by Swegon AB; or (2) the serial number on the product has been made illegible or is missing.
WISE Damper
6
Swegon reserves the right to alter specications. 20180620
A
Replacement of WISE CU
Figure 17. Dismantle the cover on the motor shelf by pulling it out of the slot in the motor shelf.
Figure 18. Remove hoses and contactors from WISE CU. Unscrew 2 screws holding WISE CU in place (screw: PH1).
Figure 19.
1. Make holes in the casing on the new WISE CU for the screws with e.g. a knife tip.
2. Screw the WISE CU on the motor shelf.
3. Connect hoses and contactors from WISE CU, see “Connection”.
4. Insert the lock in the slot until it “snaps into place”.
5. Apply the new supplied QR codes over the existing QR codes on the product.
Supplementary installation
WISE SMA
1 2 3
Figure 11. Dismantle the sealing plug from tubular damper casing.
Figure 13. Tighten the counter nut against the tubular damper casing so that it presses the seal against the tubular damper casing.
Replacing the damper motor
Figure 15. Dismantling the damper motor.
1. Disconnect the cable.
2. Loosen the nuts on the spindle clamp (nuts: 8mm).
3. Dismantle 2 screws for the locking strip (screws: TX20).
4. Lift off the damper motor and spindle adapter.
Figure 16.
1. Fit the damper motor and spindle adapter on the damper spindle.
2. Fit the locking strip.
3. Make sure that the cut-out on the spindle is as on A (damper is then closed).
4. Spindle clamp on the damper motor must be directed towards 0, see B.
5. Tighten nuts on the spindle clamp.
6. Connect the cable.
Figure 14. WISE SMA installed. Electrical con­nection see “Connection”.
B
Figure 12. Install WISE SMA in the following order:
1. Counter-nut
2. Flat washer
3. Seal
4. Screw WISE SMA on the shelf (screw: TX20).
7
20180620 Swegon reserves the right to alter specications.
WISE Damper
Changing the running direction
of the spring return actuator
Figure 28.
1. Standard installation of the spindle clamp.
2. Dismantle the circlip and spindle clamp.
Replacing the spring return
actuator - Rectangular damper
Figure 20. Dismantling the spring return actuator.
1. Disconnect the cable.
2. Loosen the nuts on the spindle clamp (nuts 8 mm).
3. Dismantle 2 screws for the locking strip (screws TX20).
4. Lift off the motor.
Figure 22. For damper position “Normally open” the damper should be open during installation of the spring return actuator. The spindle clamp then sits as shown above. NOTE! The spindle clamp needs to be moved to the rear of the motor, see figure 28-30.
Replacing the spring return
actuator - Circular damper
Figure 25. Damper blade position “Normally closed”.
Figure 23. Install the new spring return actuator.
1. Fit the motor on the damper spindle.
2. Fit the locking strip.
3. Make sure that the spindle clamp on the motor is fitted according to one of the designs shown in figure 21 or 22.
4. Tighten the nuts on the spindle clamp.
5. Connect the cable.
Figure 21. For damper position “Normally closed” the damper should be closed during installation of the spring return actuator. The spindle clamp then sits as shown above.
Figure 24. Dismantling the spring return actua­tor.
1. Disconnect the cable.
2. Loosen the nuts on the spindle clamp (nuts 8 mm).
3. Dismantle 2 screws for the locking strip (screws TX 20).
4. Lift off the motor and spindle adapter.
Figure 26. Damper blade position “Normally open”.
Figure 27. Install the new spring return actuator.
1. Fit the motor and spindle adapter on the damper spindle.
2. Fit the locking strip.
3. Makes sure that the position of the damper blade is correct, see figure 25 or 26. NOTE! The spindle clamp is always fitted in the direction as set out above on the circular damper.
4. Tighten the nuts on the spindle clamp.
5. Connect the cable.
Figure 30.
1. Fit the spindle clamp and circlip as shown above.
2. Mounted with the spindle clamp. NOTE! The signal must be inverted in software.
Figure 29. Reverse the motor.
1
2
3
4
1
2
3
4
1
2
1
2
Move to the right
Move to the left
WISE Damper
8
Swegon reserves the right to alter specications. 20180620
Declaration of Conformity
Swegon AB hereby affirms that
WISE Damper with integrated radio, complies with the essential characteristic demands and relevant regulations specified in the following directives: 2006/42/EC (MD), 2014/53/EU (RED) and 2011/65/EU (RoHS2):
The following standards have been observed:
EN ISO 12100:2010
Safety of machinery - General principles for design - Risk assessment and risk mitigation
EN 60204-1:2006
Safety of machinery - Electrical equipment of machines - Par t 1: Generic standards
EN 60730-1:2011
Automatic electrical controls for household and similar use - Part 1 Generic standards
EN 60730-2-14:2009
Automatic electrical controls for household and similar use - Part 2 Particular require­ments for electric actuators
IEC 60529:1992+A2:2013
Degrees of protection provided by enclosures (IP code)
EN 61000-6-2:2007
Electromagnetic compatibility (EMC). Generic standards. Immunity for industrial environ­ments
EN 61000-6-3:2007
Electromagnetic compatibility (EMC). Generic standards. Emission standard for residential, commercial and light-industrial environments
EN 300328 V1.9.2, V1.9.1, V1.8.1
Electromagnetic compatibility and Radio spec­trum Matters (ERM) - Wideband Transmis­sion systems - Data transmission equipment operating in the 2.4 GHz ISM band and using spread spectrum modulation techniques
Person responsible for this declaration:
Name: Ingvar Hagström, Factory Manager Tomelilla
Address: Industrigatan 5, 273 21 Tomelilla, Sweden
Date: 170131
This declaration is applicable only if the product has been installed according to the instructions in this document and if no modifications or changes have been made on this product.
References
www.swegon.com
Building Materials Declaration
WISE Damper product data sheet
WISE System Guide
SuperWISE II / SuperWISE II SC User Manual
WISE Project Planning Guide VS & Cooling, Electric & Control and Ventilation
Technical data
Output (ERP): 50 mW
Frequency band: 2.45 GHz, IMS band
(2400 --2483 MHz)
Temperature sensor: 0 - 50°C ± -0.5°C
Pressure sensor: 0 - 300 Pa
With SMA
VOC sensor 450 - 2000 ppm
RH sensor: 0 - 100 RH%
IP class: IP20
Corrosivity class: C3
Pressure class: A
Air tightness class, casing: C
Air tightness class circular damper, closed:
4
Air tightness class rectangular damper, closed:
3
Running time open/close (90°): 120 s
Spring return actuator, running time electricity (90°):
120 s
Return time spring: max. 20 s (90°)
Ambient temperature
Operation: 0 – 50°C
Storage: -20 – +50°C
RH: 10 - 95%
(non-condensing)
CE marking: 2016 / 42 / EC (MD )
2014 / 53 / EU (RED)
2011/65/EU (RoHS)
Variant Motor
VA
Default
+1 valve actuator
+2 valve actuator
Normal
5 Nm
8 15 2210 Nm
15 N m
Spring return
5 Nm
12 19
10 Nm 20 Nm 16 23
Electrical data
Power supply: 24V AC ±15% 50 - 60Hz
Connections pipe dim.
Power:
Screw terminal max. 2.5mm
2
Valve actuator:
Push-in spring force connections,
max. 1.5 mm
2
Max. power consumption: See table below
Loading...