Swegon TBLZ-1-75 SILVER C Instructions Manual

GB.TBLZ75.150526
Instructions for the hand-held micro terminal of the fan motor control system, TBLZ-1-75 SILVER C
1. General
The hand-held micro terminal is used for setting the motor parameters of the SILVER C.
The hand-held micro terminal can be hung in the wall mounting supplied, See illustration below. Mount the wall mounting on a flat surface.
To lift the hand-held micro terminal out of the wall mount­ing, slide it upward and then draw it out.
3. Technical data
Supply voltage From junction box Modbus RTU 2 x RJ12/6/6-pole RS485 Enclosure class: IP21 Humidity 10 – 95 % - non-condensing Ambient temperature -30.. +50 °C (Storage)
0.. +40 °C (in operation) Dimensions 171 x 82 x 38.5 mm Weight 150 g
We reserve the right to alter specifications.
www.swegon.com 1
4. Function
The hand-held micro terminal communicates with the motor control system via Modbus commands.
Factory and user settings are stored in the control system. The settings are preserved in the memory even if the line voltage is switched off or if the hand-held micro terminal is removed.
If the hand-held micro terminal is not used for more than 10 minutes, the system automatically switches back to the main menu. This reduces the risk of unintentional entry of settings.
The possible settings and displays are shown in the table on the next page. Scrolling up and down in the menu is done by turning the adjusting knob on the hand-held micro terminal, and selections are entered by pressing on the adjusting knob. Modification of the selected values is done by turning the adjustment knob. Select "Exit" to leave the menu.
GB.TBLZ75.150526
Standard Modbus address is Address = 54. Standard baudrate is set to 38.4 Kbit/s.
The Modbus address and other motor parameters can be changed in the hand-held micro terminal.
The standard Modbus address and baudrate can be changed with the hand-held micro terminal in the follow­ing way: With the function selector switch (See illustration) set to ”0”, set the parameters to the required values with the hand-held micro terminal. When the new values have been set, set the function selector switch to position "1". This activates the user-preset parameters.
The hand-held micro terminal will not work if the baudrate is changed from the standard setting of 38.4 kBit/s and if the hand-held micro terminal is disconnected from contact "C".
If the standard baudrate is changed from 38.4 Kbit/s and the hand-held micro terminal is disconnected from its con­nection, it will only be possible to restart communication with the hand-held micro terminal if the function selector switch is set to position "0". The baudrate will then be set to 38.4 Kbit/s. If the function selector switch is subse­quently set to position "1", the user-preset parameters will be activated again.
2 www.swegon.com
We reserve the right to alter specifications.