Swegon TBLZ-1-66 Installation Instructions Manual

Page 1
GB.TBLZ66.110620
Swegon reserves the right to alter specifications.
www.swegon.com 1
1. General
The TBLZ-1-66 accessory is a control system incorporated into a control box. The control box is designed for installa­tion in connection with the GOLD air handling units.
The control box contains a Programmable Logic Control­ler system and its front panel has a control terminal with a display screen.
The buttons and display screen are used for entering set­tings and viewing readings for common functions.
2. Range of application
The TBLZ-1-66 control box is a control system for control­ling two parallel GOLD air handling units.
One GOLD air handling unit is selected as the Master, and the other unit is selected as the Slave.
The control box transmits set points to both air handling units. These set points then control each unit separately.
If the air handling units are to be regulated on a VAV basis and the duct pressure is to be kept constant, connect a standard pressure sensor to the GOLD unit that operates as the Master. The pressure readings are transmitted via the communication system to the control box and are processed there. This also applies to the external room temperature sensor and the CO
2
sensor, if one is used in
the system.
Conditions
Parallel control is possible for the size 04–80 GOLD air handling units.
The GOLD air handling units involved must be of the same size.
The air handling units are considered parallel if they are connected to a common duct system.
Both air handling units must be equipped with the same accessories, such as an air heater, air cooler, dampers, etc.
Installation instructions for the TBLZ-1-66 control box for controlling two air handling units (Twin Function) GOLD 04-80
3. Installation
The control box should be installed in connection with the GOLD unit selected as the Master.
It is advantageous if the control box panel and the hand­held micro terminal of the Master air handling unit are located in such a way that they can be operated and supervised from the same place.
4. Technical data
Enclosure class IP 66
Ambient temp. 0 - +50°C for a rel. hum. of 5 - 85% (non-condensing)
Weight 7 kg
Dimensions 380x300x220
(WidthxHeightxDepth)
Page 2
GB.TBLZ66.110620
Swegon reserves the right to alter specifications.
2 www.swegon.com
7. Description of functions
The ordinary control circuit card in the GOLD air handling units controls its respective functions, but obtains set points for certain functions of the control circuit card in the control box.
The type of temperature and fan regulation to be used are selected in the control panel of the control box.
All the other functions are set in the hand-held micro terminal on the GOLD air handling unit that is the opera­tional Master. The settings in the Master AHU are auto­matically copied over to the Slave AHU.
5. Electrical connections
The electrical connections are to be wired by a qualified electrician in accordance with local electrical safety regula­tions.
The supply voltage to the control box must be single­phase, 230 V, and the cable conductors must be con­nected to wiring terminals 101 (L) and 102 (N).
The control box must be connected to the control circuit card of the GOLD air handling unit with twisted-pair, shielded communication cables. Communication is con­ducted via Modbus RTU and the control circuit card of the control box is the communication Master.
The following wiring terminals must be connected as specified below:
Terminal in the control box Terminal in GOLD unit
401 28 in the Master AHU 402 27 in the Master AHU 403 28 in the Slave AHU 404 27 in the Slave AHU
6. Commissioning
Energize the control box and both GOLD air handling units.
Set the Modbus addresses for communication in both GOLD units.
In the hand-held micro terminal, go to communication below the Settings level.
Select EIA-485 and check under Protocol that Modbus RTU is selected.
Go to Settings and set the following parameters: Address 1 for the Master AHU and Address 2 for the Slave AHU. The speed should be 38,400; the parity should be “Even”; Stop bits should be 1. This applies to both GOLD air han­dling units
7.1 Temperature regulation:
ERS and Supply air regulation
ERS and supply air regulation are controlled in each GOLD unit. The settings in the control box are automatically transmitted over to the air handling units.
Extract air regulation.
The extract air controller is located inside the control box. The extract air controller transmits set points to the supply air controllers of the GOLD air handling units. The air handling units are then automatically set for supply air regulation.
The extract air controller in the control box receives values for extract air temperature from the Master AHU’s extract air temperature sensor or via communication from exter­nal extract air /room sensors connected to the Master AHU.
7.2 Fan regulation
Flow regulation
The total flow set on the control box panel is split equally and is transmitted to the flow controllers of the GOLD air handling units. The air handling units are then automati­cally set for flow regulation.
Pressure regulation
The pressure regulation controller is located inside the control box. The pressure controller controls how the air handling units operate by transmitting flow set points to both GOLD air handling units. The control circuit cards of the air handling units maintain constant airflow in both air handling units. The air handling units are then automati­cally set for flow regulation.
The standard pressure sensor of the GOLD units are used as duct pressure sensors in the common ducts. The duct pressure sensors are connected to the Master AHU’s con­nections marked Internal EIA-485.
The control box controller receives pressure values from the Master AHU via the communication system.
Demand regulation
If demand regulation is used, the Master AHU’s extract air fan is controlled via signals on wiring terminals, inputs 32-33. The supply air fan of the Master AHU is control­led in response to the extract airflow as a Slave. The Slave AHU copies the current flow regulation values and set points from the Master air handling unit. The air handling units are then automatically set for their respective func­tions.
Page 3
GB.TBLZ66.110620
Swegon reserves the right to alter specifications.
www.swegon.com 3
Settings
GOLD RX PARALLEL 2010 10/12 13:40
Manual Stop
Stop
8. Control panel and menus
8.1 Control panel buttons
The A buttons under the display screen, are used for navi­gating between the various menus. Text along the lower edge of the display indicates the current function of the buttons.
The B button is the Enter button. Press Enter to change a function or a value at which the cursor is pointing. The value can then be changed by selecting a new function, or by entering a new value using the number buttons. The Enter button confirms and also executes the entered selec­tion or adjusted value.
The C buttons are used for moving the cursor in the dis­play.
The D buttons are number buttons and are used for enter­ing values.
8.2 Menus in the display
8.2.1 Main menu
The uppermost text line shows the type of air handling unit, date and time of day.
The second and third lines show the current operating mode of the Master air handling unit. Low speed, High speed, Start up, etc.
The fourth line shows the operational setting of the Master air handling unit. Stop, Manual operation or Auto­matic operation.
8.2.2 Settings menu
The buttons under the display are used for navigating to the desired function/menu image.
MAIN: Return to the Main menu.
TEMPERATURE: Reading/setting temperatures.
FLOW/PRESS: Reading/setting flows/pressures.
INSTALLAT: Selection of temperature and flow
functions. Requires logging in.
A
B
CD
Set
GOLD RX PARALLEL 2010 10/12 13:40
Manual Stop
Stop
Set
LOG OUT
TEMPE
RATURE
LOG
IN
INST
ALLAT
FLOW/
PRESSURE
MAIN
Page 4
GB.TBLZ66.110620
Swegon reserves the right to alter specifications.
4 www.swegon.com
LOG IN: Opens the Authorization level. Requires that you enter a code.
LOG OUT: Closes the Authorization level.
8.2.3 Temperature PREV: For returning to the next higher level.
READ: For reading temperatures.
SET: For setting temperature set points.
Readings
For reading current temperatures in the Master unit (Unit
1) and the Slave unit (Unit 2).
The first value for SA shows the current supply air tem­perature of each air handling unit, the second value shows the current supply air set point of each air handling unit.
The first value for EA shows the current extract air tem­perature of each air handling unit, the second value shows the current extract air set point (for extract air regulation) in the control box.
The value for OUTDOORS shows the current outdoor tem­perature of the relevant air handling unit.
PREV: For returning to the next higher level.
Setting PREV: For returning to the next higher level.
CTRL: For setting the temperature controller parameters.
Temperature controller PREV: For returning to the next higher level.
Temperature
PREV. READ SET
Temperature AHU 1 AHU 2 SA 22.4°C/30.0°C 26.7°C/30.0°C EA 21.9°C/23.0°C 27.1°C/23.0°C OUTD 22.2°C 27.4°C
PREV.
Temperature set points
ROOM 23.0°C Min. limit. 14.0°C Max. limit. 30.0°C
PREV.
For setting of extract air temperature set points.
PREV. REG.
For setting of supply air temperature set points.
Temperature set points Supply air 30.0°C
PREV.PREV. REG.
For setting the temperature controller parameters:
Prop factor Xp/Fp 50.00 I-time 60.0 sec. Ctrl. deviation 10.7 K Output signal 29.96°C
PREV.PREV.
Page 5
GB.TBLZ66.110620
Swegon reserves the right to alter specifications.
www.swegon.com 5
REG. EAREG.
SA
8.2.4 Flow/Pressure PREV: For returning to the next higher level.
READ: For reading the current flows/pressures.
SET: For setting flow/pressure set points.
Readings
For reading the current flows or pressures.
In the display image to the right, SA is shown as pressure regulation and EA as flow regulation.
The first value for SA shows the current pressure; the second value shows the current pressure set point.
The first value for EA shows the total airflow from both air handling units; the second value shows the current flow set point.
PREV: For returning to the next higher level.
Setting
For setting the desired pressure in the common duct, or for setting the total airflow from both air handling units.
In the display image to the right, SA is shown as pressure regulation and EA as flow regulation.
If flow regulation is used, the control system of the control box splits the airflow into two equal set points, one for each air handling unit.
PREV: For returning to the next higher level.
CTRL. SA: For setting the parameters for the supply
air fan flow controller.
CTRL. EA: For setting the parameters for the extract
air fan flow controller.
Flow/Pressure
PREV. READ SET
SA -142 Pa/ 200Pa EA 01/s/ 01/s
PREV. Flow/Pressure
SA 200 Pa/ EA low 300 l/s SA max 1,000 l/s EA high 600 l/s EA min 3,500 l/s EA max 24,000 l/s
PREV. Pressure setting
For setting the flow controller parameters.
Prop factor Xp/Fp 50.00 I-time 30.0 sec. D-time 1.0 sec. Ctrl. deviation 34.2 K Output signal 1,500 l/s
PREV.PREV.
For setting the desired pressure in the duct, or for setting the total air­flow from both air handling units.
Page 6
GB.TBLZ66.110620
Swegon reserves the right to alter specifications.
6 www.swegon.com
8.2.5 To select temperatures and flow functions
The operator must log in onto Authorization level 3 in order to be able to change the functions for temperature or flow regulation, see Section 8.2.6.
PREV: For returning to the next higher level.
FUNCTIONS: For setting temperatures and flow func-
tions.
COMMUNICAT: For setting the parameters for commu-
nication with a main control system.
For selecting temperatures and fan functions.
The form of regulation for temperature regulation or flow/ pressure regulation can be selected by moving the cursor to the relevant control configuration. When you press the Enter button, a new window appears offering possible alternatives. Select the desired type of regulation and confirm by pressing the Enter button.
BACK: For returning to the next higher level.
To set the communication means with the main control system
For selecting the communication system.
PREV: For returning to the next higher level.
Ethernet: For setting the Ethernet parameters.
Modbus: For setting the Modbus parameters.
To set Ethernet communication
To set the IP-address, netmask and gateway for Ethernet communication.
PREV: For returning to the next higher level.
To set Modbus communication
PREV: For returning to the next higher level.
DIAGN.: Diagnostic of internal Modbus communi-
cation
FUNC
TIONS
COMMU
NICATPREV.
Temp.reg. Flow/Pressure ERS Regulation 1 SA fan Flow regulation EA fan Flow regulation
BACK
Communication
Mod-
bus
Ether
net
PREV.
IP address: 192.168.000.001 Netmask: 255.255.255.000 GateWay: 000.000.000.000
PREV.
PREV.
DIAGN.
Page 7
GB.TBLZ66.110620
Swegon reserves the right to alter specifications.
www.swegon.com 7
NEXT
Station no. 2 Number of items 2 Function 2 Error no. 0 Base addr. 6 Cycle time 4 File addr. 0
PREV.
GOLD 1 conn. GOLD 2 conn. GOLD 1 OK GOLD 2 OK
Diagnostic of internal Modbus communication
PREV: For returning to the next higher level.
NEXT: Internal system diagnostic.
8.2.6 To log In/Out
You must log in at Authorization level 3 in order to obtain authorization for changing temperature and flow regula­tion functions.
Press the “Log In” button, enter the digits: 1111. Then press the Enter button. A confirmation will then appear on the screen: “OK, level is 3”.
Your authorization will last for 5 minutes; then you will be automatically logged out.
To log out manually, press the “Log Out” button.
Initialized 0 Length error 0 Diagnostic 0 Parameter error 0 Diagnostics 0 Start error 0 Range error 0 Value error 0 Media error 0
PREV. Server
Settings
LOG OUT
TEMPE
RATURE
LOG
IN
INST
ALLAT
FLOW/
PRESSURE
MAIN
Password:
****
Page 8
GB.TBLZ66.110620
Swegon reserves the right to alter specifications.
8 www.swegon.com
Loading...